Programming Guide | VLT® HVAC Drive FC 102
Disables the live zero monitoring, for example, if the analog outputs are used as part of a decentral I/O system (when an analog output
does not fulfill any control function, but feeds a data storage device).
Option
Name
[0]
Disabled
[1]*
Enabled
6.8.5
6-4* Analog Input X30/12
Use the parameters in this group for configuring the scale and limits for analog input 4 (X30/12) in VLT® General Purpose I/O MCB 101.
6-40 X30/12 Low Voltage
Default value:
0.07 V
Setup:
All setups
Data type:
Int16
Sets the analog input scaling value to correspond to the low reference feedback value set in parameter 6-44 Term. X30/12 Low Ref./
Feedb. Value.
6-41 Terminal X30/12 High Voltage
Default value:
10 V
Setup:
All setups
Data type:
Int16
Sets the analog input scaling value to correspond to the high reference feedback value set in parameter 6-45 Term. X30/12 High Ref./
Feedb. Value.
6-44 Term. X30/12 Low Ref./Feedb. Value
Default value:
0
Setup:
All setups
Data type:
Int32
Sets the analog output scaling value to correspond to the low voltage value set in parameter 6-40 Terminal X30/12 Low Voltage.
6-45 Term. X30/12 High Ref./Feedb. Value
Default value:
100
Setup:
All setups
Data type:
Int32
Sets the analog input scaling value to correspond to the high voltage value set in parameter 6-41 Terminal X30/12 High Voltage.
198
| © 2024.10
Description
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter Descriptions
Range, 0 - par. 6-41 V
-2
True
Range, par. 6-40 V - 10 V
-2
True
Range, -999999.999 -
999999.999
-3
True
Range, -999999.999 -
999999.999
-3
True
AU430028034214en-001901 / 130R0310