Programming Guide | VLT® HVAC Drive FC 102
40-2* PM Motor Specific
6.32.2
40-26 Individual Currents
Default value:
[0] Off
Setup:
All setups
Data type:
Uint8
Select whether or not to use individual axis currents for induction calculations.
Option
Name
[0]*
Off
[1]
On
40-4* Extend. Alarm Log
6.32.3
Parameters in this group are array parameters, where up to 10 alarm logs can be viewed. [0] is the most recently logged data, and [9] is
the oldest. This parameter group provides details on reference, frequency, motor current, voltage, DC-link voltage, status, and control
word values at the time an alarm occurred.
40-40 Alarm Log: Ext. Reference
Default value:
0%
Setup:
All setups
Data type:
Int16
View the present reference value applied on impulse or analog basis when the logged event occurred.
40-41 Alarm Log: Frequency
Default value:
0 Hz
Setup:
All setups
Data type:
Int16
View the actual motor frequency when the logged event occurred.
40-42 Alarm Log: Current
Default value:
0 A
Setup:
All setups
Data type:
Int32
View the motor current measured when the logged event occurred.
40-43 Alarm Log: Voltage
Default value:
0 V
644
| © 2024.10
Parameter type:
Conversion index:
Change during operation:
Description
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Parameter Descriptions
Option
–
True
Range, -200 - 200%, Array [10]
-1
False
Range, -3276.8 - 3276.7 [Hz],
Array [10]
-1
False
Range, 0 - 10000 A, Array [10]
0
False
Range, 0 - 6000 V, Array [10]
AU430028034214en-001901 / 130R0310