24-03 Fire Mode Min Reference
Default value:
Size related
Setup:
All setups
Data type:
Int32
Minimum value to the reference/setpoint (limiting the sum of values in parameter 24-05 Fire Mode Preset Reference and value of signal
on input selected in parameter 24-06 Fire Mode Reference Source). If running in open loop when fire mode is active, the unit is selected
by the setting parameter 0-02 Motor Speed Unit. For closed loop, select the unit in parameter 24-02 Fire Mode Unit.
© 2024.10
2
Description
Parameter type:
Conversion index:
Change during operation:
AU430028034214en-001901 / 130R0310 |
Parameter Descriptions
Range, -999999.999 - par.
24-04 FireModeMaxReference
-3
True
541