Download Print this page

Process Control; Fault Code - Danfoss VLT FC 102 Programming Manual

Hvac drive
Hide thumbs Also See for VLT FC 102:

Advertisement

Programming Guide | VLT® HVAC Drive FC 102
Setup:
2 setups
Data type:
Uint16
Parameters can be edited via:
PROFIBUS
l
The standard RS485 interface
l
The LCP
l
Option
Name
[0]
Disabled
[1]*
Enabled

9-28 Process Control

Default value:
[1] Enable cyclic master
Setup:
2 setups
Data type:
Uint8
Process control (setting of control word, speed reference, and process data) is possible via either PROFIBUS or standard fieldbus, but not
both simultaneously. Local control is always possible via the LCP. Control via process control is possible via either terminals or fieldbus
depending on the settings in parameter 8-50 Coasting Select to parameter 8-56 Preset Reference Select.
Option
Name
[0]
Disable
[1]*
Enable cyclic master
9-44 Fault Message Counter
Default value:
0
Setup:
All setups
Data type:
Uint16
Indicates the number of fault events presently stored in parameter 9-45 Fault Code. The buffer capacity is maximum 8 error events. The
buffer and counter are set to 0 by reset or power-up.

9-45 Fault Code

Default value:
0
Setup:
All setups
Data type:
Uint16
This buffer contains the alarm word for all alarms and warnings that have occurred since the last reset or power-up. The buffer capacity is
maximum 8 error events.
© 2024.10
Conversion index:
Change during operation:
Description
Parameter type:
Conversion index:
Change during operation:
Description
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
AU430028034214en-001901 / 130R0310 |
Parameter Descriptions
False
Option
False
Range, 0 - 65535
0
True
Range, 0 - 0 N/A
0
True
251

Advertisement

loading
Need help?

Need help?

Do you have a question about the VLT FC 102 and is the answer not in the manual?

Save PDF