Programming Guide | VLT® HVAC Drive FC 102
Scale the maximum output of terminal X49/11. For example, the scaling is done for the following reasons:
To provide an output value lower than the maximum possible value.
l
To provide the full signal range using output values lower than a certain limit.
l
To know more about how this parameter works, see parameter 6-52 Terminal 42 Output Max Scale.
Example:
Parameter 36-05 Terminal X49/11 Mode = [0] Voltage 0–10 V
l
Parameter 36-60 Terminal X49/11 Analogue Output = [100] Output Frequency.
l
Parameter 4-19 Max Output Frequency = 200 Hz.
l
Example case 1: 5 V maximum output is required when the output frequency is 200 Hz. Parameter 36-63 Terminal X49/11 Max. Scale x
100% = 200%.
Example case 2: 10 V maximum output is required when the output frequency is 150 Hz (75% of the maximum output frequency).
Parameter 36-63 Terminal X49/11 Max. Scale = 75%.
36-64 Terminal X49/11 Bus Ctrl
Default value:
0%
Setup:
All setups
Data type:
N2
This parameter contains the output level of terminal X49/11 if the terminal is controlled by bus.
36-65 Terminal X49/11 Timeout Preset
Default value:
0%
Setup:
1 setup
Data type:
Uint16
The drive sends the value of this parameter to the output terminal when the terminal is controlled by a fieldbus and a timeout is
detected.
Parameter Group 40-** Special Settings
6.32
40-1* Aux. Functions Control
6.32.1
40-10 Kin. Back-up UdcRef
Default value:
Size related
Setup:
All setups
Data type:
Uint16
Set DC-link voltage for kinetic backup mode. To set a higher DC-link voltage for riding through an unbalanced fault, set parameter 14-10
Mains Failure to [4] Kinetic back-up and leave parameter 40-14 Mains Loss Duration as set. If ride through is not required, set parameter
14-10 Mains Failure to either [1] Ctrl. ramp-down, [2] Ctrl. ramp-down, trip, or [5] Kinetic back-up, trip.
40-11 Kin. Back-up Integral Time
Default value:
Size related
642
| © 2024.10
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Parameter Descriptions
Range, 0 - 100%
0
True
Range, 0 - 100%
0
True
Range, 300 - 1080 V
0
True
Range, 0.001 - 1000 s
AU430028034214en-001901 / 130R0310