Programming Guide | VLT® HVAC Drive FC 102
Option
Name
[0]
Disabled
[1]*
Enabled
[2]
Password
0-43 [Reset] Key on LCP
Default value:
[1] Enabled
Setup:
All setups
Data type:
Uint8
Option
Name
[0]
Disabled
[1]*
Enabled
[2]
Password
[3]
Enabled without OFF
[4]
Password without OFF
[5]
Enable with OFF
[6]
Password with OFF
0-44 [Off/Reset] Key on LCP
Default value:
[1] Enabled
Setup:
All setups
Data type:
Uint8
This parameter is only available when a VLT® Bypass Option MCB 104 is installed in the drive.
Enable or disable the [Off/Reset] key.
© 2024.10
Description
Avoids accidental stop of the drive in auto-on mode.
Avoids unauthorized start in auto-on mode. If parameter 0-42
[Auto on] Key on LCP is included in the Quick Menu, then define
the password in parameter 0-65 Personal Menu Password.
Parameter type:
Conversion index:
Change during operation:
Description
No effect when [Reset] is pressed. Avoids accidental alarm reset.
Avoids unauthorized start in auto-on mode. If parameter 0-43
[Reset] Key on LCP is included in the Quick Menu, then define the
password in parameter 0-65 Personal Menu Password.
Resets the drive without setting it in Off mode.
Resets the drive without setting it in Off mode. A password is
required when pressing [Reset] (see option [2] Password).
Parameter type:
Conversion index:
Change during operation:
NOTICE
Parameter Descriptions
Option
–
True
Option
–
True
AU430028034214en-001901 / 130R0310 |
71
Need help?
Do you have a question about the VLT FC 102 and is the answer not in the manual?