Programming Guide | VLT® HVAC Drive FC 102
30-21 High Starting Torque Current [%]
Default value:
Size related
Setup:
All setups
Data type:
Uint32
Set the high starting current that should be applied for the time specified in parameter 30-20 High Starting Torque Time. The increased
current will improve the starting torque and starting performance in demanding applications. The high starting torque current is valid
for VVC+ and flux in speed open loop. The parameter can be used with the following motors:
SPM
l
IPM
l
SynRM
l
PMaSynRM
l
30-22 Locked Rotor Protection
Default value:
[0] Off
Setup:
All setup
Data type:
Uint8
Available for PM motors only, in flux sensorless mode and VVC+ open-loop mode.
Option
Name
[0]*
Off
[1]
On
30-23 Locked Rotor Detection Time [s]
Default value:
Size related
Setup:
All setups
Data type:
Uint8
Time period for detecting the locked rotor condition. A low parameter value leads to faster detection.
30-24 Locked Rotor Detection Speed Error [%]
Default value:
25%
Setup:
All setups
Data type:
Uint32
Detects locked rotor condition for SPMSM at high speed.
© 2024.10
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Description
Protects the motor from the locked rotor condition. The control
algorithm detects a possible locked rotor condition in the motor
and trips the drive to protect the motor.
Parameter type:
Conversion size
Change during operation:
Parameter type:
Conversion index:
Change during operation:
AU430028034214en-001901 / 130R0310 |
Parameter Descriptions
Range, 0 - 200.0%
-1
True
Option
True
Range, 0.05 - 1 s
-2
True
Range, 0 - 100%
-1
True