Programming Guide | VLT® HVAC Drive FC 102
Option
Name
[20]
N2 Override release
[27]
Forced stop and trip
[30]
Warning only
8-05 End-of-Timeout Function
Default value:
[1] Resume set-up
Setup:
1 setup
Data type:
Uint8
Select the action after receiving a valid control word following a timeout. This parameter is active only when parameter 8-04 Control
Word Timeout Function is set to:
[7] Setup 1
l
[8] Setup 2
l
[9] Setup 3
l
[10] Setup 4
l
Option
Name
[0]
Hold set-up
[1]*
Resume setup
8-06 Reset Control Word Timeout
Default value:
[0] Do not reset
Setup:
All setups
Data type:
Uint8
This parameter is active only when [0] Hold set-up has been selected in parameter 8-05 End-of-Timeout Function.
Option
Name
[0]*
Do not reset
[1]
Do reset
8-07 Diagnosis Trigger
Default value:
[0] Disable
© 2024.10
Description
Parameter type:
Conversion index:
Change during operation:
Description
Retains the setup selected in parameter 8-04 Control Word
Timeout Function and shows a warning until parameter 8-06
Reset Control Word Timeout toggles. Then the drive resumes its
original setup.
Resumes the setup that was active before the timeout.
Parameter type:
Conversion index:
Change during operation:
Description
Retains the setup specified in parameter 8-04 Control Word
Timeout Function, following a control word timeout.
Restores the drive to the original setup following a control word
timeout. The drive resets and then immediately reverts to the [0]
Do not reset setting.
Parameter type:
AU430028034214en-001901 / 130R0310 |
Parameter Descriptions
Option
True
Option
True
Option
223