Programming Guide | VLT® HVAC Drive FC 102
Sets up the filter mask for PCD 3. When operating in COS (change-of-state), it is possible to filter out bits in PCD 3 that should not be sent
if they change.
10-23 COS Filter 4
Default value:
0
Setup:
All setups
Data type:
Uint16
Sets up the filter mask for PCD 4. When operating in COS (change-of-state), it is possible to filter out bits in PCD 4 that should not be sent
if they change.
6.12.4

10-3* Parameter Access

10-30 Array Index
Default value:
0
Setup:
2 setups
Data type:
Uint8
View array parameters. This parameter is only valid when a VLT® DeviceNet MCA 104 is installed.
10-31 Store Data Value
Default value:
[0] Off
Setup:
All setups
Data type:
Uint8
This parameter is used to activate a function that stores all parameter values in the non-volatile memory, this retaining changed
parameter values at power-down.
Option
Name
[0]*
Off
[1]
Store edit setup
[2]
Store all setups
10-32 Devicenet Revision
Default value:
0
Setup:
All setups
Data type:
Uint16
The DeviceNet revision number. This parameter is used for EDS file creation.
268
| © 2024.10
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Description
Deactivates the non-volatile storage function.
Stores all parameter values from the active setups in the non-
volatile memory. The selection returns to [0] Off when all values
have been stored.
Stores all parameter values for all setups in the non-volatile
memory. The selection returns to [0] Off when all parameter
values have been stored.
Parameter type:
Conversion index:
Change during operation:
Parameter Descriptions
Range, 0 - 65535
0
False
Range, 0 - 255
0
True
Option
True
Range, 0 - 65535, Array 2
0
True
AU430028034214en-001901 / 130R0310

Advertisement