Programming Guide | VLT® HVAC Drive FC 102
Set the threshold value which defines a high warning S2 for load envelope monitoring. When the value of the monitored value exceeds
the threshold specified in the parameter for the duration of time specified in warning S2 time, a warning S2 high is triggered. The
parameter contains 20 index values which can be used to manually configure Load Warning S2 High Threshold for each individual speed
point.
46-32 Warning S1 High
Default value:
0%
Setup:
All setups
Data type:
Uint16
Set the threshold value which defines a high warning S1 for load envelope monitoring. When the value of the monitored value exceeds
the threshold specified in the parameter for the duration of time specified in warning S1 time, a high warning S1 is triggered. The
parameter contains 20 index values which can be used to manually configure Load Warning S1 High Threshold for each individual speed
point.
46-33 Warning S1 Low
Default value
0%
Setup:
All setups
Data type:
Uint16
Set the threshold value which defines a low S1 warning for load envelope monitoring. When the value of the monitored value exceeds
the threshold specified in the parameter for the duration of time specified in warning S1 time, a low S1 warning is triggered. The
parameter contains 20 index values which can be used to manually configure Load Warning S1 Low Threshold for each individual speed
point.
46-34 Warning S2 Low
Default value:
0%
Setup:
All setups
Data type:
Uint16
Set the threshold value which defines a low S2 warning for load envelope monitoring. When the value of the monitored value exceeds
the threshold specified in the parameter for the duration of time specified in warning S2 time, a low S2 warning is triggered. The
parameter contains 20 index values which can be used to manually configure Load Warning S2 Low Threshold for each individual speed
point.
46-35 Alarm Low
Default value:
0%
Setup:
All setups
Data type:
Uint16
Set the threshold value which defines a low alarm for load envelope monitoring. When the value of the monitored value exceeds the
threshold specified in the parameter for the duration of time specified in alarm time, a low alarm is triggered. The parameter contains 20
index values which can be used to manually configure Load Alarm Low Threshold for each individual speed point.
680
| © 2024.10
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter Descriptions
Range, 0 - 200%, Array [20]
-2
True
Range, 0 - 200%, Array [20]
-2
True
Range, 0 - 200%, Array [20]
-2
True
Range, 0 - 200%, Array [20]
-2
True
AU430028034214en-001901 / 130R0310
Need help?
Do you have a question about the VLT FC 102 and is the answer not in the manual?