Programming Guide | VLT® HVAC Drive FC 102
Option
Name
[0]*
Normal operation
[1]
Control card test
[2]
Initialisation
[3]
Boot mode
[4]
Initialize all parameters
[5]
Clear service logs
[6]
Clear param. log
14-24 Trip Delay at Current Limit
Default value:
60 s
Setup:
All setups
Data type:
Uint8
Enter the current limit trip delay in s. When the output current reaches the current limit (parameter 4-18 Current Limit), a warning is
triggered. When the current limit warning has been continuously present for the period specified in this parameter, the drive trips. To
run continuously in current limit without tripping, set the parameter to 60 s. Thermal monitoring of the drive remains active.
14-25 Trip Delay at Torque Limit
Default value:
60 s
Setup:
All setups
Data type:
Uint8
Enter the torque limit trip delay in s. When the output torque reaches the torque limits (parameter 4-16 Torque Limit Motor Mode and
parameter 4-17 Torque Limit Generator Mode), a warning is triggered. When the torque limit warning has been continuously present for
the period specified in this parameter, the drive trips. Disable the trip delay by setting the parameter to 60 s. Thermal monitoring of the
drive remains active.
14-26 Trip Delay at Inverter Fault
Default value:
Size related
Setup:
All setups
370
| © 2024.10
Description
Normal operation of the drive with the motor in the selected
application.
Remember to set switches S201 (A53) and S202 (A54) as specified
in the parameter description when performing a control card
test. Otherwise, the test fails.
Select this option to perform initialization. The drive resets
during the next power-up. This option does not clear the service
logs.
Select this option to reset all parameters (including bus and
motor parameters) to default values.
Save the log information using MCT 10 Set-up Software
before clearing the service logs.
Select this option and perform a power cycle to clear the log.
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Change during operation:
Parameter type:
Conversion index:
Parameter Descriptions
NOTICE
Range, 0 - 60 s
0
True
Range, 0 - 60 s
0
True
Range, 0 - 35 s
0
AU430028034214en-001901 / 130R0310