Programming Guide
VLT® HVAC Drive FC 102
Software Version 7.61
drives.danfoss.com |

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VLT FC 102 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Danfoss VLT FC 102

  • Page 1 Programming Guide VLT® HVAC Drive FC 102 Software Version 7.61 drives.danfoss.com |...
  • Page 3: Table Of Contents

    Programming Guide | VLT® HVAC Drive FC 102 Contents Contents Introduction C o n t e n t s Purpose of the Programming Guide Supported Software Versions Document Version Type Approvals and Certifications Safety Safety Symbols Safety Precautions Protection Mode Electrical Diagrams Wiring Diagram Input Polarity of Control Terminals...
  • Page 4: Set-Up

    Programming Guide | VLT® HVAC Drive FC 102 Contents Status View I 5.1.8.1 Status View II 5.1.8.2 Status View III 5.1.8.3 Parameter Setup 5.1.9 5.1.10 Quick Menu Key Functions 5.1.11 Programming in the Quick Setup Overview of Function Setups 5.1.12 5.1.12.1 Function Setups 5.1.12.2...
  • Page 5 Programming Guide | VLT® HVAC Drive FC 102 Contents 0-3* LCP Custom Readout 6.2.5 6.2.6 0-4* LCP Keypad 6.2.7 0-5* Copy/Save 0-6* Password 6.2.8 6.2.9 0-7* Clock Settings 6.2.10 0-9* Varia Parameter Group 1-** Load and Motor 6.3.1 1-0* General Settings Motor Selection 6.3.2 6.3.2.1...
  • Page 6 Programming Guide | VLT® HVAC Drive FC 102 Contents 5-0* Digital I/O Mode 6.7.1 6.7.2 5-1* Digital Inputs 6.7.3 5-3* Digital Outputs 5-4* Relays 6.7.4 6.7.5 5-5* Pulse Input 6.7.6 5-6* Pulse Outputs 5-8* I/O Options 6.7.7 6.7.8 5-9* Bus-controlled Parameter Group 6-** Analog In/Out 6.8.1 6-0* Analog I/O Mode...
  • Page 7 Programming Guide | VLT® HVAC Drive FC 102 Contents 10-2* COS Filters 6.12.3 6.12.4 10-3* Parameter Access 6.13 Parameter Group 11-** LonWorks 6.13.1 11-0* LonWorks ID 6.13.2 11-1* LON Functions 11-2* LON Param. Access 6.13.3 6.14 Parameter Group 12-** Ethernet 12-0* IP Settings 6.14.1 6.14.2...
  • Page 8 Programming Guide | VLT® HVAC Drive FC 102 Contents 15-1* Data Log Settings 6.17.2 6.17.3 Service Log 6.17.4 Clearing the Service Log Service Log Indication 6.17.5 6.17.6 Reading the Service Log Information 6.17.7 Alarms that Trigger a Service Log Record 15-2* Historic Log 6.17.8 6.17.9...
  • Page 9 Programming Guide | VLT® HVAC Drive FC 102 Contents 20-2* Feedback/Setpoint 6.20.3 6.20.4 20-3* Feedback Adv. Conversion 6.20.5 20-6* Sensorless 20-7* Autotuning 6.20.6 6.20.7 20-8* PID Basic Settings 6.20.8 20-9* PID Controller Parameter Group 21-** Ext. Closed Loop 6.21 6.21.1 Introduction to Parameter Group 21-** Ext.
  • Page 10 Programming Guide | VLT® HVAC Drive FC 102 Contents Parameter Group 25-** Cascade Controller 6.25 6.25.1 Introduction to Cascade Controller Parameters 25-0* System Settings 6.25.2 6.25.3 25-2* Bandwidth Settings 6.25.4 25-4* Staging Settings 25-5* Alternation Settings 6.25.5 6.25.6 25-8* Status 6.25.7 25-9* Service Parameter Group 26-** Analog I/O Option...
  • Page 11 Programming Guide | VLT® HVAC Drive FC 102 Contents 35-1* Temp. Input X48/4 6.30.2 6.30.3 35-2* Temp. Input X48/7 6.30.4 35-3* Temp. Input X48/10 35-4* Analog Input X48/2 6.30.5 6.31 Parameter Group 36-** Programmable I/O Option 36-0* I/O Mode 6.31.1 6.31.2 36-1* Analog Input X49/1 6.31.3...
  • Page 12 Programming Guide | VLT® HVAC Drive FC 102 Contents 46-0* General 6.36.2 6.36.3 46-1* Timing 6.36.4 46-2* Stator 46-3* Load 6.36.5 6.36.6 46-4* Sensor 1 6.36.7 46-5* Sensor 2 46-6* Sensor 3 6.36.8 6.36.9 46-7* Sensor 4 6.37 Parameter Group 47-** CBM Baseline Data 6.37.1 47-0* History 6.37.2...
  • Page 13: Introduction

    Programming Guide | VLT® HVAC Drive FC 102 Introduction Introduction Purpose of the Programming Guide This programming guide provides information required for setting up parameters in a drive. The guide contains the following main areas: How to use the local control panel (LCP) Detailed descriptions of all parameters Troubleshooting Supported Software Versions...
  • Page 14 Programming Guide | VLT® HVAC Drive FC 102 Introduction Table 1: Type Approvals and Certifications (continued) NOTICE The specific approvals and certification for the drive are on the nameplate of the drive. For more information, contact the local office or partner. For more information on UL 508C thermal memory retention requirements, refer to the section Motor Thermal Protection in the product- specific design guide.
  • Page 15: Safety

    Programming Guide | VLT® HVAC Drive FC 102 Safety Safety Safety Symbols The following symbols are used in Danfoss documentation. DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a hazardous situation which, if not avoided, could result in death or serious injury.
  • Page 16 Programming Guide | VLT® HVAC Drive FC 102 Safety WARNING UNINTENDED START When the drive is connected to AC mains, DC supply, or load sharing, the motor may start at any time. Unintended start during programming, service, or repair work can result in death, serious injury, or property damage. Start the motor with an external switch, a fieldbus command, an input reference signal from the local control panel (LCP), via remote operation using MCT 10 software, or after a cleared fault condition.
  • Page 17: Protection Mode

    Programming Guide | VLT® HVAC Drive FC 102 Safety Protection Mode Once a hardware limit on motor current or DC-link voltage is exceeded, the drive enters protection mode. Protection mode means a change of the PWM modulation strategy and a low switching frequency to minimize losses. This continues for 10 s after the last fault and increases the reliability and robustness of the drive while re-establishing full control of the motor.
  • Page 18: Electrical Diagrams

    Programming Guide | VLT® HVAC Drive FC 102 Electrical Diagrams Electrical Diagrams Wiring Diagram 91 (L1) (U) 96 3-phase (V) 97 92 (L2) power (W) 98 93 (L3) input (PE) 99 Motor Switch Mode DC bus 88 (-) Power Supply 89 (+) 10 V DC 24 V DC...
  • Page 19: Input Polarity Of Control Terminals

    Programming Guide | VLT® HVAC Drive FC 102 Electrical Diagrams To avoid that ground currents from both long cables and analog signals affect other groups, connect the digital and analog inputs and outputs separately to the common inputs (terminals 20, 55, and 39) of the drive. For example, switching on the digital input may disturb the analog input signal.
  • Page 20: Grounding Of Shielded/Armored Cables

    Programming Guide | VLT® HVAC Drive FC 102 Electrical Diagrams NPN (Sink) Digital input wiring Figure 3: NPN (Sink) Grounding of Shielded/Armored Cables See the section Grounding in the design guide for the correct termination of control cables. Figure 4: Grounding of Shielded/Armored Cables | ©...
  • Page 21: Other Wiring Examples

    Programming Guide | VLT® HVAC Drive FC 102 Other Wiring Examples Other Wiring Examples Start/Stop Terminal 18 = Parameter 5-10 Terminal 18 Digital Input, [8] Start. Terminal 27 = Parameter 5-12 Terminal 27 Digital Input, [0] No Operation (default [2] Coast inverse). Terminal 37 = Safe Torque Off (where available).
  • Page 22: Speed Up/Down

    Programming Guide | VLT® HVAC Drive FC 102 Other Wiring Examples Start Stop inverse Safe Stop Speed Start (18) Start (27) Figure 6: Pulse Start/Stop Speed Up/Down Terminals 29/32 = Speed up/down Terminal 18 = Parameter 5-10 Terminal 18 Digital Input, [9] Start (default). Terminal 27 = Parameter 5-12 Terminal 27 Digital Input, [19] Freeze reference.
  • Page 23: Potentiometer Reference

    Programming Guide | VLT® HVAC Drive FC 102 Other Wiring Examples +24V Par. 5-10 Par. 5-12 Par. 5-13 Par. 5-14 Figure 7: Speed Up/Down Potentiometer Reference Voltage reference via a potentiometer Reference source 1= [1] Analog input 53 (default). Terminal 53, Low Voltage = 0 V. Terminal 53, High Voltage = 10 V.
  • Page 24 Programming Guide | VLT® HVAC Drive FC 102 Other Wiring Examples Speed RPM 39 42 53 54 P 6-15 Ref. voltage P 6-11 10V Figure 8: Potentiometer Reference | © 2024.10 AU430028034214en-001901 / 130R0310...
  • Page 25: How To Program

    Programming Guide | VLT® HVAC Drive FC 102 How to Program How to Program The Graphical Local Control Panel Overview of the LCP 5.1.1 Easily program the drive via the local control panel (LCP). Status 1(0) 1234rpm 10.4A 43.5Hz 43.5Hz Run OK Quick Main...
  • Page 26: Lcd Display

    Programming Guide | VLT® HVAC Drive FC 102 How to Program NOTICE If start-up is delayed, the LCP shows the INITIALIZING message until it is ready. Adding or removing options can delay the start-up. LCD Display 5.1.2 The display has backlight and a total of 6 alpha-numeric lines. The display lines show the direction of rotation (arrow), the selected setup, and the programming setup.
  • Page 27: Lcp Keys

    Programming Guide | VLT® HVAC Drive FC 102 How to Program Flashing Red LED/Alarm: Indicates an alarm. Warn. Alarm Figure 11: Indicator Lights 5.1.3 LCP Keys Control keys The control keys are divided into functions. The keys below the display and indicator lights are used for parameter setup, including option of display indication during normal operation.
  • Page 28: Local Control Keys

    Programming Guide | VLT® HVAC Drive FC 102 How to Program Table 2: LCP Keys and Description (continued) LCP keys Description Navigation keys The 4 navigation keys are used to navigate between the different options available in Quick Menu, Main Menu, and Alarm Log. Press the keys to move the cursor. [OK] Press to select a parameter marked by the cursor and to enable the change of a parameter.
  • Page 29: Quick Transfer Of Parameter Settings Between Multiple Drives

    Programming Guide | VLT® HVAC Drive FC 102 How to Program Table 3: Local Control Keys and Description (continued) LCP keys Description [Auto On] Enables the drive to be controlled via the control terminals and/ or serial communication. When a start signal is applied on the control terminals and/or the bus, the drive starts.
  • Page 30 Programming Guide | VLT® HVAC Drive FC 102 How to Program Refer to to see the measurements that can be linked to each of the operating variables. When options are mounted, more Table 4 measurements are available. Define the links: Parameter 0-20 Display Line 1.1 Small.
  • Page 31 Programming Guide | VLT® HVAC Drive FC 102 How to Program Table 4: Units (continued) Operating variable Unit Parameter 16-30 DC Link Voltage Parameter 16-32 Brake Energy /s Parameter 16-33 Brake Energy Average °C Parameter 16-34 Heatsink Temp. Parameter 16-35 Inverter Thermal Parameter 16-36 Inv.
  • Page 32: Status View

    Programming Guide | VLT® HVAC Drive FC 102 How to Program Table 4: Units (continued) Operating variable Unit [Hz] Parameter 16-69 Pulse Output #27 [Hz] [Hz] Parameter 16-70 Pulse Output #29 [Hz] Parameter 16-71 Relay Output [bin] Parameter 16-72 Counter A Parameter 16-73 Counter B Parameter 16-74 Prec.
  • Page 33 Programming Guide | VLT® HVAC Drive FC 102 How to Program Status 1 (1) 799 RPM 7.83 A 36.4 kW 0.000 53.2 % Auto Remote Ramping Figure 12: Status View I 5.1.8.2 Status View II See the operating variables (1.1, 1.2, 1.3, and 2) shown in the following illustration. In the example, speed, motor current, motor power, and frequency are selected in the 1st and 2nd lines.
  • Page 34: Parameter Setup

    Programming Guide | VLT® HVAC Drive FC 102 How to Program Parameter Setup 5.1.9 The drive can be used for practically all assignments. The drive offers 2 programming modes: Main menu mode Quick menu mode Main menu mode provides access to all parameters. Quick menu mode enables operation of the drive by setting only a few basic parameters.
  • Page 35: Programming In The Quick Setup

    Programming Guide | VLT® HVAC Drive FC 102 How to Program Table 5: Selection of Parameter (continued) Parameter Setting [RPM] Parameter 4-11 Motor Speed Low Limit [RPM] [Hz] Parameter 4-12 Motor Speed Low Limit [Hz] [RPM] Parameter 4-13 Motor Speed High Limit [RPM] [Hz] Parameter 4-14 Motor Speed High Limit [Hz] [RPM]...
  • Page 36: Overview Of Function Setups

    Programming Guide | VLT® HVAC Drive FC 102 How to Program  The new ramp-down time is now set to 100 s. Overview of Function Setups 5.1.12 Function Setups 5.1.12.1 The Function Setups provide quick and easy access to all parameters required for most HVAC applications, including: Most VAV and CAV supply and return fans Cooling tower fans Primary pumps...
  • Page 37 Programming Guide | VLT® HVAC Drive FC 102 How to Program Press [▲] and [▼] to scroll down to Function Setups. 69.3% 5.20A 1(1) Quick Menus Q1 My Personal Menu Q2 Quick Setup Q3 Function Setups Q5 Changes Made  The Function Setups options appear Select Q3-1 General Settings and press [OK].
  • Page 38: Function Setups Q3-1 General Settings

    Programming Guide | VLT® HVAC Drive FC 102 How to Program 26.3% 5.82A 1(1) Analog Output 03.11 6-50 Terminal 42 Output (100) Output frequency Press [▲] and [▼] to select between the different options and press [OK] to select. 1(1) 43.4% 7.99A Analog Output...
  • Page 39: Function Setups Q3-2 Open-Loop Settings

    Programming Guide | VLT® HVAC Drive FC 102 How to Program Function Setups Q3-2 Open-loop Settings 5.1.12.4 Table 7: Q3-2 Open-loop Settings Q3-20 Digital reference Q3-21 Analog reference Parameter 3-02 Minimum Reference Parameter 3-02 Minimum Reference Parameter 3-03 Maximum Reference Parameter 3-03 Maximum Reference Parameter 3-10 Preset Reference Parameter 6-10 Terminal 53 Low Voltage...
  • Page 40 Programming Guide | VLT® HVAC Drive FC 102 How to Program Table 8: Q3-3 Closed-loop Settings (continued) Q3-30 Single zone int. setpoint Q3-31 Single zone ext. setpoint Q3-32 Multi zone/adv Parameter 20-81 PID Normal/Inverse Parameter 6-25 Terminal 54 High Ref./ Parameter 20-12 Reference/Feedback Unit Control Feedb.
  • Page 41: Function Setups Q3-4 Application Settings

    Programming Guide | VLT® HVAC Drive FC 102 How to Program Table 8: Q3-3 Closed-loop Settings (continued) Q3-30 Single zone int. setpoint Q3-31 Single zone ext. setpoint Q3-32 Multi zone/adv – – Parameter 20-20 Feedback Function – – Parameter 20-21 Setpoint 1 –...
  • Page 42: Main Menu Mode

    Programming Guide | VLT® HVAC Drive FC 102 How to Program Table 9: Q3-4 Application Settings (continued) Q3-40 Fan function Q3-41 Pump functions Q3-42 Compressor functions Parameter 22-44 Wake-up Ref./FB Parameter 22-26 Dry Pump Function Parameter 1-87 Trip Speed Low [Hz] Difference –...
  • Page 43: Parameter Selection

    Programming Guide | VLT® HVAC Drive FC 102 How to Program All parameters can be changed in the Main Menu. However, depending on the choice of configuration (parameter 1-00 Configuration Mode), some parameters can be hidden. For example, open loop hides all the PID parameters, and other enabled options make more parameter groups visible.
  • Page 44: Infinitely Variable Change Of Numeric Data Value

    Programming Guide | VLT® HVAC Drive FC 102 How to Program 113 RPM 1.78 A 1(1) Load depen. setting 1- 6* 1 - 60 Low speed load c ompensation 100% Figure 19: Changing a Data Value Press the [▲] [▼] keys to change the data value. [▲] increases the data value, and [▼] decreases the data value. Place the cursor on the value to save and press [OK].
  • Page 45: Value, Step By Step

    Programming Guide | VLT® HVAC Drive FC 102 How to Program Value, Step by Step 5.1.19 Certain parameters can be changed step by step. This applies to: Parameter 1-20 Motor Power [kW]. Parameter 1-22 Motor Voltage. Parameter 1-23 Motor Frequency. The parameters are changed both as a group of numeric data values and as numeric data values that are infinitely varying.
  • Page 46: The Numerical Control Panel

    Programming Guide | VLT® HVAC Drive FC 102 How to Program The Numerical Control Panel Overview of the Numerical LCP 5.2.1 Setup Status Quick Main Setup Menu Menu Warn. Alarm Hand Auto Reset Figure 23: NLCP Numeric display. Menu keys and indicator lights - changing parameters and switching between display functions.
  • Page 47 Programming Guide | VLT® HVAC Drive FC 102 How to Program Table 10: LCP Keys and Description LCP keys Description [Status] Indicates the status of the drive and/or the motor. If an alarm occurs, the NLCP automatically switches to status mode. Several alarms can be shown.
  • Page 48: Restoring Factory Default Settings

    Programming Guide | VLT® HVAC Drive FC 102 How to Program Local control keys: Local control keys are at the bottom of the control panel. Table 11: Local Control Keys and Description LCP keys Description [Hand On] Enables control of the drive via the LCP. [Hand On] also starts the motor, and it is now possible to enter the motor speed data with the navigation keys.
  • Page 49: Restoring Factory Default Settings Using Manual Initialization

    Programming Guide | VLT® HVAC Drive FC 102 How to Program NOTICE LOSS OF DATA Restoring default settings results in a loss of programming, motor data, localization, and monitoring records. To create a backup, upload data to the LCP before initialization. Press [Main Menu] twice to access parameters.
  • Page 50: Parameter Descriptions

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Parameter Descriptions Selecting Parameters The parameters are grouped into various parameter groups for easy selection of the correct parameter for optimal operation of the drive. Parameter descriptions and selections are shown in the LCP. Access the parameters by pressing [Quick Menu] or [Main Menu] on the LCP. The Quick Menu is used mainly for commissioning the unit at start-up by providing parameters necessary to start operation.
  • Page 51 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [28] Bras. Port Part of language package 4. [36] Slovenian Part of language package 3. [39] Korean Part of language package 2. [40] Japanese Part of language package 2. [41] Turkish Part of language package 4.
  • Page 52 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Select to show motor speed variables and parameters using motor speed (RPM). [1]* Select to show motor speed variables and parameters using output frequency (Hz). 0-03 Regional Settings Default value: –...
  • Page 53: Set-Up Operations

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions This parameter defines if the local reference unit should be shown as the motor shaft speed (in RPM/Hz) or as percent. Option Name Description [0]* As motor speed unit 0-1* Set-up Operations 6.2.3 Define and control the individual parameter setups.
  • Page 54 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Set-up 4 Multi Set-up Remote setup selections using digital inputs and the serial communication port. This setup used the settings from parameter 0-12 This Set-up Linked to. Stop the drive before making changes to open-loop and closed-loop functions.
  • Page 55 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Factory setup Cannot be changed. It contains the data set and can be used as a data source when returning the other setups to a known state. Set-up 1 Set-up 2 Set-up 3...
  • Page 56 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 0 RPM 0.00A 1(1) Set-up Handling 0-1* 0-12 This Set-up Linked to Setup 1 Figure 28: Setup 1 While still in setup 1, copy setup 1 to setup 2. Then set parameter 0-12 This Set-up Linked to to [2] Set-up 2. 0 RPM 0.00A 1(1)
  • Page 57: Lcp Display

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Int32 Change during operation: False View the setting of parameter 0-11 Edit Set-up for each of the 4 different communication channels. When the number is shown as a hex number, as it is in the LCP, each number represents 1 channel.
  • Page 58 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [17] Active fire mode setup [37] Display Text 1 Enables an individual text string to be written for showing in the LCP or to be read via serial communication. [38] Display Text 2 Enables an individual text string to be written for showing in the...
  • Page 59 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [1602] Reference % Total reference (sum of digital/analog/preset/bus/freeze reference/catch up and slow down) in percent. [1603] Status Word Present status word. [1605] Main Actual Value [%] View the 2-byte word sent with the status word to the bus master reporting the main actual value in %.
  • Page 60 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [1631] System Temp. View the combined (highest) internal system temperature measurement. [1632] Brake Energy /s Present brake power transferred to an external brake resistor. Stated as an instant value. [1633] Brake Energy Average Brake power transferred to an external brake resistor.
  • Page 61 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [1663] Terminal 54 Switch Setting Setting of input terminal 54. Current=0; Voltage=1. [1664] Analog Input 54 Actual value at input 54 either as reference or protection value. [1665] Analog Output 42 [mA] Actual value at output 42 in mA.
  • Page 62 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [1694] Ext. Status Word One or more status conditions in a hex code. [1695] Ext. Status Word 2 One or more status conditions in a hex code. [1696] Maintenance Word The bits reflect the status for the programmed preventice...
  • Page 63 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [1874] Inrush Mode The reported mode of each inrush board. Values: 0 = unknown, 1 = inrush, 2 = running. Indexes: 0 = inrush 1, 1 = inrush 2, and so on. [1875] Rectifier DC Volt.
  • Page 64 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [3128] Pressure sensor 3 [3129] Pressure sensor 4 [3130] Pressure sens cmp state [3131] Pressure sens toggle [3401] PCD 1 Write to MCO [3402] PCD 2 Write to MCO [3403] PCD 3 Write to MCO [3404]...
  • Page 65: Lcp Custom Readout

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [4596] Sensor 3 [%] [4597] Sensor 3 [unit] [4598] Sensor 4 [%] [4599] Sensor 4 [unit] 0-21 Display Line 1.2 Small The options are the same as those listed for parameter 0-20 Display Line 1.1 Small. Select a variable to show in line 1, center position. 0-22 Display Line 1.3 Small The options are the same as those listed for parameter 0-20 Display Line 1.1 Small.
  • Page 66 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Custom Readout (Value) P 16-09 Custom Readout Unit P 0-30 Max value P 0-32 Min value Linear units Motor Speed only (P0-31) Motor Speed High limit P 4-13 (RPM) P 4-14 (Hz) Figure 30: Custom Readout The relation depends on the type of unit selected in parameter 0-30 Custom Readout Unit.
  • Page 67 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [10] 1/min [11] [12] Pulse/s [20] [21] l/min [22] [23] [24] /min [25] [30] kg/s [31] kg/min [32] kg/h [33] t/min [34] [40] [41] m/min [45] [60] °C [70] mbar...
  • Page 68 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [126] /min [127] [130] lb/s [131] lb/min [132] lb/h [140] ft/s [141] ft/min [145] [160] °F [170] [171] lb/in [172] in WG [173] ft WG [174] in Hg [180] 0-31 Min Value of User-defined Readout Default value:...
  • Page 69: Lcp Keypad

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: 1 setup Conversion index: Data type: VisStr[25] Change during operation: True Enter a text which can be viewed in the graphical display by selecting [37] Display Text 1 in Parameter 0-20 Display Line 1 Small Parameter 0-21 Display Line 1.2 Small Parameter 0-22 Display Line 1.3 Small...
  • Page 70 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Disabled No effect when [Hand On] is pressed. Select [0] Disabled to avoid accidental start of the drive in hand-on mode. [1]* Enabled The LCP switches to hand-on mode directly when [Hand On] is pressed.
  • Page 71 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Disabled Avoids accidental stop of the drive in auto-on mode. [1]* Enabled Password Avoids unauthorized start in auto-on mode. If parameter 0-42 [Auto on] Key on LCP is included in the Quick Menu, then define the password in parameter 0-65 Personal Menu Password.
  • Page 72: Copy/Save

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Disabled No effect when [Reset] is pressed. Avoids accidental alarm reset. [1]* Enabled Password Avoids unauthorized start in auto-on mode. If parameter 0-43 [Reset] Key on LCP is included in the Quick Menu, then define the password in parameter 0-65 Personal Menu Password.
  • Page 73: Password

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description All from LCP Copies all parameters in all setups from the LCP memory to the drive memory. Size indep. from LCP Copy only the parameters that are independent of the motor size.
  • Page 74 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* Full access Disables password defined in parameter 0-60 Main Menu Password. LCP: Read only Prevent unauthorized editing of Main Menu parameters. LCP: No access Prevent unauthorized viewing and editing of Main Menu parameters.
  • Page 75 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 14: How Combinations of Parameters 0-61 and 0-66 Work with LCP Combination number Operation selected in Option selected in parameter LCP behavior when pressing [Quick Menu] after power-up parameter 0-66 Access to 0-61 Access to Main Menu w/o Personal Menu w/o Password Password...
  • Page 76: Clock Settings

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint16 Change during operation: True Use this parameter to unlock the drive via fieldbus or VLT® Motion Control Tool MCT 10. When a valid password is entered, the drives is unlocked for 30 minutes. 0-7* Clock Settings 6.2.9 Set the time and date of the internal clock.
  • Page 77 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description YYYY-MM-DD DD-MM-YYYY MM/DD/YYYY 0-72 Time Format Default value: – Parameter type: Option Setup: 1 setup Conversion index: – Data type: Uint8 Change during operation: True Set the time format to be used in the LCP. Option Name Description...
  • Page 78 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: TimeOfDay Change during operation: True This parameter stores the last 5 drive power-off timestamps. Index [0] is the latest power-off time, and index [4] is the oldest. 0-76 DST/Summertime Start Default value: Parameter type: Size related...
  • Page 79 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description 0-82 Additional Working Days Default value: Parameter type: Size related Range, 0 - 0, Array [5] Setup: 1 setup Conversion index: Data type: TimeOfDay Change during operation: True Array with 5 elements [0]–[4] shown below the parameter number in the display.
  • Page 80: Varia

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Shows the summer time end for fieldbus. 0-88 Clock Restore at Powerup Default value: [0] Disabled Parameter type: Option Setup: 1 setup Conversion index: – Data type: Uint8 Change during operation: True Option Name...
  • Page 81 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: 1 setup Conversion index: – Data type: Uint8 Change during operation: True NOTICE This parameter cannot be changed while the motor is running. NOTICE When set to [3] Closed loop, the commands reversing and start reversing do not reverse the motor direction. Select the application control principle to be used when a remote reference (that is via analog input or fieldbus) is active.
  • Page 82 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 1-03 Torque Characteristics Default value: – Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True NOTICE This parameter cannot be adjusted while the motor is running. Select the torque characteristic required.
  • Page 83: Motor Selection

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 1-05 Local Mode Configuration Default value: [0] Open loop Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Select which application configuration mode (parameter 1-00 Configuration Mode), that is application control principle, to use when a local (LCP) reference is active.
  • Page 84 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 15: Active Parameters with Induction and PM Non-salient Motors [0] Asynchron [1] PM Motor Non Salient Parameter 1-10 Motor Construction Parameter 1-00 Configuration Mode – Parameter 1-03 Torque Characteristics Parameter 1-06 Clockwise Direction –...
  • Page 85 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 15: Active Parameters with Induction and PM Non-salient Motors (continued) [0] Asynchron [1] PM Motor Non Salient Parameter 1-10 Motor Construction – Parameter 1-60 Low Speed Load Compensation – Parameter 1-61 High Speed Load Compensation –...
  • Page 86 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 15: Active Parameters with Induction and PM Non-salient Motors (continued) [0] Asynchron [1] PM Motor Non Salient Parameter 1-10 Motor Construction – Parameter 2-03 DC Brake Cut In Speed [RPM] –...
  • Page 87: Motor Selection

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 1-1* Motor Selection 6.3.3 1-10 Motor Construction Default value: [0] Asynchron Parameter type: Option Setup: All seutps Conversion index: – Data type: Uint8 Change during operation: False Select the motor design type. Option Name Description...
  • Page 88: Motor Data

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions The damping gain stabilizes the PM machine to run smoothly and with stability. The value of damping gain controls the dynamic performance of the PM machine. High damping gain gives high dynamic performance and low damping gain gives low dynamic performance.
  • Page 89 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 1-20 Motor Power [kW] Default value: Size related Parameter type: Range, 0.09 - 3000.00 kW Setup: All setups Conversion index: Data type: Uint32 Change during operation: False NOTICE This parameter cannot be adjusted while the motor is running. Enter the nominal motor power in kW according to the motor nameplate data.
  • Page 90 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions NOTICE Setting this parameter sets the following parameters to their default settings: Parameter 1-15 Low Speed Filter Time Const. Parameter 1-16 High Speed Filter Time Const. Parameter 1-17 Voltage Filter Time Const. Parameter 1-24 motor Current Parameter 1-30 Stator Resistance (Rs) Parameter 1-31 Rotor Resistance (Rr)
  • Page 91 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions NOTICE Setting this parameter sets the following parameters to their default settings: Parameter 1-15 Low Speed Filter Time Const. Parameter 1-16 High Speed Filter Time Const. Parameter 1-17 Voltage Filter Time Const. Parameter 1-30 Stator Resistance (Rs) Parameter 1-31 Rotor Resistance (Rr) Parameter 1-33 Stator Leakage Reactance (X1)
  • Page 92 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Enter the value from the motor nameplate data. The default value corresponds to the nominal rated output. This parameter is available when parameter 1-10 Motor Construction is set to [1] PM, non-salient SPM, [2] PM, salient IPM, [5] SynRM, and [6] PMaSynRM. 1-28 Motor Rotation Check Default value: [0] Off...
  • Page 93: 1-3* Adv. Motor Data

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* Enable complete AMA Performs • AMA of the stator resistance R • The rotor resistance R • The stator leakage reactance X • The rotor leakage reactance X , and •...
  • Page 94 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions   NOTICE A simple check of the X sum value is to divide the line-to-line motor voltage by the sqrt(3) and divide this value by the motor no load current. [VL-L/sqrt(3)]/INL = X .
  • Page 95 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions NOTICE This parameter cannot be adjusted while the motor is running. NOTICE The parameter value is updated after each torque calibration if option [3] 1st start with store or option [4] Every start with store is selected in parameter 1-47 Torque Calibration.
  • Page 96 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions NOTICE This parameter is only relevant for induction motors. Set the rotor leakage reactance of the motor using 1 of these methods: Run an AMA on a cold motor. The drive measures the value from the motor. Enter the X value manually.
  • Page 97 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Enter the equivalent iron loss resistance (R ) value to compensate for iron loss in the motor. The R value cannot be found by performing an AMA. The R value is especially important in torque control applications. If R is unknown, leave parameter 1-36 Iron Loss Resistance (Rfe) on default setting.
  • Page 98 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions NOTICE This parameter is only active when parameter 1-10 Motor Construction is set to options that enable PM (permanent magnet) motors. Set the nominal back EMF for the motor when running at 1000 RPM. Back EMF is the voltage generated by a PM motor when no drive is connected and the shaft is turned externally.
  • Page 99 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Use this parameter to optimize the torque estimate in the full speed range. The estimated torque is based on the shaft power, P shaft . Make sure that the R value is correct.
  • Page 100: Load Indep. Setting

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint16 Change during operation: False NOTICE Run an AMA to set the value of this parameter. Edit the value manually only when the application requires a value other than determined by AMA.
  • Page 101 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 1-52 Min Speed Normal Magnetising [Hz] Default value: Size related Parameter type: Range, 0.3 - 10.0 Hz Setup: All setups Conversion index: Data type: Uint16 Change during operation: True NOTICE Parameter 1-52 Min Speed Normal Magnetising [Hz] has no effect when parameter 1-10 Motor Construction = [1] PM, non-salient SPM.
  • Page 102 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Int8 Change during operation: True The value of this parameter reduces the maximum voltage available for the flux of the motor in field weakening, providing more voltage for torque. Increasing the value increases the risk of stalling at high speed. When reducing the voltage below 0, the output voltage is increased and at some point the current controller is forced into "Voltage Limit".
  • Page 103: Load Depend. Setting

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint16 Change during operation: False The parameter is active when parameter 1-73 Flying Start is enabled. The value range and function depend on parameter 1-10 Motor Construction: [0] Asynchron: [0-500%] Control the percentage of the frequency for the pulses used to detect the motor direction. Increasing this value reduces the generated torque.
  • Page 104 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 1-61 High Speed Load Compensation Default value: 100% Parameter type: Range, 0 - 300% Setup: All setups Conversion index: Data type: Int16 Change during operation: True NOTICE Parameter 1-61 High Speed Load Compensation only has effect when parameter 1-10 Motor Construction = [0] Asynchron. Enter the % value to compensate voltage in relation to load when the motor is running at high speed and obtain the optimum U/f characteristic.
  • Page 105 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint16 Change during operation: True NOTICE Parameter 1-64 Resonance Damping only has effect when parameter 1-10 Motor Construction = [0] Asynchron. Enter the resonance damping value. Set parameter 1-64 Resonance Damping and parameter 1-65 Resonance Damping Time Constant to help eliminate high-frequency resonance problems.
  • Page 106: Start Adjustments

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* Passive load For conveyors, fans, and pump applications. Active load For hoisting applications. This option allows the drive to ramp up at 0 RPM. When [1] Active Load is selected, set parameter 1-66 Min.
  • Page 107 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Rotor detection Estimates the electrical angle of the rotor and uses this as a starting point. Standard selection for automation applications. [1]* Parking The parking function applies DC current across the stator winding and rotates the rotor to electrical 0 position (typically selected for HVAC applications).
  • Page 108 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions NOTICE This function is not recommended for hoisting applications. For power levels above 55 kW, flux mode must be used to achieve the best performance. NOTICE To obtain the best flying start performance, the advanced motor data, parameter 1-30 Stator Resistance (Rs) to parameter 1-35 Main Reactance (Xh), must be correct.
  • Page 109 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Current testing limited to a speed range up to 300 Hz. For certain units, the limit is 250 Hz; all 200–240 V units to and including 2.2 kW (3.0 hp) and all 380–480 V units up to and including 4.0 kW (hp 5.0). For high-inertia applications (when the load inertia is more than 30 times higher than the motor inertia), use a brake resistor to avoid overvoltage trip during high-speed engagement of the flying-start function.
  • Page 110: Stop Adjustments

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions to get a fast start, parameter 1-86 Trip Speed Low [RPM] is also activated to protect the application from running below minimum motor speed, for example when in current limit. This function allows high starting torque and use of a fast starting ramp. To ensure the build-up of a high torque during the start, enter appropriate values for start delay/start speed/start current.
  • Page 111 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 1-81 Min Speed for Function at Stop [RPM] Default value: Size related Parameter type: Range, 0 - 600 RPM Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Set the speed at which to activate parameter 1-80 Function at Stop.
  • Page 112: Motor Temperature

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 1-87 Trip Speed Low [Hz] Default value: Size related Parameter type: Range, 0 - parameter 4-14 Motor Speed High Limit [Hz] Setup: Conversion index: All setups Data type: Uint16 Change during operation: True NOTICE This parameter is only available if parameter 0-02 Motor Speed Unit is set to [1] Hz.
  • Page 113 If the temperature of the motor is monitored through a thermistor, the PELV is not complied with if there are short circuits between motor windings and the sensor. To comply with PELV, isolate the motor appropriately. NOTICE Danfoss recommends using 24 V DC as thermistor supply voltage. NOTICE The ETR timer function does not work when parameter 1-10 Motor Construction=[1] PM, non-salient SPM.
  • Page 114 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 1-91 Motor External Fan Default value: [0] No Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Option Name Description [0]* No external fan is required, that is the motor is derated at low speed.
  • Page 115 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Select the input to which the thermistor (PTC sensor) should be connected. An analog input option [1] Analog Input 53 or [2] Analog Input 54 cannot be selected if the analog input is already in use as a reference source (selected in parameter 3-15 Reference Resource 1, parameter 3-16 Reference Resource 2, or parameter 3-17 Reference Resource 3).
  • Page 116 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Pt1000 1 kΩ at 0 °C (32 °F). Ni1000 (6178 ppm/K) 1 kΩ at 0 °C (32 °F). Ni1000-LG (TC5) Examples: • Siemens LG-Ni1000 • Tasseron RTD Ni1000-TC5 1000 Ohm 1-96 Thermistor Sensor Resource Default value: Parameter type: [0] None...
  • Page 117 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 100% 5 Hz 15 Hz 25 Hz 50 Hz Figure 37: Example of ATEX ETR Thermal Limitation Curve x-axis: f [Hz] y-axis: I x 100 [%] 1-99 ATEX ETR Interpol. Points Current Default value: Parameter type: Size related...
  • Page 118: Parameter Group 2-** Brakes

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Parameter Group 2-** Brakes 2-0* DC Brakes 6.4.1 Parameter group for configuring the DC brake and DC hold functions. 2-00 DC Hold Current Default value: Parameter type: Range, 0 - 160% Setup: All setups Conversion index:...
  • Page 119: Brake Energy Funct

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Set the DC brake cut-in speed for activation of the DC brake current set in parameter 2-01 DC Brake Current, upon a stop command. 2-04 DC Brake Cut In Speed [Hz] Default value: Size Parameter type:...
  • Page 120 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description No brake resistor installed. Resistor brake A brake resistor is incorporated in the system for dissipation of surplus brake energy as heat. Connecting a brake resistor allows a higher DC-link voltage during braking (generating operation).
  • Page 121 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions T7 units: 1099 V NOTICE If R is not known, or if T is different from 120 s, the practical approach is to run the brake application, read parameter 16-33 Brake Energy Average and then enter this + 20% in parameter 2-12 Brake Power Limit (kW). 2-13 Brake Power Monitoring Default value: [0] Off...
  • Page 122 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [10] Warning 300s Activates a warning on the display when the power transmitted during the duty time exceeds 100% of the monitoring limit (parameter 2-12 Brake Power Limit (kW)). The warning disappears when the transmitted power drops below 80% of the monitoring limit.
  • Page 123 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* Monitors brake resistor and brake IGBT for a short circuit during operation. If a short circuit occurs, Warning 25 Brake resistor shortcircuited appears. Warning Monitors brake resistor and brake IGBT for a short circuit and runs a test for brake resistor disconnection during power-up.
  • Page 124: Parameter Group 3-** Reference/Ramps

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 2-19 Over-voltage Gain Default value: 100% Parameter type: Range, 10 - 200% Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Use this parameter for adjusting the overvoltage gain for parameter 2-17 Over-voltage Controlin the low-speed area. Parameter Group 3-** Reference/Ramps 3-0* Reference Limits 6.5.1...
  • Page 125: References

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Sums both external and preset reference sources. External/Preset Use either the preset or the external reference source. Shift between external and preset via a command or a digital input. 3-05 On Reference Window Default value: Size related...
  • Page 126 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions P3-03 P3-02 P3-10 100% Figure 38: Preset Reference 12 (+24V) Preset 76543210 [P 5-13=Preset ref. bit 0] 10101010 [P 5-14=Preset ref. bit 1] 11001100 11110000 [P 5-15=Preset ref. bit 2] Figure 39: Preset Reference Scheme Table 17: Preset Referenece Bits Preset ref.
  • Page 127 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 17: Preset Referenece Bits (continued) Preset ref. bit Preset ref. 6 Preset ref. 7 P 3-14 Preset relative ref. Input command: Preset ref. bit0, bit1, bit2 P 1-00 Configuration mode Input command: Open loop Freeze ref.
  • Page 128 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint16 Change during operation: True The jog speed is a fixed output speed at which the drive is running when the jog function is activated. See also parameter 3-80 Jog/ Homing Ramp Time.
  • Page 129 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Resulting Relative actual Z=X+X*Y/100 reference Figure 41: Preset Relative Reference -100 P 3-14 Figure 42: Actual Reference 3-15 Reference Resource 1 Default value: Parameter type: [1] Analog input 53 Option Setup: All setups Conversion index:...
  • Page 130 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [30] Ext. closed loop 1 [31] Ext. closed loop 2 [32] Ext. closed loop 3 [37] Analog Input X49/1 [38] Analog Input X49/3 [39] Analog Input X49/5 [133] Fieldbus REF 1 3-16 Reference Resource 2...
  • Page 131 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [37] Analog input X49/1 [38] Analog input X49/3 [39] Analog input X49/5 [133] Fieldbus REF 1 3-16 Reference Resource 2 Default value: Parameter type: [0] No function Option Setup: All setups...
  • Page 132: Ramp

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [39] Analog input X49/5 [133] Fieldbus REF 1 3-19 Jog Speed [RPM] Default value: Parameter type: Size related Range, 0 - par. 4-13 RPM Setup: All setups Conversion index: Data type: Change during operation:...
  • Page 133 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 3-41 Ramp 1 Ramp Up Time Default value: Size related Parameter type: Range, 1.00 - 3600 s Setup: All setups Conversion index: Data type: Uint32 Change during operation: True Enter the ramp-up time, that is the acceleration time from 0 RPM to the synchronous motor speed n .
  • Page 134: Other Ramps

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 3-8* Other Ramps 6.5.5 3-80 Jog Ramp Time Default value: Size related Parameter type: Range, 1 - 3600 s Setup: All setups Conversion index: Data type: Uint32 Change during operation: True Enter the jog ramp time, that is the acceleration/deceleration time between 0 RPM and the rated motor frequency n .
  • Page 135: Digital Pot.meter

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions The ramp-up time is the acceleration time from 0 RPM to the nominal motor speed set in parameter 3-82 Starting Ramp Up Time when [0] Compressor Torque is active in parameter 1-03 Torque Characteristics. 3-9* Digital Pot.Meter 6.5.6 The digital potentiometer enables increase of decrease of the actual reference by adjusting the setup of the digital inputs using the...
  • Page 136: Parameter Group 4-** Limits/Warnings

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 3-92 Power Restore Default value: [0] Off Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Option Name Description [0]* Resets the digital potentiometer reference to 0% after power-up. Restores the most recent digital potentiometer reference at power-up.
  • Page 137 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 4-10 Motor Speed Direction Default value: [2] Both directions Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: False NOTICE This parameter cannot be adjusted while the motor is running. Select the motor speed directions required.
  • Page 138 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Enter the maximum limit for motor speed. The motor speed high limit can be set to correspond to the manufacturer’s maximum nominal motor speed. The motor speed high limit must exceed the setting in parameter 4-11 Motor Speed Low Limit [RPM]. 4-14 Motor Speed High Limit [Hz] Default value: Size related...
  • Page 139: Speed Monitor

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions NOTICE If [20] ATEX ETR is selected in parameter 1-90 Motor Thermal Protection, set parameter 4-18 Current Limit current limit to 150%. This is a true current limit function that continues in the oversynchronous range. However, due to field weakening the motor torque at current limit will drop accordingly when the voltage increase stops above the synchronized speed of the motor.
  • Page 140: Adjustable Warnings

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* As fast as possible The motor time constant (x10) is used as the time interval to check the motor. Every 1 hour [10] Every 2 hours [15] Every 12 hours [20]...
  • Page 141 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Enter the I value. When the motor current exceeds this limit, the display reads Current High. The signal outputs can be programmed to HIGH produce a status signal on terminal 27 or 29. 4-52 Warning Speed Low Default value: 0 RPM...
  • Page 142 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Int32 Change during operation: True Enter the lower feedback limit. When the feedback drops below this limit, the display reads Feedb . The signal outputs can be programmed to produce a status signal on terminal 27 or 29 and on relay output 01 or 02. 4-57 Warning Feedback High Default value: 999999.99 ProcessCtrlUnit...
  • Page 143 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 18: Missing Motor Phase for Different Motor Control Principles Option Missing motor VVC+ Flux open loop Flux closed loop phase function Disabled No function Trip 100 ms Detects missing 1 Detects missing 1 Detects 1–3 phase Detects 1–3 phase...
  • Page 144: Speed Bypass

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 19: Motor Check at Start for Different Motor Control Principles Option Motor check at VVC+ Flux open loop Flux closed loop start No function. 4-6* Speed Bypass 6.6.4 Some systems require that certain output frequencies or speeds are avoided due to resonance problems in the system. A maximum of 4 frequency or speed ranges can be avoided.
  • Page 145: Semi-Automatic Bypass Speed Setup

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Some systems require that certain output frequencies or speeds are avoided due to resonance problems in the system. Enter the upper limits of the speeds to be avoided. 4-64 Semi-auto Bypass Set-up Default value: [0] Off Parameter type:...
  • Page 146: Digital Inputs

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 5-00 Digital I/O Mode Default value: [0] PNP Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: False NOTICE Perform a power cycle to activate the parameter once it has been changed. Digital inputs and programmed digital outputs are preprogrammable for operation either in PNP or NPN systems.
  • Page 147 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 20: Function Groups Group Functions Reset, coast stop, reset and coast stop, quick stop, DC brake, stop, and the [Off ] key. Start, latched start, reversing, start reversing, jog, and freeze out- put.
  • Page 148 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 21: Digital Input Functions and Terminals (continued) Digital input function Select Terminal Run permissive [52] Hand start [53] Auto start [54] DigiPot increase [55] DigiPot decrease [56] DigiPot clear [57] Counter A (up) [60]...
  • Page 149 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 21: Digital Input Functions and Terminals (continued) Digital input function Select Terminal Firemode setup bit 0 [193] Firemode setup bit 1 [194] Test fire mode [195] Reset fire mode [196] All = Terminals 18, 19, 27, 29, 32, 33, X30/2, X30/3, X30/4.
  • Page 150 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 22: Digital Inputs, Function Descriptions - 1 (continued) Option Functions External interlock Same function as coasting inverse and stop inverse, but this op- tion generates the alarm message External fault on the display when the terminal programmed for coast inverse has signal 0.
  • Page 151 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 23: Preset Reference Bit (continued) Preset ref. bit Preset ref. 4 Preset ref. 5 Preset ref. 6 Preset ref. 7 Table 24: Digital Inputs, Function Descriptions - 2 Option Functions [19] Freeze reference...
  • Page 152 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 26: Digital Inputs, Function Descriptions - 3 Option Function [22] Speed down Same as [21] Speed up. [23] Set-up select bit 0 Select [23] Set-up select bit 0 or select [24] Set-up select bit 1 to select 1 of the 4 setups.
  • Page 153 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 28: Digital Inputs, Function Descriptions - 4 Option Function [37] Fire mode A signal applied puts the drive into fire mode and the preset ref bits 0–2 define the operation mode of fire mode where all other commands are disregarded.
  • Page 154 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 28: Digital Inputs, Function Descriptions - 4 (continued) Option Function [60] Counter A (up) (Terminals 29 and 33 only). Input for increment counting in the SLC counter. [61] Counter A (down) (Terminals 29 and 33 only).
  • Page 155 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 28: Digital Inputs, Function Descriptions - 4 (continued) Option Function [191] Fire mode ref bit 1 Enables a choice between1 of the 8 preset references according Table [192] Fire mode ref bit 2 Enables a choice between1 of the 8 preset references according Table [193]...
  • Page 156 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [11] Start reversing [14] [15] Preset reference on [16] Preset ref bit 0 [17] Preset ref bit 1 [18] Preset ref bit 2 [19] Freeze reference [20] Freeze output [21] Speed up...
  • Page 157 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [121] Lead pump alternation [130] Pump 1 interlock [131] Pump 2 interlock [132] Pump 3 interlock [139] Pump 1 inverse interlock [140] Pump 2 inverse interlock [141] Pump 3 inverse interlock [190] Fire mode ref bit 0...
  • Page 158 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description No operation Reset Coast inverse Coast and reset inv DC-brake inverse Stop inverse External interlock Start Latched start [10] Reversing [11] Start reversing [14] [15] Preset reference on [16] Preset ref bit 0 [17]...
  • Page 159 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [60] Counter A (up) [61] Counter A (down) [62] Reset counter A [63] Counter B (up) [64] Counter B (down) [65] Reset counter B [66] Sleep mode [68] Timed actions disabled [69]...
  • Page 160 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True The options for this parameter are the same as those listed for parameter 5-10 Terminal 18 Digital Input. 5-15 Terminal 33 Digital Inputs Default value: Size related...
  • Page 161 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions NOTICE Selecting Auto Reset/Warning enables automatic restart of the drive. Use this parameter to configure the Safe Torque Off functionality. A warning message makes the drive coast the motor and enables the automatic restart.
  • Page 162 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 29: Overview of Functions, Alarms, and Warnings (continued) Function Number Relay PTC 1 and relay A/W PTC 1 Safe Torque Off [A71] Safe Torque Off [W68] PTC 1 and relay W/A PTC 1 Safe Torque Off [W71] Safe Torque Off [A68] 1) W means warning and A means alarm.
  • Page 163 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [24] Set-up select bit 1 [34] Ramp bit 0 [36] Mains failure inverse [37] Fire mode [52] Run permissive [53] Hand start [54] Auto start [55] DigiPot increase [56] DigiPot decrease [57]...
  • Page 164 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [195] Test fire mode [196] Reset fire mode 5-21 Terminal X46/3 Digital Input Default value: Parameter type: – Option Setup: All setups Conversion index: – Data type: Change during operation: Uint8 True...
  • Page 165: 5-3* Digital Outputs

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True The options for this parameter are the same as those listed for parameter 5-20 Terminal X46/1 Digital Input. 5-3* Digital Outputs 6.7.3 The 2 solid-state digital outputs are common for terminals 27 and 29.
  • Page 166 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 30: Digital Outputs, Function Descriptions (continued) Option Function [17] Above speed, high The output speed is higher than the setting in parameter 4-53 Warning Speed High. [18] Out of feedb. range Feedback is below the limit set in parameter 4-56 Warning Feedback Low and parameter 4-57 Warning Feedback High.
  • Page 167 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 30: Digital Outputs, Function Descriptions (continued) Option Function [45] Bus ctrl. Controls output via bus. The state of the output is set in parameter 5-90 Digital & Relay Bus Control. If a bus timeout occurs, the output state is retained.
  • Page 168 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 30: Digital Outputs, Function Descriptions (continued) Option Function [72] Logic rule 2 See parameter group 13-4* Logic Rules. If logic rule 2 is evaluated as true, the output goes high. Otherwise, it is low. [73] Logic rule 3 See parameter group 13-4* Logic Rules.
  • Page 169 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 30: Digital Outputs, Function Descriptions (continued) Option Function [90] kWh counter pulse Sends a pulse (200 ms pulse width) to the output terminal when- ever the kWh counter changes (parameter 15-02 kWh Counter). [150] CBM warning [151]...
  • Page 170 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 30: Digital Outputs, Function Descriptions (continued) Option Function [181] Prev. maintenance One or more of the preventive maintenance events programmed in 23-10 Maintenance Item has passed the time for the specified action is parameter 23-11 Maintenance Action.
  • Page 171 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 30: Digital Outputs, Function Descriptions (continued) Option Function [202] Pump 2 running See [201] Pump 1 running. [203] Pump 3 running See [201] Pump 1 running. [234] PE power off [236] Ext.
  • Page 172 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint8 Change during operation: True Select the function from the available digital output range. All functions are described in Table Option Name Description No operation Control ready Drive ready Coast and reset inv Standby/no warning Running...
  • Page 173 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [40] Out of ref range [41] Below reference, low [42] Above ref, high [45] Bus ctrl. [46] Bus ctrl, 1 if timeout [47] Bus ctrl, 0 if timeout [51] MCO controlled [55]...
  • Page 174 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [84] SL digital output E [85] SL digital output F [90] kWh counter pulse [151] ATEX ETR cur. alarm [152] ATEX ETR freq. alarm [153] ATEX ETR cur. warning [154] ATEX ETR freq.
  • Page 175 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [202] Pump 2 running [203] Pump 3 running [234] PE power off [236] Ext. CL 1 on ref [237] Ext. CL 2 on ref [238] Ext. CL 3 on ref [240] RS flipflop 0 [241]...
  • Page 176: 5-4* Relays

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint8 Change during operation: True This parameter is active when option module VLT® General Purpose I/O MCB 101 is mounted in the drive. The options for this parameter are the same as those listed for parameter 5-30 Terminal 27 Digital Output.
  • Page 177 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [15] Out of speed range Output speed/frequency is outside the frequency range set in parameter 4-52 Warning Speed Low and parameter 4-53 Warning Speed High. [16] Below speed, low Output speed is lower than the setting in parameter 4-52 Warning Speed Low.
  • Page 178 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [37] Control word bit 12 Activate relay 2 by control word from fieldbus. No other functional impact in the drive. Typical application: Controlling auxiliary device from fieldbus. The function is valid when [0] FC profile in parameter 8-10 Control Word Profile is selected.
  • Page 179 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [70] Logic rule 0 See parameter group 13-4* Logic Rules. If logic rule 0 in SLC is true, the output goes high. Otherwise, it is low. [71] Logic rule 1 See parameter group 13-4* Logic Rules.
  • Page 180 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [151] ATEX ETR cur. alarm Selectable if parameter 1-90 Motor Thermal Protection is set to [20] ATEX ETR or [21] Advanced ETR. If alarm 164, ATEX ETR cur.lim.alarm is active, the output is 1.
  • Page 181 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [189] External fan control The internal logics for internal fan control is transferred to this output to make it possible to control an external fan (relevant for hp duct cooling).
  • Page 182 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [245] RS flipflop 5 See parameter group 13-1* Comparators. [246] RS flipflop 6 See parameter group 13-1* Comparators. [247] RS flipflop 7 See parameter group 13-1* Comparators. [249] Fire m OPR unexpected Fire mode input or safe stop is not operating as expected, for...
  • Page 183: Pulse Input

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Selected event Relay output On delay Off delay P 5-41 P 5-42 Figure 50: Off Delay, Relay 5-5* Pulse Input 6.7.5 The pulse input parameters are used to define an appropriate window for the impulse reference area by configuring the scaling filter settings for the pulse inputs.
  • Page 184 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Enter the high frequency limit corresponding to the high motor shaft speed (that is high reference value) in parameter 5-53 Term. 29 High Ref./Feedb. Value. 5-52 Term. 29 Low Ref./Feedb. Value Default value: 0 ReferenceFeedbackUnit Parameter type:...
  • Page 185: Pulse Outputs

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint32 Change during operation: True Enter the high frequency corresponding to the high motor shaft speed (that is high reference value) in parameter 5-58 Term. 33 High Ref./Feedb. Value. 5-57 Term.
  • Page 186 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Output value High output value P 5-60(term27) P 5-63(term29) High freq. Output P 5-62(term27) (Hz) P 5-65(term29) Figure 52: Configuration of Pulse Outputs Table 32: Options for Readout Output Variables Option Name Description...
  • Page 187 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 5-60 Terminal 27 Pulse Output Variable Default value: [0] No operation Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Option Name Description [0]* No operation Select the display output for terminal 27.
  • Page 188 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Option Name Description [0]* No operation Select the display output for terminal 27. [45] Bus ctrl. [48] Bus ctrl., timeout [51] MCO controlled...
  • Page 189: I/O Options

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* No operation Select the display output for terminal 27. [45] Bus ctrl. [48] Bus ctrl., timeout [51] MCO controlled [86] Pressure sensor 1 [88] Pressure sensor 2 [93] Pressure sensor 3 [100]...
  • Page 190: Bus-Controlled

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Guarantees a minimum off-time for the capacitors. The timer starts once the AHF capacitor disconnects and has to expire before the output is allowed to be on again. It only turns on again if the drive power is 20–30%. 5-9* Bus-controlled 6.7.8 This parameter group selects digital and relay outputs via a fieldbus setting.
  • Page 191: Parameter Group 6-** Analog In/Out

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Set the output frequency transferred to output terminal 29 when the terminal is configured as [48] Bus Ctrl Timeout in parameter 5-63 Terminal 29 Pulse Output Variable and a timeout is detected. 5-97 Pulse Out #30/6 Bus Control Default value: Parameter type:...
  • Page 192: Analog Input

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint8 Change during operation: True Select the timeout function. If the input signal on terminal 53 or 54 is below 50% of the value in Parameter 6-10 Terminal 53 Low Voltage Parameter 6-12 Terminal 53 Low Current Parameter 6-20 Terminal 54 Low Voltage Parameter 6-22 Terminal 54 Low Current...
  • Page 193 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Ref./Feedback [RPM] Par 6-xx 1500 'High Ref./ Feedb. Value' 1200 Par 6-xx 'Low Ref./ Feedb. Value' 10 V Par 6-xx Par 6-xx Analog input 'Low Voltage'or 'High Voltage'or 'Low Current' 'High Current' Figure 53: Analog Input 1 6-10 Terminal 53 Low Voltage...
  • Page 194 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 6-14 Terminal 53 Low Ref./Feedb. Value Default value: Size related Parameter type: Range, -999999.999 - 999999.999 Setup: Conversion index: All setups Data type: Int32 Change during operation: True Enter the analog input scaling value that corresponds to the low voltage/low current set in parameter 6-10 Terminal 53 Low Voltage and parameter 6-12 Terminal 53 Low Current.
  • Page 195: Analog Input

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 6-2* Analog Input 2 6.8.3 Parameters for configuring the scaling and limits for analog input 2 (terminal 54). 6-20 Terminal 54 Low Voltage Default value: 0.07 V Parameter type: Range, 0 - par. 6-21 V Setup: All setups Conversion index:...
  • Page 196: Analog Input 3 General Purpose I/O Mcb

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 6-25 Terminal 54 High Ref./Feedb. Value Default value: Parameter type: Range, -999999.999 - 999999.999 Setup: Conversion index: All setups Data type: Int32 Change during operation: True Enter the analog input scaling value that corresponds to the maximum reference feedback value set in parameter 3-03 Maximum Reference.
  • Page 197 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Sets the analog input scaling value to correspond to the low reference feedback value (set in parameter 6-34 Term. X30/11 Low Ref./ Feedb. Value). 6-31 Terminal X30/11 High Voltage Default value: 10 V Parameter type: Range, par.
  • Page 198: 6-4* Analog Input X30/12

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Disables the live zero monitoring, for example, if the analog outputs are used as part of a decentral I/O system (when an analog output does not fulfill any control function, but feeds a data storage device). Option Name Description...
  • Page 199: Analog Output

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 6-46 X30/12 Filter Time Constant Default value: 0.005 s Parameter type: Range, 0.005 - 10 s Setup: All setups Conversion index: Data type: Uint16 Change during operation: True NOTICE This parameter cannot be adjusted while the motor is running. Enter the filter time constant.
  • Page 200 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description No operation Indicates no signal on the analog output. [52] [53] MCO 4–20mA [86] Pressure sensor 1 [87] Pressure sensor 1 (4–20 mA) [88] Pressure sensor 2 [89] Pressure sensor 2 (4–20 mA) [93]...
  • Page 201 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [122] Air pres. to flow [130] Out frq. 0–100 4–20mA 0 Hz = 4 mA, 100 Hz = 20 mA. [131] Reference 4–20mA Parameter 3-00 Reference Range [-Max-Max] 0% = 4 mA; 100% = 20 mA Parameter 3-00 Reference Range [-Max-Max] -100% = 4 mA;...
  • Page 202 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 6-51 Terminal 42 Output Min Scale Default value: Parameter type: Range, 0 - 200% Setup: All setups Conversion index: Data type: Int16 Change during operation: True Scale for the minimum output (0 mA or 4 mA) of the analog signal at terminal 42. Set the value to be the percentage of the full range of the variable selected in parameter 6-50 Terminal 42 Output.
  • Page 203 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 20 mA 0/4 mA 100% 50Hz 100Hz Figure 55: Example 1, Terminal 52 Output Maximum Scale Example 2 Variable = feedback, range = -200%...+200%. Range needed for output = 0–100%. Output signal 0 mA or 4 mA is needed at 0% (50% of range).
  • Page 204 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 20 mA 10 mA 0/4 mA 100% 200% Min ref Max ref Max ref X 20/10 Figure 57: Example 3, Terminal 52 Output Maximum Scale 6-53 Term 42 Output Bus Ctrl Default value: Parameter type: Range, 0 - 100%...
  • Page 205: Analog Output 2 Mcb

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 33: Readout Parameters Selection 0–20 mA 4–20 mA Motor current (I [103] [133] Torque limit (0–T [104] [134] Rated torque (0–T [105] [135] Power (0–P [106] [136] nom) Speed (0–Speed [107] [137] Option...
  • Page 206 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [101] Reference Parameter 3-00 Reference Range [-Max - Max]0% = 0 mA; 100% = 20 mA Parameter 3-00 Reference Range [-Max - Max]-100% = 0 mA; 0% = 10 mA; +100% = 20 mA. [102] Feedback -200% to +200% of parameter 20-14 Maximum Reference/Feedb.,...
  • Page 207 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [133] Motor cur. 4–20mA The value is taken from parameter 16-37 Inv. Max. Current. The inverter maximum current (160% current) is equal to 16 mA. Example: Inverter normal current (11 kW) is 24 A. 160% = 38.4 A. Motor normal current is 22 A, the readout is 13.17 mA.
  • Page 208: Analog Output 3 Mcb

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Scales the minimum output of the selected analog signal on terminal X30/8. Scale the minimum value as a percentage of the maximum signal value. For example, enter the value 25% if the output should be 0 mA at 25% of the maximum output value. The value can never exceed the corresponding setting in parameter 6-62 Terminal X30/8 Max.
  • Page 209 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* No operation Indicates no signal on the analog output. [52] [53] MCO 4–20mA [86] Pressure sensor 1 [87] Pressure sensor 1 (4–20 mA) [88] Pressure sensor 2 [89] Pressure sensor 2 (4–20 mA) [93]...
  • Page 210 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [130] Out frq. 0–100 4–20mA 0 Hz = 4 mA, 100 Hz = 20 mA. [131] Reference 4–20mA Parameter 3-00 Reference Range [-Max-Max]0% = 4 mA; 100% = 20 mA Parameter 3-00 Reference Range [-Max-Max]-100% = 4 mA; 0% = 12 mA;...
  • Page 211 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 6-71 Terminal X45/1 Min. Scale Default value: Parameter type: Range, 0 - 200% Setup: All setups Conversion index: Data type: Int16 Change during operation: True Scale the minimum output of the selected analog signal at terminal X45/1 as a percentage of the maximum signal value. For example, if 0 mA (or 0 Hz) is required at 25% of the maximum output value, then program 25%.
  • Page 212: Analog Output 4 Mcb

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 6-74 Terminal X45/1 Output Timeout Preset Default value: Parameter type: Range, 0 - 100% Setup: 1 setup Conversion index: Data type: Uint16 Change during operation: True Holds the preset level of analog output 3 (terminal X45/1). If there is a fieldbus timeout and a timeout function is selected in parameter 6-70 Terminal X45/1 Output, the output is preset to this level.
  • Page 213 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [103] Motor cur. 0–I The value is taken from parameter 16-37 Inv. Max. Current. The inverter maximum current (160% current) is equal to 20 mA. Example: Inverter normal current (11 kW) is 24 A. 160%=38.4 A. Motor normal current is 22 A, the readout is 11.46 mA.
  • Page 214 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [136] Power 4–20mA Taken from parameter 1-20 Motor Power [kW]. [137] Speed 4–20mA Taken from parameter 3-03 Maximum Reference. 20 mA = value in parameter 3-03 Maximum Reference. [139] Bus ctrl.
  • Page 215: Parameter Group 7-** Controllers

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Scale the maximum output of the selected analog signal at terminal X45/3. Set the value to the maximum value of the current signal output. Scale the output to give a current lower than 20 mA at full scale, or 20 mA at an output below 100% of the maximum signal value.
  • Page 216 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Drive 1 Speed Torque Setpoint Ramp Calculation Droop Drive 2 Speed Torque Setpoint External Setpoint Ramp Calculation Droop Drive 3 Torque Speed Setpoint Ramp Calculation Droop Figure 59: Concept of Speed PID Droop The value in parameter 7-01 Speed PID Droop ensures that the load is shared equally between the motors.
  • Page 217: Speed Trim

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions NOTICE Do not use overvoltage control when using the PID droop function (select [0] Disabled in parameter 2-17 Over-voltage Control). NOTICE If the speed reference is lower than the value in parameter 7-01 Speed PID Droop, the drive makes the PID droop factor equal to the speed reference.
  • Page 218: Speed Pid Ctrl

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions The drawing shows a single-source setup where the master sends the torque signal to all followers. The number of available analog outputs on the master limits this setup. To overcome the limitation of the number of analog outputs, use a cascade principle. The cascade principle makes the control slower and less accurate compared with the setup using analog outputs.
  • Page 219 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint16 Change during operation: True Set a limit for the gain provided by the differentiator. Consider limiting the gain at higher frequencies. For example, set up a pure D- link at low frequencies and a constant D-link at higher frequencies.
  • Page 220 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Feedback Disturbed feedback signal t (Sec.) Lowpass filter = 10 Hz Feedback Filtered feedback signal t (Sec.) Figure 61: Feedback Signal 7-08 Speed PID Feed Forward Factor Default value: Parameter type: Range, 0 - 500% Setup Conversion index:...
  • Page 221: Parameter Group 8-** Communications And Options

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Parameter Group 8-** Communications and Options 6.10 8-0* General Settings 6.10.1 8-01 Control Site Default value: – Parameter type: Option Setup: Conversion index: All setups – Data type: Uint8 Change during operation: True The setting in this parameter overrides the settings in parameter 8-50 Coasting Select to parameter 8-56 Preset Reference Select.
  • Page 222 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 8-03 Control Word Timeout Time Default value: Size related Parameter type: Range, 0.5 - 18000 s Setup: 1 setup Conversion index: Data type: Uint32 Change during operation: True Enter the maximum time expected to pass between the reception of 2 consecutive telegrams. If this time is exceeded, it indicates that the serial communication has stopped.
  • Page 223 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [20] N2 Override release [27] Forced stop and trip [30] Warning only 8-05 End-of-Timeout Function Default value: [1] Resume set-up Parameter type: Option Setup: Conversion index: 1 setup –...
  • Page 224 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: 2 setups Conversion index: – Data type: Uint8 Change during operation: True This parameter has no function for DeviceNet. Option Name Description [0]* Disable Trigger on alarms Trigger alarm/warn. 8-08 Readout Filtering Default value: Parameter type:...
  • Page 225: Ctrl. Word Settings

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description ISO 8859-1 ANSI X3.4 UTF-8 8-1* Ctrl. Word Settings 6.10.2 8-10 Control Word Profile Default value: [0] FC profile Parameter type: Option Setup: All setups Conversion index: –...
  • Page 226 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Trip excl Alarm 68 Set if a trip occurs, unless alarm 68, Safe Torque Off is set to execute the trip. Vir. master on ref. [10] T18DI status The bit indicates the status of terminal 18.
  • Page 227 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [64] Comparator 4 See parameter group 13-1* Comparators. If comparator 4 is evaluated as true, the output goes high. Otherwise, it is low. [65] Comparator 5 See parameter group 13-1* Comparators. If comparator 5 is evaluated as true, the output goes high.
  • Page 228 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [82] SL digital out C See parameter 13-52 SL Controller Action. The output goes high whenever the smart logic action [40] Set digital out C high is executed.
  • Page 229: Product Code

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions This is an array parameter with 16 elements, 1 element for each bit in range 0–15. Each of the bits can be configured to any of the following options. Option Name Description None...
  • Page 230: Counters

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 8-2* Counters 6.10.3 8-20 Invalid Memory Write Counter Default value: 0 N/A Parameter type: Range (0 - 65535) Setup: 1 setup Conversion index: – Data type: Uint16 Change during operation: True The error counter is incremented each time the Ethernet-based fieldbus options writes to an invalid memory.
  • Page 231 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description FC option To be used when a gateway is connected to the integrated RS485 port, for example the BACnet gateway. The following changes take place: • Address for the FC port is set to 1, and parameter 8-31 Address is now used to set the address for the gateway on the network, for example BACnet.
  • Page 232 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Even parity, 1 stop bit Odd parity, 1 stop bit No parity, 1 stop bit No parity, 2 stop bits 8-35 Minimum Response Delay Default value: Size related Parameter type: Range, 5 - 10000 ms Setup:...
  • Page 233: Fc Mc Protocol Select

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Index [6] = PROFIdrive profile Index [7] = DS402 profile 8-4* FC MC Protocol Select 6.10.5 8-40 Telegram Selection Default value: [1] Standard telegram 1 Parameter type: Option Setup: 2 setups Conversion index: –...
  • Page 234 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Select the parameters to be assigned to the PCDs of the telegrams. The number of available PCDs depends on the telegram type. PCDs contain the actual data values of the selected parameters. 8-45 BTM Transaction Command Default value.
  • Page 235: Digital/Bus

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 8-47 BTM Timeout Default value: 60 s Parameter type: Range, 1 - 360 s Setup: 1 setup Conversion index: Data type: Uint16 Change during operation: False Select the BTM timeout after a BTM transaction has been started. Timeout is between each acyclic write of parameters. 8-48 BTM Maximum Errors Default value: Parameter type:...
  • Page 236 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Logic AND The fieldbus/serial communication port and a digital input trigger the coasting function. [3]* Logic OR The fieldbus/serial communication port or a digital input triggers the coasting function. 8-52 DC Brake Select Default value: Parameter type:...
  • Page 237 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 8-54 Reversing Select Default value: – Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Select the trigger for the reversing function. Option Name Description Digital input...
  • Page 238: Bacnet

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Digital input A digital input triggers the preset reference selection. A serial communication port or the fieldbus triggers the preset reference selection. Logic AND The fieldbus/serial communication port and a digital input trigger the preset reference selection.
  • Page 239 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 8-74 I-AM Service Default value: [0] Send at power-up Parameter type: Option Setup: 1 setup Conversion index: – Data type: Uint8 Change during operation: True NOTICE This parameter is active only when parameter 8-30 Protocol is set to [5] BACnet [9] FC Option. Choose whether the device should send the "I-Am"...
  • Page 240: Fc Port Diagnostics

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 8-8* FC Port Diagnostics 6.10.8 These parameters are used for monitoring the bus communication via the drive RD 485 port terminals 68–69. 8-80 Bus Message Count Default value: Parameter type: Range, 0 - 0 Setup: All setups...
  • Page 241: Bus Jog/Feedback

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions This parameter shows the number of messages suppressed due to timeout. 8-89 Diagnostics Count Default value: Parameter type: Range, 2147483648 - 2147483647, Array [10] Setup: 1 setup Conversion index: Data type: Change during operation: Uint32 True...
  • Page 242: Parameter Group 9-** Profibus

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Parameter Group 9-** PROFIBUS 6.11 9-00 Setpoint Default value: Parameter type: Range, 0 - 65535 Setup: Conversion index: All setups Data type: Uint16 Change during operation: True This parameter receives cyclic references from a master class 2. If the control priority is set to master class 2, the reference for the drive is taken from this parameter, whereas the cyclic reference is ignored.
  • Page 243: Node Address

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [413] Motor speed high limit [RPM] [414] Motor speed high limit [Hz] [416] Torque limit motor mode [417] Torque limit generator mode [553] Term. 29 high ref./feedb. value [558] Term.
  • Page 244: Telegram Selection

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 9-22 Telegram Selection Default value: [100] None Parameter type: Option Setup: Conversion index: 1 setup – Data type: Uint8 Change during operation: True Select a standard PROFIBUS telegram configuration for the drive as an alternative to the freely configurable telegrams in parameter 9-15 PCD Write Configuration and parameter 9-16 PCD Read Configuration.
  • Page 245 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [342] Ramp 1 ramp down time [351] Ramp 2 ramp up time [352] Ramp 2 ramp down time [380] Jog/homing ramp time jog ramp time [381] Quick stop ramp time [411] Motor speed low limit [RPM] [412]...
  • Page 246 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [1502] kWh counter [1600] Control word [1601] Reference [unit] [1602] Reference % [1603] Status word [1605] Main actual value [%] [1609] Custom readout [1610] Power [kW] [1611] Power [hp] [1612] Motor voltage...
  • Page 247 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [1647] Motor phase W current [1648] Speed ref. after ramp [RPM] [1650] External reference [1652] Feedback[unit] [1653] Digi pot reference [1654] Feedback 1 [unit] [1655] Feedback 2 [unit] [1656] Feedback 3 [unit] [1660]...
  • Page 248 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [1690] Alarm word [1691] Alarm word 2 [1692] Alarm word [1693] Alarm word 2 [1694] Ext. status word [1695] Ext. status word 2 [1696] Maintenance word [1697] Alarm word 3 [1698] Warning word 3...
  • Page 249 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [2014] Maximum reference/feedb. [2021] Setpoint 1 [2022] Setpoint 2 [2023] Setpoint 3 [2643] Terminal X42/7 bus control [2653] Terminal X42/9 bus control [2663] Terminal X42/11 bus control [3126] Pressure sensor 1 [3127]...
  • Page 250: Parameter Edit

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [3407] PCD 7 write to MCO [3408] PCD 8 write to MCO [3409] PCD 9 write to MCO [3410] PCD 10 write to MCO [3421] PCD 1 read from MCO [3422] PCD 2 read from MCO [3423]...
  • Page 251: Process Control

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: 2 setups Conversion index: – Data type: Uint16 Change during operation: False Parameters can be edited via: PROFIBUS The standard RS485 interface The LCP Option Name Description Disabled [1]* Enabled 9-28 Process Control Default value:...
  • Page 252 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 9-47 Fault Number Default value: Parameter type: Range, 0 - 0 N/A Setup: Conversion index: All setups Data type: Uint16 Change during operation: True This buffer contains the alarm word for all alarms and warnings that have occurred since the last reset or power-up. The buffer capacity is maximum 8 error events.
  • Page 253: Device Identification

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 35: PROFIBUS Warning Word (continued) Description Timeout active. Warning 34, Fieldbus Fault is active. 9-63 Actual Baud Rate Default value: [255] No baud rate found Parameter type: Option Setup: Conversion index: All setups –...
  • Page 254: Control Word

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Index Content Value Manufacturer 128 (for ) Device type Version xxyy Firmware date year yyyy Firmware date month ddmm No. of axes Variable Vendor specific: PB version xxyy Vendor specific: Database version xxyy Vendor specific: AOC version xxyy...
  • Page 255 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint8 Change during operation: True Select the setup to be programmed during operation. Option Name Description Factory setup Set-up 1 Set-up 2 Set-up 3 Set-up 4 [9]* Active set-up 9-71 PROFIBUS Save Data Value Default value: Parameter type:...
  • Page 256 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 9-80 Defined Parameters (1) Default value: Parameter type: Range, 0 - 9999, Array [116] Setup: Conversion index: All setups Data type: Uint16 Change during operation: False This parameter shows a list of all the defined drive parameters available for PROFIBUS. 9-81 Defined Parameters (2) Default value: Parameter type:...
  • Page 257 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 9-90 Changed Parameters (1) Default value: Parameter type: Range, 0 - 9999, Array [116] Setup: Conversion index: All setups Data type: Uint16 Change during operation: False This parameters shows a list of all the drive parameters deviating from default setting. 9-91 Changed Parameters (2) Default value: Parameter type:...
  • Page 258: Parameter Group 10-** Can Fieldbus

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Parameter Group 10-** CAN Fieldbus 6.12 10-0* Common Settings 6.12.1 10-00 CAN Protocol Default value: [1] DeviceNet Parameter type: Option Setup: Conversion index: 2 setups Data type: Uint8 Change during operation: False View the active CAN protocol.
  • Page 259: Devicenet

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint8 Change during operation: True View the number of CAN control transmission errors since the last power-up. 10-06 Readout Receive Error Counter Default value: Parameter type: Range, 0 - 255 Setup:...
  • Page 260 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 10-11 Process Data Config Write Default value: – Parameter type: Option, Array [4] Setup: 2 setups Conversion index: – Data type: Uint16 Change during operation: True Select the process write data for I/O Assembly Instances 101/151. Elements [2] and [3] of this array can be selected. Elements [0] and [1] of the array are fixed.
  • Page 261 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [663] Terminal X30/8 output bus control [673] Terminal X45/1 bus control [683] Terminal X45/3 bus control [890] Bus jog 1 speed [891] Bus jog 2 speed [894] Bus feedback 1 [895] Bus feedback 2...
  • Page 262 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [1601] Reference [unit] [1602] Reference % [1603] Status word [1605] Main actual value [%] [1609] Custom readout [1610] Power [kW] [1611] Power [hp] [1612] Motor voltage [1613] Frequency [1614] Motor current...
  • Page 263 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [1648] Speed ref. after ramp [RPM] [1650] External reference [1652] Feedback[unit] [1653] Digi pot reference [1654] Feedback 1 [unit] [1655] Feedback 2 [unit] [1656] Feedback 3 [unit] [1660] Digital input [1661]...
  • Page 264 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [1694] Ext. status word [1695] Ext. status word 2 [1696] Maintenance word [1697] Alarm word 3 [1698] Warning word 3 [1830] Analog input X42/1 [1831] Analog input X42/3 [1832] Analog input X42/5 [1833]...
  • Page 265 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [3136] Bus feedback pressure 1 [3137] Bus feedback pressure 2 [3138] Bus feedback pressure 3 [3139] Bus feedback pressure 4 [3151] Pressure warning 2 [3159] Current specific fan power [3163] Nominal pressure sensor 1 [3164]...
  • Page 266 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [4596] Sensor 3 [%] [4597] Sensor 3 [unit] [4598] Sensor 4 [%] [4599] Sensor 4 [unit] 10-13 Warning Parameter Default value: Parameter type: Range, 0 - 65535 Setup: All setups Conversion index:...
  • Page 267: Cos Filters

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint8 Change during operation: True Select the reference source in instances 21/71 and 20/70. Option Name Description [0]* 10-15 Net Control Default value: Parameter type: [0] Off Option Setup: 2 setups Conversion index:...
  • Page 268: Parameter Access

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Sets up the filter mask for PCD 3. When operating in COS (change-of-state), it is possible to filter out bits in PCD 3 that should not be sent if they change. 10-23 COS Filter 4 Default value: Parameter type:...
  • Page 269: Parameter Group 11-** Lonworks

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 10-33 Store Always Default value: [0] Off Parameter type: Option Setup: 1 setup Conversion index: – Data value: Uint8 Change during operation: True This parameter is used to select whether parameter data received via the DeviceNet option should always be stored in non-volatile memory.
  • Page 270 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint8 Change during operation: True This parameter allows selecting between LONMARK functional profiles. Option Name Description [0]* VSD profile The Profile and the Node Object are common for all profiles. 11-15 LON Warning Word Default value: Parameter type:...
  • Page 271: Lon Param. Access

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions This parameter contains the version of the external interface file on the Neuron C chip on the LON option. 11-18 LonWorks Revision Default value: Parameter type: Range, 0 - 5 Setup: All setups Conversion index:...
  • Page 272 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 12-01 IP Address Default value: Parameter type: Range, 0 - 4294967295 Setup: 1 setup Conversion index: Data type: OctStr[4] Change during operation: True Configure the IP address of the option. Read-only if parameter 12-00 IP Address Assignment is set to [1] DHCP, [2] BOOTP, or via DIP switches.
  • Page 273: Ethernet Link Parameters

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: 1 setup Conversion index: Data type: OctStr[4] Change during operation: True IP addresses of the domain name servers. Can be automatically assigned when using DHCP. 12-07 Domain Name Default value: Parameter type: Range, 0 - 48 Setup:...
  • Page 274 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 12-11 Link Duration Default value: Size related Parameter type: Range, 0 - 0, Array [2] Setup: All setups Conversion index: Data type: TimeDifferenceWithDateIndication Change during operation: True Shows the duration of the present link on each port in dd:hh:mm:ss. 12-12 Auto Negotiation Default value: [1] On...
  • Page 275: Process Data

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Half duplex [1]* Full duplex 12-18 Supervisor MAC Default value: Parameter type: Range, 0 - 2147483647, Array Setup: 2 setups Conversion index: Data type: Change during operation: OctStr[6] True MAC addresses of currently active supervisors.
  • Page 276 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [311] Jog speed [Hz] [319] Jog speed [RPM] [341] Ramp 1 ramp up time [342] Ramp 1 ramp down time [351] Ramp 2 ramp up time [352] Ramp 2 ramp down time [380] Jog/homing ramp time jog ramp time...
  • Page 277 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [1685] FC port CTW 1 [1686] FC port REF 1 12-22 Process Data Config Read Default value: Parameter type: Size related Option, Array [20] Setup: All setups Conversion index: –...
  • Page 278 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [1617] Speed [RPM] [1618] Motor thermal [1619] Thermistor sensor temperature [1620] Motor angle [1622] Torque [%] [1623] Motor shaft power [kW] [1624] Calibrated stator resistance [1626] Power filtered [kW] [1627] Power filtered [hp] [1630]...
  • Page 279 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [1665] Analog output 42 [mA] [1666] Digital output [bin] [1667] Freq. input #29 [Hz] [1668] Freq. input #33 [Hz] [1669] Pulse output #27 [Hz] [1670] Pulse output #29 [Hz] [1671] Relay output [bin] [1672]...
  • Page 280 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [1837] Temp. input X48/4 [1838] Temp. input X48/7 [1839] Temp. input X48/10 [1840] Analog input X49/1 [1841] Analog input X49/3 [1842] Analog input X49/5 [1843] Analog out X49/7 [1844] Analog out X49/9 [1845]...
  • Page 281: Ethernet/Ip

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* Store all setups Store all setups 12-29 Store Always Default value: [0] Off Parameter type: Option Setup: 1 setup Conversion index: – Data type: Uint8 Change during operation: True Activates a function that always stores received parameter data in the non-volatile memory (EEPROM).
  • Page 282 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 38: 16-Bit Status Word, EtherNet/IP (continued) Description Major unrecoverable fault Not used Not used Not used Not used 12-31 Net Reference Default value: [0] Off Parameter type: Option Setup: Conversion index: 2 setups –...
  • Page 283: Modbus Tcp

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 12-34 CIP Product Code Default value: Size related Parameter type: Range, 0 - 65535 Setup: 1 setup Conversion index: Data type: Uint16 Change during operation: True This parameter is read-only. It shows the CIP product code. 12-35 EDS Parameter Default value: Parameter type:...
  • Page 284: 12-4* Fieldbus Extension

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 39: 16-Bit Status Word, Modbus TCP Description Bit = [0] Bit = [1] Link status port 1 Disconnected Connected Link status port 2 Disconnected Connected Link speed 0/10 Mbps 100 Mbps Link duplex Half...
  • Page 285: Other Ethernet Services

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: 1 setup Conversion index: Data type: Uint32 Change during operation: True This parameter provides extra information from Ethernet-based communication. 12-8* Other Ethernet Services 6.14.7 12-80 FTP Server Default value: Parameter type: [0] Disabled Option...
  • Page 286: Advanced Ethernet Services

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 12-83 SNMP Agent Default value: [1] Enabled Parameter type: Option Setup: 2 setups Conversion index: – Data type: Uint8 Change during operation: True Use this parameter to either enable or disable the SNMP agent. Option Name Description...
  • Page 287 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: 2 setups Conversion index: – Data type: Uint8 Change during operation: True Enables/disables advanced cable diagnosis function. If enabled, the distance to cable errors can be read out in parameter 12-93 Cable Error Length.
  • Page 288 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: 1 setup Conversion index: Data type: Uint16 Change during operation: True If cable diagnostics is enabled in parameter 12-90 Cable Diagnostic, the built-in switch is possible via time domain reflectometry (TDR).
  • Page 289: Parameter Group 13-** Smart Logic Control

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 12-97 QoS Priority Default value: Size related Parameter type: Range, 0 - 63, Array [7] Setup: 2 setups Conversion index: Data type: Int8 Change during operation: True Each index sets the DSCP value of different types of QoS prioritized messages. 12-98 Interface Counters Default value: Parameter type:...
  • Page 290 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Par. 13-51 Par. 13-52 SL Controller Event SL Controller Action Running Coast Warning Start timer Torque limit Set Do X low Digital input X 30/2 Select setup 2 ..
  • Page 291: Slc Settings

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Start event P13-01 State 1 13-51.0 13-52.0 State 2 13-51.1 Stop 13-52.1 event P13-02 Stop event P13-02 State 4 13-51.3 13-52.3 State 3 13-51.2 13-52.2 Stop event P13-02 Figure 63: Example of Events and Actions Starting and stopping the SLC Start and stop the SLC by selecting [1] On or [0] Off in parameter 13-00 SL Controller Mode.
  • Page 292 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description False Select the boolean (true or false) input to activate smart logic control. Enters the fixed value False. True Enters the fixed value True. Running The motor runs. In range The motor runs within the programmed current and speed ranges set in parameter 4-50 Warning Current Low to parameter...
  • Page 293 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [22] Comparator 0 Use the result of comparator 0. [23] Comparator 1 Use the result of comparator 1. [24] Comparator 2 Use the result of comparator 2. [25] Comparator 3 Use the result of comparator 3.
  • Page 294 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [91] ECB bypass mode [92] ECB test mode [93] Fire mode [94] RS Flipflop 0 See parameter group 13-1* Comparators. [95] RS Flipflop 1 See parameter group 13-1* Comparators. [96] RS Flipflop 2 See parameter group 13-1* Comparators.
  • Page 295 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description On reference See parameter group 5-3* Digital Outputs for further description. Torque limit See parameter group 5-3* Digital Outputs for further description. Current limit See parameter group 5-3* Digital Outputs for further description. Out of current range See parameter group 5-3* Digital Outputs for further description.
  • Page 296 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [37] Digital input DI32 Use the value of DI32 in the logic rule (high=true). [38] Digital input DI33 Use the value of DI33 in the logic rule (high=true). [39] Start command This event is true if the drive is started (either via digital input,...
  • Page 297 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [92] ECB test mode [93] Fire mode [94] RS flipflop 0 See parameter group 13-1* Comparators. [95] RS flipflop 1 See parameter group 13-1* Comparators. [96] RS flipflop 2 See parameter group 13-1* Comparators.
  • Page 298: 13-1* Comparators

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [229] Comparator 7 Use the result of comparator 7 in the logic rule. [230] Comparator 8 Use the result of comparator 8 in the logic rule. [231] Comparator 9 Use the result of comparator 9 in the logic rule.
  • Page 299 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Par. 13-11 Comparator Operator Par. 13-10 Comparator Operand TRUE longer than. Par. 13-12 . . . Comparator Value . . . Figure 64: Comparators There are digital values that are compared to fixed time values. See the explanation in parameter 13-10 Comparator Operand. Comparators are evaluated once in each scan interval.
  • Page 300 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [18] Pulse input FI29 The value is in %. [19] Pulse input FI33 The value is in %. [20] Alarm number Shows the actual alarm number. NOTICE With this selection, it is not possible to use <...
  • Page 301 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [44] Analog input X49/3 [45] Analog input X49/5 [50] FALSE Use to enter the fixed value False in the comparator. [51] TRUE Use to enter True in the comparator. [52] Control ready The control board receives supply voltage.
  • Page 302 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [77] Above feedback high The feedback exceeds the limit set in parameter 4-57 Warning Feedback High. [80] Thermal warning This operand becomes true when the drive detects any thermal warning, for instance when the temperature exceeds the limit in the motor, the drive, the brake resistor, or thermistor.
  • Page 303 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [118] Logic rule 8 The result of logic rule 8. [119] Logic rule 9 The result of logic rule 9. [120] SL time-out 0 The result of the SLC timer 0. [121] SL time-out 1 The result of the SLC timer 1.
  • Page 304 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [155] SL digital output F Use the result of the SLC output F. [160] Relay 1 Relay 1 is active. [161] Relay 2 Relay 2 is active. [180] Local reference active Active when parameter 3-13 Reference Site is [2] Local or when...
  • Page 305: Rs Flip Flops

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint8 Change during operation: True Select the operator to be used in the comparison. This is an array parameter containing comparator operators 0–5. Option Name Description < NOTICE If [20] Alarm number or [21] Warning number is selected in parameter 3-10 Comparator Operand, [0] <...
  • Page 306 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Parameter 13-15 RS-FF Operand S Parameter 13-16 RS-FF Operand R Figure 65: Reset/Set Flip flops Two parameters are used, and the output can be used in the logic rules and as events. Flip flop output Figure 66: Flip flop Outputs The 2 operators can be selected from a long list.
  • Page 307 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 40: Operators (continued) Parameter Setting Notes Parameter 13-16 RS-FF Operand R [0] Output from parameter 13-41 Logic Rule [27] Logic rule 1 Operator 1 [1] Output from parameter 13-15 RS-FF Parameter 13-51 SL Controller 1 Event[0] [94] RS flip flop 0 Operand S and parameter 13-16 RS-FF...
  • Page 308 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [15] Above feedb. high See parameter group 5-3* Digital Outputs for further description. [16] Thermal warning See parameter group 5-3* Digital Outputs for further description. [17] Mains out of range See parameter group 5-3* Digital Outputs for further description.
  • Page 309 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [45] Left key This event is true [◄] [46] Right key [►] [47] Up key [▲] [48] Down key [▼] [50] Comparator 4 Use the result of comparator 4 in the logic rule. [51] Comparator 5 Use the result of comparator 5 in the logic rule.
  • Page 310 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [104] Relay 2 [109] Relay 7 X34/VLT® Relay Card MCB 105. [110] Relay 8 X34/VLT® Relay Card MCB 105. [111] Relay 9 X34/VLT® Relay Card MCB 105. [140] ATEX ETR cur.
  • Page 311 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [240] SL digital output A [241] SL digital output B [242] SL digital output C [243] SL digital output D [244] SL digital output E [245] SL digital output F 13-16 RS-FF Operand R Default value: Parameter type:...
  • Page 312 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [19] Warning See parameter group 5-3* Digital Outputs for further description. [20] Alarm (trip) See parameter group 5-3* Digital Outputs for further description. [21] Alarm (trip lock) See parameter group 5-3* Digital Outputs for further description.
  • Page 313 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [50] Comparator 4 Use the result of comparator 4 in the logic rule. [51] Comparator 5 Use the result of comparator 5 in the logic rule. [60] Logic rule 4 Use the result of logic rule 4 in the logic rule.
  • Page 314 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [140] ATEX ETR cur. warning Available if parameter 1-90 Motor Thermal Protection is set to [20] ATEX ETR or [21] Advanced ETR. If the alarm 164, ATEX ETR cur.lim.alarm is active, the output is 1.
  • Page 315: Timers

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [244] SL digital output E [245] SL digital output F 6.15.5 13-2* Timers Use the result (true or false) from timers directly to define an event (see parameter 13-51 SL Controller Event), or as boolean input in a logic rule (see parameter 13-40 Logic Rule Boolean 1, parameter 13-42 Logic Rule Boolean 2, or parameter 13-44 Logic Rule Boolean 3).
  • Page 316 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Select the 1st boolean (true or false) input for the selected logic rule. See parameter 13-01 Start Event and parameter 13-02 Stop Event for more information. Option Name Description False True Running In range...
  • Page 317 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [31] SL time-out 1 [32] SL time-out 2 [33] Digital input DI18 [34] Digital input DI19 [35] Digital input DI27 [36] Digital input DI29 [37] Digital input DI32 [38] Digital input DI33 [39]...
  • Page 318 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [83] Broken belt [90] ECB drive mode [91] ECB bypass mode [92] ECB test mode [93] Fire mode [94] RS Flipflop 0 See parameter group 13-1* Comparators. [95] RS Flipflop 1 See parameter group 13-1* Comparators.
  • Page 319 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [150] Pressure 3 high [151] Pressure 4 high [228] Comparator 6 [229] Comparator 7 [230] Comparator 8 [231] Comparator 9 [232] Logic rule 6 [233] Logic rule 7 [234] Logic rule 8 [235]...
  • Page 320 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description DISABLED Ignores • Parameter 13-42 Logic Rule Boolean 2. • Parameter 13-43 Logic Rule Operator 2. • Parameter 13-44 Logic Rule Boolean 3. Evaluates the expression [13-40] AND [13-42]. Evaluates the expression [13-40] OR [13-42].
  • Page 321 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [13] Out of feedb. range [14] Below feedb. low [15] Above feedb. high [16] Thermal warning [17] Mains out of range [18] Reversing [19] Warning [20] Alarm (trip) [21] Alarm (trip lock) [22]...
  • Page 322 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [46] Right key [►] is pressed. Only available on the graphical LCP. [47] Up key [▲] is pressed. Only available on the graphical LCP. [48] Down key [▼] is pressed.
  • Page 323 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [109] Relay 7 X34/VLT® Relay Card MCB 105. [110] Relay 8 X34/VLT® Relay Card MCB 105. [111] Relay 9 X34/VLT® Relay Card MCB 105. [140] ATEX ETR cur. warning Available if parameter 1-90 Motor Thermal Protection is set to [20] ATEX ETR or [21] Advanced ETR.
  • Page 324: Data Type: Uint8

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [241] SL digital output B [242] SL digital output C [243] SL digital output D [244] SL digital output E [245] SL digital output F 13-43 Logic Rule Operator 2 Default value: –...
  • Page 325 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Select the 3rd boolean (true or false) input for the selected logic rule. See parameter 13-01 Start Event and parameter 13-02 Stop Event for more information. Option Name Description False True Running In range...
  • Page 326 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [31] SL time-out 1 [32] SL time-out 2 [33] Digital input DI18 [34] Digital input DI19 [35] Digital input DI27 [36] Digital input DI29 [37] Digital input DI32 [38] Digital input DI33 [39]...
  • Page 327 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [83] Broken belt [90] ECB drive mode [91] ECB bypass mode [92] ECB test mode [93] Fire mode [94] RS Flipflop 0 See parameter group 13-1* Comparators. [95] RS Flipflop 1 See parameter group 13-1* Comparators.
  • Page 328: States

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [150] Pressure 3 high [151] Pressure 4 high [228] Comparator 6 [229] Comparator 7 [230] Comparator 8 [231] Comparator 9 [232] Logic rule 6 [233] Logic rule 7 [234] Logic rule 8 [235]...
  • Page 329 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description On reference Torque limit Current limit Out of current range Below I low Above I high [10] Out of speed range [11] Below speed low [12] Above speed high [13] Out of feedb.
  • Page 330 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [37] Digital input DI32 [38] Digital input DI33 [39] Start command [40] Drive stopped [41] Reset trip [42] Auto-reset trip [43] OK key [OK] is pressed. Only available on the graphical LCP. [44] Reset key [Reset] is pressed.
  • Page 331 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [95] RS Flipflop 1 See parameter group 13-1* Comparators. [96] RS Flipflop 2 See parameter group 13-1* Comparators. [97] RS Flipflop 3 See parameter group 13-1* Comparators. [98] RS Flipflop 4 See parameter group 13-1* Comparators.
  • Page 332 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [232] Logic rule 6 [233] Logic rule 7 [234] Logic rule 8 [235] Logic rule 9 [236] SL time-out 8 [237] SL time-out 9 [238] RS flipflop 8 [239] RS flipflop 9 [240]...
  • Page 333 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [13] Select preset ref 3 Select preset reference 3. [14] Select preset ref 4 Select preset reference 4. [15] Select preset ref 5 Select preset reference 5. [16] Select preset ref 6 Select preset reference 6.
  • Page 334 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [61] Reset counter B Resets counter B to 0. [62] Counter A (up) The motor runs at a reference which exceeds the value in parameter 4-55 Warning Reference High. [63] Counter A (down) [64]...
  • Page 335 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description On reference Torque limit Current limit Out of current range Below I low Above I high [10] Out of speed range [11] Below speed low [12] Above speed high [13] Out of feedb.
  • Page 336 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [37] Digital input DI32 [38] Digital input DI33 [39] Start command [40] Drive stopped [41] Reset trip [42] Auto-reset trip [43] OK key [OK] is pressed. Only available on the graphical LCP. [44] Reset key [Reset] is pressed.
  • Page 337 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [95] RS Flipflop 1 See parameter group 13-1* Comparators. [96] RS Flipflop 2 See parameter group 13-1* Comparators. [97] RS Flipflop 3 See parameter group 13-1* Comparators. [98] RS Flipflop 4 See parameter group 13-1* Comparators.
  • Page 338 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [232] Logic rule 6 [233] Logic rule 7 [234] Logic rule 8 [235] Logic rule 9 [236] SL time-out 8 [237] SL time-out 9 [238] RS flipflop 8 [239] RS flipflop 9 [240]...
  • Page 339 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [14] Select preset ref 4 Select preset reference 4. [15] Select preset ref 5 Select preset reference 5. [16] Select preset ref 6 Select preset reference 6. [17] Select preset ref 7 Select preset reference 7.
  • Page 340 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [62] Counter A (up) The motor runs at a reference which exceeds the value in parameter 4-55 Warning Reference High. [63] Counter A (down) [64] Counter B (up) [65] Counter B (down) [70]...
  • Page 341 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Torque limit Current limit Out of current range Below I low Above I high [10] Out of speed range [11] Below speed low [12] Above speed high [13] Out of feedb.
  • Page 342 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [38] Digital input DI33 [39] Start command [40] Drive stopped [41] Reset trip [42] Auto-reset trip [43] OK key [OK] is pressed. Only available on the graphical LCP. [44] Reset key [Reset] is pressed.
  • Page 343 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [96] RS Flipflop 2 See parameter group 13-1* Comparators. [97] RS Flipflop 3 See parameter group 13-1* Comparators. [98] RS Flipflop 4 See parameter group 13-1* Comparators. [99] RS Flipflop 5 See parameter group 13-1* Comparators.
  • Page 344 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [233] Logic rule 7 [234] Logic rule 8 [235] Logic rule 9 [236] SL time-out 8 [237] SL time-out 9 [238] RS flipflop 8 [239] RS flipflop 9 [240] SL digital output A [241]...
  • Page 345 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [14] Select preset ref 4 Select preset reference 4. [15] Select preset ref 5 Select preset reference 5. [16] Select preset ref 6 Select preset reference 6. [17] Select preset ref 7 Select preset reference 7.
  • Page 346 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [62] Counter A (up) The motor runs at a reference which exceeds the value in parameter 4-55 Warning Reference High. [63] Counter A (down) [64] Counter B (up) [65] Counter B (down) [70]...
  • Page 347 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Torque limit Current limit Out of current range Below I low Above I high [10] Out of speed range [11] Below speed low [12] Above speed high [13] Out of feedb.
  • Page 348 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [38] Digital input DI33 [39] Start command [40] Drive stopped [41] Reset trip [42] Auto-reset trip [43] OK key [OK] is pressed. Only available on the graphical LCP. [44] Reset key [Reset] is pressed.
  • Page 349 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [96] RS Flipflop 2 See parameter group 13-1* Comparators. [97] RS Flipflop 3 See parameter group 13-1* Comparators. [98] RS Flipflop 4 See parameter group 13-1* Comparators. [99] RS Flipflop 5 See parameter group 13-1* Comparators.
  • Page 350 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [233] Logic rule 7 [234] Logic rule 8 [235] Logic rule 9 [236] SL time-out 8 [237] SL time-out 9 [238] RS flipflop 8 [239] RS flipflop 9 [240] SL digital output A [241]...
  • Page 351 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [14] Select preset ref 4 Select preset reference 4. [15] Select preset ref 5 Select preset reference 5. [16] Select preset ref 6 Select preset reference 6. [17] Select preset ref 7 Select preset reference 7.
  • Page 352: User-Defined Alerts And Readouts

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [62] Counter A (up) The motor runs at a reference which exceeds the value in parameter 4-55 Warning Reference High. [63] Counter A (down) [64] Counter B (up) [65] Counter B (down) [70]...
  • Page 353 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Actions reflected in parameter 16-03 Status Word and alert parameters When an action containing trip is selected and triggered, the drive trips, bit 3 in the basic status word is set, and the corresponding hex value is shown in parameter 13-97 Alert Alarm Word.
  • Page 354 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 41: Example of Setting up Triggers, Actions, and Readouts (continued) Name Setup 1 1392.3 Alert Text User Alert 1392.4 Alert Text User Alert 1392.5 Alert Text User Alert 1392.6 Alert Text User Alert 1392.7...
  • Page 355 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [26] Logic rule 0 [27] Logic rule 1 [28] Logic rule 2 [29] Logic rule 3 [30] SL time-out 0 [31] SL time-out 1 [32] SL time-out 2 [33] Digital input DI18 [34]...
  • Page 356 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [145] Pressure 2 low [146] Pressure 3 low [147] Pressure 4 low [148] Pressure 1 high [149] Pressure 2 high [150] Pressure 3 high [151[ Pressure 4 high [228] Comparator 6 [229]...
  • Page 357 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Stop Stop & warning Jogging Jogging & warning Max speed Max speed & warn [10] Stop and trip [11] Stop and trip w manual reset [12] Trip [13] Trip w manual reset [14]...
  • Page 358: Parameter Group 14-** Special Functions

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Shows the status word of a user-defined alarm in hex code. Parameter Group 14-** Special Functions 6.16 14-0* Inverter Switching 6.16.1 14-00 Switching Pattern Default value: Parameter type: – Option Setup: All setups Conversion index:...
  • Page 359: Default Value: [0] Off

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description 3.5 kHz 4.0 kHz 5.0 kHz 6.0 kHz 7.0 kHz [10] 8.0 kHz [11] 10.0 kHz [12] 12.0 kHz [13] 14.0 kHz [14] 16.0 kHz 14-02 Switching Pattern Shift Frequency Default value: Parameter type: Size related...
  • Page 360 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* Select [0] Off for no overmodulation of the output voltage to avoid torque ripple on the motor shaft. Select [1] On to enable the overmodulation function for the output voltage.
  • Page 361: Mains On/Off

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 14-1* Mains On/Off 6.16.2 This parameter group contains parameters for configuring the monitoring and handling of a mains failure. If a mains failure appears, the drive tries to continue in a controlled way until the power in the DC link is exhausted. 14-10 Mains Failure Default value: [0] No function...
  • Page 362 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description together with a flying start, which occurs when the mains is restored. Kinetic back-up Kinetic back-up ensures that the drive keeps running as long as there is energy in the system due to the inertia from motor and load.
  • Page 363 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description above the reference speed. This leads to the motor running mechanically until the speed is above the reference speed and the situation in point 2 occurs. Instead of waiting for that criterion, point 3 is introduced.
  • Page 364 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description SP-11*1.35 t [S] n [RPM] SP-15 t [S] Figure 70: Kinetic Back-up Trip w/Recovery, Mains Returns Above Parameter 14-15 Kin. Back-up Trip Recovery Level A Normal operation B Mains Failure C Kinetic back-up D Mains return...
  • Page 365 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description If the ramp is quicker than the ramp-down speed of the application, the ramping generates current. This results in a higher U , which is limited using the brake chopper/resistor brake.
  • Page 366 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions This parameter defines the threshold voltage at which the function in parameter 14-10 Mains Failure is activated. Select the detection level depending on the supply quality. For a supply of 380 V, set parameter 14-11 Mains Fault Voltage Level to 342 V. This results in a DC detection level of 462 V (parameter 14-11 Mains Fault Voltage Level x 1.35).
  • Page 367: Trip Reset

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint32 Change during operation: True This parameter specifies the kinetic back-up trip recovery level. The unit is defined in parameter 0-02 Motor Speed Unit. 14-16 Kin.
  • Page 368 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Select the reset function after tripping. Once reset, the drive can be restarted. NOTICE The motor may start without warning. If the specified number of automatic resets is reached within 10 minutes, the drive enters [0] Manual reset mode.
  • Page 369 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Use this parameter to specify normal operation, to perform tests, or to initialize all parameters except parameter 15-03 Power Up's, parameter 15-04 Over Temp's, and parameter 15-05 Over Volt's. This function is active only when the power is cycled to the drive. Select [0] Normal operation for normal operation of the drive with the motor in the selected application.
  • Page 370 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* Normal operation Normal operation of the drive with the motor in the selected application. Control card test Remember to set switches S201 (A53) and S202 (A54) as specified in the parameter description when performing a control card test.
  • Page 371: Current Limit Control

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint8 Change during operation: True When the drive detects an overvoltage in the set time, a trip is effected after the set time. If the value is 0, protection mode is disabled. 6.16.4 14-3* Current Limit Control The drive features an integral current limit controller, which is activated when the motor current, and thus the torque, is higher than the...
  • Page 372: Energy Optimizing

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions NOTICE This parameter is active in flux mode only. Option Name Description Disabled Disables stall protection in field weakening flux mode and might cause the motor to be lost. [1]* Enabled Enables stall protection in field weakening flux mode.
  • Page 373 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions NOTICE This parameter is not active when parameter 1-10 Motor Construction is set to [1] PM non-salient SPM. Enter the minimum frequency at which the automatic energy optimization (AEO)is to be active. 14-43 Motor Cosphi Default value: Parameter type:...
  • Page 374: Environment

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [13] External fan off [255]* Ready to operate 14-48 PROFIEnergy Desired State Default value: Parameter type: [255] Ready to operate Option Setup: 2 setups Conversion index: – Data type: Change during operation: Uint8...
  • Page 375 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 42: Motor Filter Types (continued) Motor construction Filter type MCC 102 dU/dt Filters MCC 101 Sine-wave Filters and MCC 201 All-mode Filters Valid P1-29 AMA options [1] Complete AMA [2] Reduced AMA AMA II not available [2] Reduced AMA...
  • Page 376 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Disables DC-link compensation. Enables DC-link compensation. Advanced Improved compensation of DC-link ripple caused by mains frequency and phase imbalance. NOTICE Parameter 0-03 Regional Setting must be set correctly according to the actual mains grid.
  • Page 377 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Select the drive action if a fan fault is detected. Option Name Description Disabled [1]* Warning Trip 14-55 Output Filter Default value: [0] No filter Parameter type: Option Setup: All setups Conversion index: –...
  • Page 378: Data Type: Uint16

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Sine-Wave Filter Fixed NOTICE SINE-WAVE FILTER FIXED SETTING Ensures that the filter is operated within the safe range of switching frequencies. Use the setting only for VLT® MCC 101 Sine-wave Filters.
  • Page 379: Auto Derate

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Set the C (capacitance) value of the output filter in uF, when using VLT® MCC 101 Sine-wave filter and VLT® MCC 201 All-mode filter. See the filter product label for the capacitance value. The value is the equivalent star-connected capacitance of the filter. When the filters are installed in parallel, enter the combined capacitance value of the paralleled filter.
  • Page 380: Default Value

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Current % of rated Time Desired current>100% Inverter load counter 90.7 Time Warning Warning 130BA260.10 Figure 74: Output Current in Overload Condition If the motor is unable to run continuously with the demanded capacity, run it at reduced speed for a while. Select parameter 14-61 Function at Inverter Overload to automatically reduce motor speed until the output current is below 100% of the rated current (set in parameter 14-62 Inv.
  • Page 381: Options

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* Trip The drive trips (trip lock) and generates an alarm. Cycle power to reset the alarm. The motor restarts when the heat sink temperature has dropped below the alarm limit. Derate If the critical temperature is exceeded, the output current is reduced until the allowable temperature has been reached.
  • Page 382: Fault Settings

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Select this option to use the 24 V DC supply of the drive. [1]* Select this option if a 24 V DC external supply is used to power the option. Inputs/outputs are galvanically isolated from the drive when operated from an external supply.
  • Page 383 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Trip Changing a fault level from default option [3] Trip Lock to [2] Trip leads to the automatic reset of the alarm. For alarms involving overcurrent, the drive has a hardware protection that issues a 3- minute recovery after 2 consecutive overcurrent incidents.
  • Page 384 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 43: Possible Actions when Selected Alarms Appear (continued) Failure Parameter Alarm Warning Trip Trip lock Trip with delayed reset Heat sink 1490.13 – – – temperature Heat sink 1490.14 –...
  • Page 385: Parameter Group 15-** Drive Information

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions VLT® Motion Control Tool MCT 10 has the element numbers listed in the column ID. Use this table with MCT 10 to get information about specific fault levels. Parameter Group 15-** Drive Information 6.17 15-0* Operating Data 6.17.1...
  • Page 386 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 15-05 Over Volt's Default value: Parameter type: Range, 0 - 65535 Setup: All setups Conversion index: Data type: Uint16 Change during operation: False View the number of drive overvoltages. 15-06 Reset kWh Counter Default value: [0] Do not reset Parameter type:...
  • Page 387: Data Log Settings

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 15-1* Data Log Settings 6.17.2 The data log enables continuous logging of up to 4 data sources (parameter 15-10 Logging Source) at individual rates (parameter 15-11 Logging Interval). A trigger event (parameter 15-12 Trigger Event) and window (parameter 15-14 Samples Before Trigger) are used to start and stop the logging conditionally.
  • Page 388 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [1630] DC link voltage [1632] Brake energy /s [1633] Brake energy average [1634] Heatsink temp. [1635] Inverter thermal [1644] Speed Error [RPM] [1645] Motor phase U current [1646] Motor phase V current [1647]...
  • Page 389 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [1830] Analog input X42/1 [1831] Analog input X42/3 [1832] Analog input X42/5 [1833] Analog out X42/7 [V] [1834] Analog out X42/9 [V] [1835] Analog out X42/11 [V] [1840] Analog input X49/1 [1841]...
  • Page 390 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* False True Running In range On reference Torque limit Current limit Out of current range Below I low Above I high [10] Out of speed range [11] Below speed low [12]...
  • Page 391 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [36] Digital input DI29 [37] Digital input DI32 [38] Digital input DI33 [50] Comparator 4 [51] Comparator 5 [60] Logic rule 4 [61] Logic rule 5 15-13 Logging Mode Default value: [0] Log always Parameter type:...
  • Page 392 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* Disabled Enabled Enable message. 15-17 Service Log Trigger Alarm Default value: Parameter type: Range, 0=Off - 9999 Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Enter alarm number that triggers the Service Log write to flash.
  • Page 393 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [34] Digital input DI19 [35] Digital input DI27 [36] Digital input DI29 [37] Digital input DI32 [38] Digital input DI33 [50] Comparator 4 [51] Comparator 5 [60] Logic rule 4 [61] Logic rule 5...
  • Page 394: Service Log

    The relevant service log file can then be analyzed as a scope in MCT 10. Danfoss specifies the channels. All scope functions such as Auto- scale and Diagnostics can be used. The HEX ad binary value can be shown, which also helps with the analysis.
  • Page 395 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 44: Alarms Triggering a Service Log Record (continued) Alarm Alarm log data Parameter Speed (RPM) Parameter 16-17 Speed [RPM] Reference % Parameter 16-02 Reference % DC-link voltage Parameter 16-30 DC Link Voltage Motor phase U current Parameter 16-45 Motor Phase U Current Motor phase V current...
  • Page 396 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Channels 1–8 are fixed channels with unfiltered signals and cannot be changed. Channels 9–11 are filtered and refer to parameter 0-20 to 0-22, which are reflected in the 3 upper lines in the LCP. Clearing the Service Log 6.17.4 The flash memory stores up to 24 records.
  • Page 397 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Figure 75: MCT 10, Read From Drive The service log view in MCT 10 looks as shown in 76. Use the cursor to view the detailed readings at a specific time. Figure Figure 76: Service Log View, 5 s Use the zoom function to focus on the last 250 ms before the fault.
  • Page 398: Historic Log

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 46: Alarms Triggering a Service Log Record (continued) Alarm title Torque limit Over current Earth (ground) fault Short circuit Start failed Brake resistor Brake overload Brake IGBT Brake check U phase loss V phase loss W phase loss...
  • Page 399 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 15-20 Historic Log: Event Default value: Parameter type: Range, 0 - 255, Array [50] Setup: All setups Conversion index: Data type: Uint8 Change during operation: False View the event type of the logged events. 15-21 Historic Log: Value Default value: Parameter type:...
  • Page 400: Alarm Log

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: TimeOfDay Change during operation: False Array parameter; Date & Time 0 – 49. This parameter shows which time the logged event occurred. 6.17.9 15-2* Operating Data Log 15-28 kWh Counter Reset Time Default value: Size related Parameter type:...
  • Page 401: Drive Identification

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions View the time when the logged event occurred. Time is measured in s from start-up of the drive. 15-33 Alarm Log: Date and Time Default value: Size related Parameter type: Range, 0 - 0, Array [10] Setup: All setups...
  • Page 402 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: VisStr[5] Change during operation: False View the combined SW version (or package version) consisting of power SW and control SW. 15-44 Ordered Typecode String Default value: Parameter type: Range, 0 - 40...
  • Page 403 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: VisStr[20] Change during operation: False View the control card software version number. 15-50 SW ID Power Card Default value: Parameter type: Range, 0 - 20 Setup: Conversion index: All setups...
  • Page 404 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: VisStr[40] Change during operation: False See the drive vendor name. 15-58 Smart Setup Filename Default value: Parameter type: Size related Range, 0 - 20 Setup: All setups Conversion index: Data type: Change during operation: VisStr[16]...
  • Page 405 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 15-63 Option Serial No Default value: Parameter type: Range, 0 - 18, Array [8] Setup: All setups Conversion index: Data type: VisStr[18] Change during operation: False View the installed option serial number. 15-64 Application Version Default value: Parameter type:...
  • Page 406 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 15-74 Option in Slot C0/E0 Default value: Parameter type: Range, 0 - 30 Setup: All setups Conversion index: Data type: VisStr[30] Change during operation: False View the type code string for the option installed in slot C and a translation of the type code string. For example, for type code string CXXXX, the translation is No option.
  • Page 407: Parameter Info

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Enter the preset fan running hours counter, see parameter 15-80 Fan Running Hours. This parameter cannot be selected via the serial port RS485. 15-87 kWh Counter Hires Default value: 0 kWh Parameter type: Range, 0 - 2147483647 kWh Setup:...
  • Page 408: Parameter Group 16-** Data Readouts

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint16 Change during operation: False This parameter contains data used by the VLT® Motion Control Tool MCT 10. Parameter Group 16-** Data Readouts 6.18 16-0* General Status 6.18.1...
  • Page 409: Motor Status

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Change during operation: False View the 2-byte word sent with the status word to the fieldbus master reporting the main actual value. 16-09 Customer Readout Default value: Parameter type: 0 CustomReadoutUnit Range, -999999.99 CustomReadoutUnit -...
  • Page 410 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions View the motor frequency without resonance damping. 16-14 Motor Current Default value: Parameter type: Range, 0 - 10000 A Setup: All setups Conversion index: Data type: Int32 Change during operation: False View the motor current measured as an average value, I .
  • Page 411 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions View the calculated thermal load on the motor. The cutout limit is 100%. The basis for calculation is the ETR function selected in parameter 1-90 Motor Thermal Protection. 16-19 Thermistor Sensor Temperature Default value: 0 °C Parameter type:...
  • Page 412: Drive Status

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Shows the calibrated stator resistance. 16-27 Power Filtered [hp] Default value: 0 hp Parameter type: Range, 0 - 10000 hp Setup: All setups Conversion index: Data type: Int32 Change during operation: False Shows the calibrated stator resistance.
  • Page 413 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint8 Conversion index: False View the percentage load on the inverter. 16-36 Inv. Nom. Current Default value: Parameter type: Size related Range, 0.01 - 10000 A Setup: All setups Conversion index: Data type: Change during operation:...
  • Page 414 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* 16-42 Service Log Counter Default value: Parameter type: Range, 0 - 24 Setup: All setups Conversion index: Data type: Uint8 Change during operation: True Shows the number of service logs stored in the ServiceLog file. If the ServiceLog file is full, clear the logged data by selecting option [5] Clear service logs in parameter 14-22 Operation Mode.
  • Page 415: Ref. & Feedb

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 16-46 Motor Phase V Current Default value: Parameter type: Range, 0 - 10000 A Setup: All setups Conversion index: Data type: Int32 Change during operation: True Shows the motor phase V current.
  • Page 416 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 16-52 Feedback[Unit] Default value: 0 ProcessCtrlUnit Parameter type: -999999.999 ProcessCtrlUnit - 999999.999 ProcessCtrlUnit Setup: Conversion index: All setups Data type: Int32 Change during operation: False View value of resulting feedback value after processing of feedback 1-3 in parameter 3-00 Reference Range, parameter 16-54 Feedback 1 [Unit], parameter 16-55 Feedback 2 [Unit], and parameter 16-56 Feedback 3 [Unit] in the feedback manager.
  • Page 417: Inputs And Outputs

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Int32 Change during operation: False View the value of feedback 3, see parameter group 20-0* Feedback. The value is limited by the settings in parameter 20-13 Minimum Reference/Feedb. and parameter 20-14 Maximum Reference/Feedb. Units are as set in parameter 20-12 Reference/Feedback Unit. 16-58 PID Output [%] Default value: Parameter type:...
  • Page 418 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 47: Active Digital Inputs (continued) Input Digital input VLT® General Purpose I/O MCB 101 terminal X30/2. Bit 10–63 Reserved for future terminals. 0 0 0 0 0 Figure 77: Relay Settings 16-61 Terminal 53 Switch Setting Default value: Parameter type:...
  • Page 419 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Int32 Change during operation: False View the actual value at input 53. 16-63 Terminal 54 Switch Setting Default value: [0] Current Parameter type: Option Setup: Conversion index:...
  • Page 420 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions View the actual frequency rate on terminal 29. 16-68 Freq. Input #33 [Hz] Default value: Parameter type: Range, 0 - 130000 Setup: All setups Conversion index: Data type: Int32 Change during operation: False View the actual value of the frequency applied at terminal 33 as an impulse input.
  • Page 421 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Int32 Change during operation: True View the present value of counter A. Counters are useful as comparator operands, see parameter 13-10 Comparator Operand. Reset or change the value either via digital inputs (parameter group 5-1* Digital Inputs) or by using an SLC action (parameter 13-52 SL Controller Action).
  • Page 422: Fieldbus & Fc Port

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 16-79 Analog Out X45/3 [mA] Default value: Parameter type: Range, 0 - 30 Setup: All setups Conversion index: Data type: Int16 Change during operation: False Shows the actual output value at terminal X45/3. The value shown reflects the selection in parameter 6-80 Terminal X45/3 Output. 16-8* Fieldbus &...
  • Page 423: Diagnosis Readouts

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Change during operation: False View the 2-byte status word (STW) sent to the fieldbus master. Interpretation of the status word depends on the fieldbus option installed and the control word profile selected in parameter 8-10 Control Word Profile. 16-87 Bus Readout Alarm/Warning Default value: Parameter type:...
  • Page 424 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 16-94 Ext. Status Word Default value: Parameter type: Range, 0 - 4294967295 Setup: All setups Conversion index: Data type: Uint32 Change during operation: False Returns the extended warning word sent via the serial communication port in hex code. 16-95 Ext.
  • Page 425 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 48: Maintenance Word Position 4⇒ Valve Fan bearings Pump bearings Motor bearings Position 3⇒ Pump seals Temperature Flow transmitter Pressure transmitter transmitter Position 2⇒ Drive system health Drive cooling fan Filter Fan belt check...
  • Page 426: Maintenance Log

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Shows the alarm word sent via the serial communication port in hex code. 16-98 Warning Word 3 Default value: Parameter type: Range, 0 - 4294967295 Setup: All setups Conversion index: Data type: Uint32 Change during operation:...
  • Page 427: Fire Mode Log

    10 latest activations of fire mode or the alarm number of the critical alarm that was suppressed as this affects the warranty of the drive. Suppressed alarm numbers are stored and can only be reset by a Danfoss service inspection.
  • Page 428: Parameter Log

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 18-1* Parameter Log 6.19.3 18-13 Parameter Number Default value: 0 N/A Parameter type: Range, 0 - 0xFFFF N/A, Array [10] Setup: All setups Conversion index: Data type: Change during operation: Uint16 False Shows the parameter which is most recently changed.
  • Page 429 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 18-18 Value Before Change as Integer Default value: Parameter type: Range, -2147483648 - 2147483647, Array [10] Setup: Conversion index: All setups Data type: Int32 Change during operation: False Shows the previous value of the parameter as integer, without scaling or unit conversion. The parameter only shows integer data. 18-19 Value Before Change Default value: Size related...
  • Page 430 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 18-33 Analog Input X42/7 [V] Default value: Parameter type: Range, 0 - 30 Setup: All setups Conversion index: Int16 Data type: Int16 Change during operation: False Readout of the value of the signal applied to terminal X42/7 on the analog I/O card. The value shown reflects the selection in parameter 26-40 Terminal X42/7 Output.
  • Page 431 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Int16 Change during operation: True View the actual temperature measured at input X48/7. The temperature unit is based on the selection in parameter 35-02 Term. X48/7 Temperature Unit. 18-39 Temp.
  • Page 432: Last Warning

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 18-44 Analog Input X49/9 Default value: Parameter type: Range, 0 - 30 Setup: All setups Conversion index: Data type: Int16 Change during operation: False Shows the actual value at output of terminal X49/9 in V or mA. The value reflects the selection in parameter 36-50 Terminal X49/9 Analog Output.
  • Page 433: Flow Calculation

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 18-50 Sensorless Readout [Unit] Default value: 0 SensorlessUnit Parameter type: Range, -999999.999 - 999999.999 SensorlessUnit Setup: Conversion index: All setups Data type: Int32 Change during operation: False This parameter shows a readout of the pressure or flow based on the sensorless calculations. This value is not used for control and will only be updated if sensorless data supports both flow and pressure.
  • Page 434 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 18-6* Diagnosis Readout 2 6.19.10 18-67 Alarm Word 4 Default value: Parameter type: Range, 0 - 4294967295 Setup: All setups Conversion index: Data type: Uint32 Change during operation: False View alarm word 4 as a hexadecimal value. 18-68 Warning Word 4 Default value: Parameter type:...
  • Page 435 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions This parameter identifies which active inrush produces the data shown in parameter 18-70 Mains Voltage, parameter 18-71 Mains Frequency, parameter 18-72 Mains Imbalance, and parameter 18-75 Rectifier DC Volt. 1 = inrush 1, 2 = inrush 2, and so on. 18-74 Inrush Mode Default value: Parameter type:...
  • Page 436 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Int16 Change during operation: True View the mains frequency measurement. The indices are as follows: 0 = inrush1 1 = inrush2 18-78 Mains Imbalance 2 Default value: Parameter type: Range, 0 - 100%, Array [4] Setup: Conversion index:...
  • Page 437 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setpoint to Reference Handling Setpoint 1 P 20-21 Setpoint 2 P 20-22 Multi setpoint min. Setpoint 3 Multi setpoint max. P 20-23 Feedback Feedback 1 Feedback 1 only Feedback conv. Feedback 1 Source Feedback 2 only P 20-01...
  • Page 438 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Analog input X30/12 Analog input X42/1 [10] Analog input X42/3 [11] Analog input X42/5 [15] Analog input X48/2 [16] Analog input X49/1 [17] Analog input X49/3 [18] Analog input X49/5 [19] Pressure 3...
  • Page 439 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Pressure to temperature Used in compressor applications to provide temperature feedback using a pressure sensor. The temperature of the refrigerant is calculated using the following formula: where A1, A2, and A3 are refrigerant-specific constants. Select the refrigerant in parameter 20-30 Refrigerant.
  • Page 440 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [11] [12] Pulse/s [20] [21] l/min [22] [23] [24] /min [25] [30] kg/s [31] kg/min [32] kg/h [33] t/min [34] [40] [41] m/min [45] [60] °C [70] mbar [71] [72]...
  • Page 441 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [130] lb/s [131] lb/min [132] lb/h [140] ft/s [141] ft/min [145] [160] °F [170] [171] lb/in [172] in WG [173] ft WG [174] in HG [180] 20-03 Feedback 2 Source Default value: [0] No function Parameter type:...
  • Page 442 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Analog input X42/1 [10] Analog input X42/3 [11] Analog input X42/5 [15] Analog input X48/2 [16] Analog input X49/1 [17] Analog input X49/3 [18] Analog input X49/5 [19] Pressure 3 [20]...
  • Page 443 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Pressure to temperature Used in compressor applications to provide temperature feedback using a pressure sensor. The temperature of the refrigerant is calculated using the following formula: where A1, A2, and A3 are refrigerant-specific constants. Select the refrigerant in parameter 20-30 Refrigerant.
  • Page 444 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [11] [12] Pulse/s [20] [21] l/min [22] [23] [24] /min [25] [30] kg/s [31] kg/min [32] kg/h [33] t/min [34] [40] [41] m/min [45] [60] °C [70] mbar [71] [72]...
  • Page 445 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [130] lb/s [131] lb/min [132] lb/h [140] ft/s [141] ft/min [145] [160] °F [170] [171] lb/in [172] in WG [173] ft WG [174] in HG [180] 20-06 Feedback 3 Source Default value: [0] No function Parameter type:...
  • Page 446 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Analog input X42/1 [10] Analog input X42/3 [11] Analog input X42/5 [15] Analog input X48/2 [16] Analog input X49/1 [17] Analog input X49/3 [18] Analog input X49/5 [19] Pressure 3 [20]...
  • Page 447 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Pressure to temperature Used in compressor applications to provide temperature feedback using a pressure sensor. The temperature of the refrigerant is calculated using the following formula: where A1, A2, and A3 are refrigerant-specific constants. Select the refrigerant in parameter 20-30 Refrigerant.
  • Page 448 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [11] [12] Pulse/s [20] [21] l/min [22] [23] [24] /min [25] [30] kg/s [31] kg/min [32] kg/h [33] t/min [34] [40] [41] m/min [45] [60] °C [70] mbar [71] [72]...
  • Page 449 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [130] lb/s [131] lb/min [132] lb/h [140] ft/s [141] ft/min [145] [160] °F [170] [171] lb/in [172] in WG [173] ft WG [174] in HG [180] 20-12 Reference/Feedback Unit Default value: –...
  • Page 450 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [30] kg/s [31] kg/min [32] kg/h [33] t/min [34] [40] [41] m/min [45] [60] °C [70] mbar [71] [72] [73] [74] m WG [75] mm Hg [80] [120] [121] gal/s...
  • Page 451 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [171] lb/in [172] in WG [173] ft WG [174] in HG [180] 20-13 Minimum Reference/Feedb. Default value: Parameter type: 0 ProcessCtrlUnit Range, -999999.999 - 999999.999 ProcessCtrlUnit Setup: All setups Conversion index: Data type:...
  • Page 452 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True This parameter determines how the 3 possible forms of feedback are used to control the output frequency of the drive. Option Name Description...
  • Page 453 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Maximum Sets up the PID controller to compare feedback 1, feedback 2, and feedback 3. The PID controller uses the highest value as the feedback. Set any unused feedback to [0] No function in: NOTE: •...
  • Page 454 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Transmitted over various serial communication protocols. The drive can be configured to handle multi-zone applications. 2 different multi-zone applications are supported: Multi-zone, single setpoint Multi-zone, multi-setpoint Examples 1 and 2 show the difference between the 2 applications. Example 1 - Multi-zone, single setpoint In an office building, a VAV (variable air volume) VLT®...
  • Page 455 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Int32 Change during operation: True NOTICE The setpoint entered in this parameter is added to any other references that are enabled. Setpoint 1 is used in closed-loop mode to enter a setpoint reference that is used by the PID controller of the drive. 20-22 Setpoint 2 Default value: 0 ProcessCtrlUnit...
  • Page 456 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* R134a R404A R407C R410A R502 R744 User defined R500 [10] R503 [11] R114 [12] R142b [14] [15] R227 [16] R401A [17] R507 [18] [19] [20] R717 [21] R407A [22]...
  • Page 457 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [32] R413A [33] Isceon 29 [34] R427A [35] R438A [36] R513A/OpteonXP10 [37] R407F [38] R1234ze [39] R1234yf [40] R448A [41] R449A [42] R452A [43] R450A [44] R452B [45] R454B [46]...
  • Page 458 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Int32 Change during operation: True Use this parameter to enter the value of coefficient A2 when parameter 20-30 Refrigerant is set to [7] User defined. 20-33 User Defined Refrigerant A3 Default value: Parameter type: Range, 200 - 300...
  • Page 459 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Used for setting the area of the air ducts in connection with feedback conversion pressure/velocity to flow. The unit (in ) is determined by the setting of parameter 0-03 Regional Settings. Fan 2 is used with feedback 2. In case of flow difference control, set parameter 20-20 Feedback Function to [1] Difference to control flow fan 1 –...
  • Page 460: Pid Autotuning

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [74] m WG [75] mm Hg [120] [121] gal/s [122] gal/min [123] gal/h [124] [125] [126] /min [127] [170] [171] lb/in [172] in WG [173] ft WG [174] in Hg 20-69 Sensorless Information...
  • Page 461 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions NOTICE If the feedback goes outside the specified limits (2073 and 2074) defined during autotune setup, the autotuning is discarded. The limits also serve as application protection during autotuning execution. NOTICE It is not possible to run the motor at maximum or minimum speed when manually adjusting the motor speed due to the need of increasing or decreasing the motor speed during autotuning.
  • Page 462 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Select the application response speed if it is known. The default setting is sufficient for most applications. A more precise value decreases the time needed for carrying out PID adaptation. The setting has no impact on values of parameters and only affects the auto-tuning speed.
  • Page 463 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Enter the minimum allowable feedback level in user units as defined in parameter 20-12 Reference/Feedback Unit. If the level drops below parameter 20-73 Minimum Feedback Level, auto tuning is aborted and an error message appears in the LCP. 20-74 Maximum Feedback Level Default value: 999999 ProcessCtrlUnit...
  • Page 464 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* Normal The output frequency of the drive decreases when the feedback is greater than the setpoint reference. This behavior is common for pressure-controlled supply fan and pump applications. Inverse The output frequency of the drive increases when the feedback is greater than the setpoint reference.
  • Page 465: Pid Controller

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 20-9* PID Controller 6.20.8 This parameter group enables manual adjustment of the PID controller. By adjusting the PID controller parameters, the control performance may be improved. 20-91 PID Anti Windup Default value: [1] On Parameter type:...
  • Page 466 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint16 Change during operation: True The integrator accumulates a contribution to the output from the PID controller as long as there is a deviation between the reference/ setpoint and feedback signals.
  • Page 467 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions To control a modulating device, for example a valve motor, this device must be a positioning servo motor with built-in electronics accepting either a 0–10 V control signal from VLT® Analog I/O Option MCB 109 or a 0/4–20 mA control signal from VLT® General Purpose I/O MCB 101.
  • Page 468 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint8 Change during operation: True This parameter defines the application response. The default mode should be sufficient for most applications. If the relative application speed is known, it can be selected here. This decreases the time needed for carrying out PID autotuning. Option Name Description...
  • Page 469 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Parameter 21-30 Ext. 2 Ref./Feedback Unit for EXT CL 2. Parameter 21-50 Ext. Ref./Feedback Unit EXT CL. If the level drops below parameter 21-03 Minimum Feedback Level, PID auto tuning is aborted, and an error message appears in the display.
  • Page 470 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 21-1* Closed Loop 1 Ref/Feedback 6.21.3 Drive External reference P 21-13 Ext. Output closed-loop signal Setpoint controller P 6-50 P 21-15 Feedback P 21-14 Output MCB 101 signal P 6-60 Figure 81: Closed Loop 1 Ref/Feedback 21-10 Ext.
  • Page 471 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [25] [30] kg/s [31] kg/min [32] kg/h [33] t/min [34] [40] [41] m/min [45] [60] °C [70] mbar [71] [72] [73] [74] m WG [75] mm Hg [80] [120] [121]...
  • Page 472 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [170] [171] lb/in [172] in WG [173] ft WG [174] in HG [180] 21-11 Ext. 1 Minimum Reference Default value: 0 ExtPID1Unit Parameter type: Range, -999999.999 - par. 21-12 Ext.PID1Unit Setup: All setups...
  • Page 473 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* No function Use this selection if feedback is not used. Analog input 53 Analog input 54 Analog input X30/11 Analog input X30/12 [11] Local bus reference [20] Digital pot.
  • Page 474 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Pulse input 29 Pulse input 33 Analog input X30/11 Analog input X30/12 Analog input X42/1 [10] Analog input X42/3 [11] Analog input X42/5 [15] Analog input X48/2 [16] Analog input X49/1 [17]...
  • Page 475 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 21-17 Ext. Reference [Unit] Default value: 0 ExtPID1Unit Parameter type: Range, -999999.999 - 999999.999 Ext.PID1Unit Setup: Conversion index: All setups Data type: Int32 Change during operation: True Readout of the reference value for the closed-loop 1 controller. 21-18 Ext.
  • Page 476 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions The proportional gain indicates the number of times the error between the setpoint and the feedback signal is to be applied. If (error x gain) jumps with a value equal to what is set in parameter 20-14 Maximum Reference/Feedb., the PID controller tries to change the output speed equal to what is set in parameter 4-13 Motor Speed High Limit [RPM]/parameter 4-14 Motor Speed High Limit [Hz].
  • Page 477 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Enter the on-reference bandwidth. When the PID control error (the difference between the reference and the feedback) is less than the value of this parameter, the on-reference status bit is high. 21-3* Ext.
  • Page 478 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [73] [74] m WG [75] mm Hg [80] [120] [121] gal/s [122] gal/min [123] gal/h [124] [125] [126] /min [127] [130] lb/s [131] lb/min [132] lb/h [140] ft/s [141] ft/min...
  • Page 479 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 21-32 Ext. 2 Maximum Reference Default value: 100 ExtPID2Unit Parameter type: Range, par. 21-31 - 999999.999 Ext.PID1Unit Setup: Conversion index: All setups Data type: Int32 Change during operation: True NOTICE Set the value for parameter 21-32 Ext.
  • Page 480 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [30] Ext. closed loop 1 [31] Ext. closed loop 2 [32] Ext. closed loop 3 [37] Analog input X49/1 [38] Analog input X49/3 [39] Analog input X49/5 [133] Fieldbus REF 1 21-34 Ext.
  • Page 481 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [22] Pressure 2 [99] Normal feedback [100] Bus feedback 1 [101] Bus feedback 2 [102] Bus feedback 3 [104] Sensorless flow Requires setup by VLT® Motion Control Tool MCT 10 with sensorless plug-in.
  • Page 482 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Int32 Change during operation: True Readout of the output value for the closed-loop 2 controller. 6.21.6 21-4* Ext. CL 2 PID 21-40 Ext. 2 Normal/Inverse Control Default value: [0] Normal Parameter type: Option...
  • Page 483 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 21-43 Ext. 2 Differentiation Time Default value: Parameter type: Range, 0=Off - 10 s Setup: All setups Conversion index: Data type: Uint16 Change during operation: True The differentiator does not react to a constant error. It only provides a gain when the feedback changes. The quicker the feedback changes, the stronger the gain from the differentiator.
  • Page 484 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [21] l/min [22] [23] [24] /min [25] [30] kg/s [31] kg/min [32] kg/h [33] t/min [34] [40] [41] m/min [45] [60] °C [70] mbar [71] [72] [73] [74] m WG [75]...
  • Page 485 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [140] ft/s [141] ft/min [145] [160] °F [170] [171] lb/in [172] in WG [173] ft WG [174] in HG [180] 21-51 Ext. 3 Minimum Reference Default value: 0 ExtPID3Unit Parameter type: Range, -999999.999 - par.
  • Page 486 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions NOTICE If feedback is not used, set its source to [0] No function. Parameter 20-20 Feedback Function determines how the PID controller uses the 3 possible feedback. This parameter defines which input on the drive should be treated as the source of the reference signal for the closed-loop 3 controller. Analog input X30/11 and analog input X30/12 refer to inputs on the VLT®...
  • Page 487 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* No function Analog input 53 Analog input 54 Pulse input 29 Pulse input 33 Analog input X30/11 Analog input X30/12 Analog input X42/1 [10] Analog input X42/3 [11] Analog input X42/5 [15]...
  • Page 488 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions The setpoint reference is used in extended 1 closed loop. Ext. 1 setpoint is added to the value from the Ext. 3 reference source selected in parameter 21-53 Ext. 3 Reference Source. 21-57 Ext.
  • Page 489 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions The proportional gain indicates the number of times the error between the setpoint and the feedback signal is to be applied. If (error x gain) jumps with a value equal to what is set in parameter 20-14 Maximum Reference/Feedb., the PID controller tries to change the output speed equal to what is set in parameter 4-13 Motor Speed High Limit [RPM]/parameter 4-14 Motor Speed High Limit [Hz].
  • Page 490 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Parameter Group 22-** Appl. Functions 6.22 22-0* Miscellaneous 6.22.1 22-00 External Interlock Delay Default value: Parameter type: Range, 0 - 600 s Setup: Conversion index: All setups Data type: Uint16 Change during operation: True Set the delay time for the external interlock command.
  • Page 491 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [18] Analog input X49/5 [19] Pressure 3 [20] Pressure 4 22-11 Air Pressure to Flow Fan k-factor Default value: 1000 Parameter type: Range, 1 - 10000 Setup: Conversion index: All setups Data type:...
  • Page 492 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0*] None A reference/feedback unit is used instead of a signal unit. [70] mbar [71] [72] [73] [74] m WG [75] mm Hg [170] [171] lb/in [172] in WG [173] ft WG...
  • Page 493 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Sleep mode No-flow detection This function is used for detecting a no-flow situation in pump systems where all valves can be closed. The function can be used with both the integrated PI controller and with an external PI controller. Program the configuration in parameter 1-00 Configuration Mode. Configuration mode for integrated PI controller: closed loop external PI controller: open loop...
  • Page 494 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Head Flow Figure 84: No-flow Detection Curve No-flow detection is based on the measurement of speed and power. For a certain speed, the drive calculates power at no flow. This coherence is based on the adjustment of 2 sets of speed and associated power at no flow.
  • Page 495 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions There are 2 conditions that trigger a dry-pump signal: Power consumption below no-flow level. Pump running at maximum speed or maximum reference open loop, whichever is lowest. The signal must be active for a set time (parameter 22-27 Dry Pump Delay) before the selected action takes place. The following actions are available (parameter 22-26 Dry Pump Function): Warning Alarm...
  • Page 496 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 22-21 Low Power Detection Default value: [0] Disabled Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Use this parameter for enabling/disabling no-flow detection based on measured motor power. Option Name Description...
  • Page 497 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0*] NOTICE Do not set parameter 14-20 Reset Mode to [13] Infinite auto reset when parameter 22-23 No-flow Function is set to [3] Alarm . Doing so causes the drive to continuously cycle between running and stopping when a no-flow condition is detected.
  • Page 498 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions NOTICE Do not set parameter 14-20 Reset Mode to [13] Infinite auto reset when parameter 22-26 Dry Pump Function is set to [2] Trip. Doing so causes the drive to continuously cycle between running and stopping when a dry-pump condition is detected. NOTICE For drives with constant-speed bypass: If an automatic bypass function starts the bypass at persistent alarm conditions, disable the automatic bypass function, if [2] Trip or [3] Manuel reset trip is selected as the dry-pump function.
  • Page 499 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 22-3* No-flow Power Tuning 6.22.4 NOTICE Set parameter 1-03 Torque Characteristics before tuning takes place. If auto setup is disabled in parameter 22-20 Low Power Auto Set-up, the tuning sequence is as follows: Close the main valve to stop flow.
  • Page 500 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Make corrections to the calculated power in parameter 22-30 No-flow Power. If no-flow is detected when it should not be, decrease the setting.
  • Page 501: Sleep Mode

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Use this parameter if parameter 0-02 Motor Speed Unit is set to [0] RPM (parameter is not visible if [1] Hz is selected). Set used speed at the 85% level. This function is used for storing values necessary for tuning no-flow detection. 22-37 High Speed [Hz] Default value: Size related...
  • Page 502 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions See also signal flow chart in parameter group 22-2* No-flow Detection. There are the following ways of using the sleep mode function. Figure 85: Sleep-mode Function Systems where the integrated PI controller is used for controlling pressure or temperature, for example, boost systems with a pressure feedback signal applied to the drive from a pressure transducer.
  • Page 503 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions If no-flow is detected, the drive increases the setpoint for pressure to ensure a slight overpressure in the system (boost set in parameter 22-45 Setpoint Boost). The feedback from the pressure transducer is monitored, and then this pressure has dropped with a set percentage below the normal setpoint for pressure (P ).
  • Page 504 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions When low power or low speed is detected, the motor is stopped, but the reference signal (f ) from the external controller is still monitored. Because of the the low pressure created, the controller increases the reference signal to gain pressure. When the reference signal has reached a set value, f , the motor restarts.
  • Page 505 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions To be used if parameter 0-02 Motor Speed Unit has been set to [0] RPM (parameter not visible if [1] Hz is selected). Only to be used if parameter 1-00 Configuration Mode is set to [0] Open loop and an external controller applies speed reference. Set the reference speed at which the sleep mode should be canceled.
  • Page 506: End Of Curve

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 22-5* End of Curve 6.22.6 The end-of-curve conditions occur when a pump is yielding a too large volume to ensure the set pressure. This situation can occur if a leakage occurs in the distribution pipe system after the pump. Such a leakage causes the pump to operate at the end of the pump characteristic valid for the maximum speed set in parameter 4-13 Motor Speed High Limit [RPM] or parameter 4-14 Motor Speed High Limit [Hz].
  • Page 507: Broken Belt Detection

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 22-51 End of Curve Delay Default value: 10 s Parameter type: Range, 0 - 600 s Setup: All setups Conversion index: Data type: Uint16 Change during operation: True When an end-of-curve condition is detected, a timer is activated. When the time set in this parameter expires, and the end-of-curve condition is steady during the entire period, the function set in parameter 22-50 End of Curve Function is activated.
  • Page 508: Short Cycle Protection

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 22-61 Broken Belt Torque Default value: Parameter type: Range, 0 - 100% Setup: All setups Conversion index: Data type: Uint8 Change during operation: True Set the broken-belt torque as a percentage of the rated motor torque. 22-62 Broken Belt Delay Default value: 10 s...
  • Page 509 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint16 Change during operation: True Sets the minimum time between 2 starts. Any normal start command (start/jog/freeze) is disregarded until the timer has expired. 22-77 Minimum Run Time Default value: Parameter type: Range, 0 - par.
  • Page 510 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions (required pressure) is the setpoint for closed-loop (PI) operation of the drive and is set for closed-loop operation without flow DESIGN compensation. It is recommended to use slip compensation and RPM unit. Figure 89: Flow Compensation NOTICE When flow compensation is used with the cascade controller (parameter group 25-** Cascade Pack Controller), the actual setpoint...
  • Page 511 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 50: Setpoint Defined by Number of Pumps (continued) Parameter used Speed at design point Speed at design point Cascade controller KNOWN UNKNOWN – Parameter 22-83 Speed at No Flow [RPM]/parameter 22-84 Speed at No Flow [Hz] –...
  • Page 512 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions (head) Control curve (flow) Figure 91: Square-Linear Curve Approximation 22-82 Work Point Calculation Default value: [0] Disabled Parameter type: Option Setup: Conversion index: All setups – Data type: Uint8 Change during operation: True H (head) H DESIGN...
  • Page 513 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions RATED Par. 22-88 setpoint DESIGN Control curve DESIGN RATED Figure 93: Example 2: Speed at Unknown System Design Working Point Speed at system design working point is not known: Where the speed at system design working point is unknown, another reference point on the control curve has to be determined based on the datasheet.
  • Page 514 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Resolution 0.033 Hz. Enter the motor speed in Hz at which flow has effectively stopped and minimum pressure, H , is achieved Alternatively, enter the speed in RPM in parameter 22-83 Speed at No-Flow [RPM].
  • Page 515 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Int32 Change during operation: True Enter the value corresponding to the flow at design point. No units are required. 22-90 Flow at Rated Speed Default value: Size related Parameter type:...
  • Page 516 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: 2 setups Conversion index: Data type: TimeOfDayWoDate Change during operation: True Sets the ON time for the desired action. NOTICE The drive has no back-up of the clock function. The set date/time resets to default (2000-01-01 00:00) after a power-down unless a real-time clockmodule with back-up is installed.
  • Page 517 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [22] [23] Run reverse [24] Stop [26] Dcstop [27] Coast [28] Freeze output [29] Start timer 0 [30] Start timer 1 [31] Start timer 2 [32] Set digital out A low [33] Set digital out B low [34]...
  • Page 518 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [76] Start timer 9 [80] Sleep mode [90] Set ECB bypass mode [91] Set ECB drive mode [100] Reset alarms 23-02 OFF Time Default value: Size related Parameter type: Range, 0 - 0, Array [10] Setup:...
  • Page 519 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [16] Select preset ref 6 [17] Select preset ref 7 [18] Select ramp 1 [19] Select ramp 2 [22] [23] Run reverse [24] Stop [26] DC brake [27] Coast [28]...
  • Page 520 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [72] Start timer 5 [73] Start timer 6 [74] Start timer 7 [75] Start timer 8 [76] Start timer 9 [80] Sleep mode [90] Set ECB bypass mode [91] Set ECB drive mode [100]...
  • Page 521 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [14] Day 5 of month [15] Day 6 of month [16] Day 7 of month [17] Day 8 of month [18] Day 9 of month [19] Day 10 of month [20] Day 11 of month [21]...
  • Page 522 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* Timed actions auto Enable timed actions. Timed actions disabled Disable timed actions, normal operation according to control commands. Constant on actions Disable timed actions. Constant on actions are activated. Constant off actions Disable timed actions.
  • Page 523: Maintenance

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 23-1* Maintenance 6.23.2 Wear and tear calls for periodic inspection and service of elements in the application, for example motor bearings, feedback sensors, seals, and filters. With preventive maintenance, the service intervals may be programmed into the drive. The drive gives a message when maintenance is required.
  • Page 524 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 23-10 Maintenance Item Default value: [1] Motor Bearings Parameter type: Option, Array [20] Setup: 1 setup Conversion index: – Data type: Uint8 Change during operation: True Array with 20 elements shown below the parameter number in the display. Press [OK] and step between elements with [◄], [►], [▲], and [▼].
  • Page 525 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [1]* Lubricate Clean Replace Inspect/check Overhaul Renew Check [20] Maintenance text 0 [21] Maintenance text 1 [22] Maintenance text 2 [23] Maintenance text 3 [24] Maintenance text 4 [25] Maintenance text 5 [28]...
  • Page 526 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: 1 setup Conversion index: Data type: Uint32 Change during operation: True Set the interval associated with the current preventive maintenance event. This parameter is only used if [1] Running Hours or [2] Operating Hours is selected in parameter 23-12 Maintenance Base.
  • Page 527: Energy Log

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 6 individual texts (Maintenance Text 0...Maintenance Text 5) can be written for use in either parameter 23-10 Maintenance Item or parameter 23-11 Maintenance Action. The text is written according to the guidelines in parameter 0-37 Display Text 1. 23-5* Energy Log 6.23.3 The drive is continuously accumulating the consumption of the controlled motor, based on the actual power yielded by the drive.
  • Page 528 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions NOTICE The drive has no backup of the clock function. The set date/time resets to default (2000-01-01 00:00) after a power-down unless a real-time clock module with backup is installed. Therefore, the logging is stopped until date/time is readjusted in parameter -70 Date and Time.
  • Page 529 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions NOTICE All counters are automatically reset when changing the setting in parameter 23-50 Energy Log Resolution. At overflow, the update of the counters stops at maximum value. NOTICE When mounting VLT® Analog I/O Option MCB 109, a battery backup of the date and time is included. Array with several elements equal to the number of counters ([00]-[xx] below parameter numbers in display).
  • Page 530 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Two sets of data for trending can be created to make it possible to compare current values for a selected operating variable with data for a certain reference period for the same variable. This reference period can be preprogrammed (parameter 23-63 Timed Period Start and 23-64 Timed Period Stop).
  • Page 531 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Select the required operating variable to be monitored for trending. Option Name Description Power [kW] Power yielded to the motor. Reference for the relative value is the rated motor power programmed in parameter 1-20 Motor Power [kW] or parameter 1-21 Motor Power [hp].
  • Page 532 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint32 Change during operation: True Array with 10 elements ([0]–[9] below parameter number in display). Press [OK] and step between the elements with [▲] and [▼]. 10 counters with the frequency of occurrence for the operating variable monitored, sorted according to the following intervals: Counter [0]: 0–<10% Counter [1]: 10–<20% Counter [2]: 20–<30%...
  • Page 533 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 23-65 Minimum Bin Value Default value: Size related Parameter type: Range, 0 - 100%, Array [10] Setup: 2 setups Conversion index: Data type: Uint8 Change during operation: True Array with 10 elements ([0]–[9] below parameter number in display). Press [OK] and step between the elements with [▲] and [▼]. Set the minimum limit for each interval in parameter 23-61 Continuous Bin Data and parameter 23-62 Timed Bin Data.
  • Page 534 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Rated power for the motor size used (P 1-20/21) Reference power ed speed) (P 23-80) Actual power yielded with variable speed control (read P 16-10/11) Figure 99: Comparison of Reference Power and Actual Power The difference between the reference power at fixed speed and the actual power yielded with speed control represents the actual saving.
  • Page 535 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: 2 setups Conversion index: Data type: Uint32 Change during operation: True Set the actual cost for a kWh in local currency. If the energy cost is changed later on, it impacts the calculation for the entire period. 23-82 Investment Default value: Parameter type:...
  • Page 536: Fire Mode

    The drive itself could be damaged, and/or cause damage or fire. When the drive has been programmed for fire mode, Danfoss accepts no responsibility for errors, malfunctions, personal injury, or any damage to the drive itself or the components herein, HVAC systems and components herein, or other property.
  • Page 537: Messages In The Display

    280, Fire M service need appears to indicate that a service inspection is required to secure a safe operation if a new critical situation occurs. Warning 280, Fire M service need can only be removed by a Danfoss service inspection. From software 6.01 onwards, there is a special setup switch within the Fire Mode parameters, which enables switching the fire mode setup without changing the general setup.
  • Page 538 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Only a Danfoss authorized service partner is allowed to reset the FM alarm log. To secure the FM operation documentation, the 1st critical alarms can never be removed. The following events are logged: Warning 200 - Fire mode active.
  • Page 539 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Enable-run reverse In this mode, the motor continues to operate in a counterclockwise direction. Works only in open loop. Set parameter 24-01 Fire Mode Configuration to [0] Open Loop. Enabled-coast In this mode, the output is disabled, and the motor is allowed to coast to stop.
  • Page 540 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True By default, fire mode is configured for open-loop control where only the motor unit is selected in parameter 0-02 Motor Speed Unit. For closed-loop operation, select any of the following options.
  • Page 541 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [74] m WG [75] mm HG [80] [120] [121] gal/s [122] gal/min [123] gal/h [124] [125] [126] /min [127] [130] lb/s [131] lb/min [132] lb/h [140] ft/s [141] ft/min [145]...
  • Page 542 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 24-04 Fire Mode Max Reference Default value: Size related Parameter type: Range, par. 24-03 - 999999.999 FireModeMinReference Setup: Conversion index: All setups Data type: Int32 Change during operation: True This parameter defines the maximum speed reference which the fire mode can operate to, although the motor limits in parameter 4-10 Motor Speed Direction has the highest priority.
  • Page 543 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [25] Analog input X42/5 [37] Analog input X49/1 [38] Analog input X49/3 [39] Analog input X49/5 [133] Fieldbus REF 1 A reference value can also come via selected fieldbus. 24-07 Fire Mode Feedback Source Default value: [0] No function...
  • Page 544 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [100] Bus feedback 1 Different feedback channels can be selected via fieldbus network. [101] Bus feedback 2 Different feedback channels can be selected via fieldbus network. [102] Bus feedback 3 Different feedback channels can be selected via fieldbus network.
  • Page 545 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 53: Fire Mode Alarm Handling Alarm number Description Fire mode alarm handling selected in parameter 24-09 Fire Mode Warranty-affecting Alarm Handling. Critical alarms cause a trip. alarms in fire mode [0] Trip+reset [1] Trip...
  • Page 546: Drive Bypass

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 24-1* Drive Bypass 6.24.2 The drive includes a feature which can be used to automatically activate an external electro-mechanical bypass if the drive trips or if there is a fire-mode coast (see parameter 24-00 Fire Mode Function). The bypass switches the motor to operation direct on line.
  • Page 547 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions NOTICE After enabling the drive bypass function, the Safe Torque Off function (where included) does not comply with standard EN 954-1, Cat. 3 installations. This parameter determines the circumstances that activate the drive bypass function. Option Name Description...
  • Page 548 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint32 Changes during operation: True This ramp time is used for deceleration while fire mode is active. 24-42 Timeout for Fire Mode Test Default value: 10 min Parameter type:...
  • Page 549 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Standard, active-high Normal high input and output signals operate the fire mode function as long as they are active (high). Inverse, active-low This option adds safety rules to ensure that fire mode still operates if a signal is lost.
  • Page 550 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Enter the quadratic coefficient of the missing motor detection function multiplied by 1000. 24-93 Missing Motor Coefficient 3 Default value: Parameter type: Range, -100 - 100 Setup: All setups Conversion index: Data type Int32 Change during operation:...
  • Page 551 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 24-98 Locked Rotor Coefficient 3 Default value: Parameter type: Range, -100 - 100 Setup: All setups Conversion index: Data type: Int32 Change during operation: True Enter the linear coefficient of the locked-rotor detection function multiplied by 1000. 24-99 Locked Rotor Coefficient 4 Default value: Parameter type:...
  • Page 552: Cascade Controller

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions . of cascade controller ation mode (P 1-00): Open Loop Closed Loop Cascade controller (P 25-00): Disabled Enabled Direct on line Soft Starter Motor start (P 25-02): Pump cycling (P 25-04): Disabled Enabled Fixed lead pump (P 25-05):...
  • Page 553 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* Disabled The cascade controller is not active. All built-in relays assigned to pump motors in the cascade function are de-energized. If a variable-speed pump is connected to the drive directly (not controlled by a built-in relay), this pump/fan is controlled as a single-pump system.
  • Page 554: Bandwidth Settings

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: 2 setups Conversion index: – Data type: Uint8 Change during operation: False Fixed lead pump is a configuration when the variable-speed pump is connected directly to the drive. If a contactor is applied between the drive and the pump, this contactor is not controlled by the drive.
  • Page 555 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Set the staging bandwidth (SBW) percentage to accommodate normal system pressure fluctuation. In cascade control systems, to avoid frequent switching of fixed speed pumps, the desired system pressure is typically kept within a bandwidth rather than at a constant level. The SBW is programmed as a percentage of parameter 20-13 Minimum Reference/ Feedb.
  • Page 556 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Override bandwidth Setpoint Figure 103: Override Bandwidth Setting the OBW too close to the SBW could defeat the purpose with frequent staging at momentary pressure changes. Setting the OBW too high might lead to unacceptably high or low pressure in the system while the SBW timers are running. The value can be optimized with increased familiarity with the system.
  • Page 557 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Immediate staging of a fixed-speed pump is not desirable when a momentary pressure drop in the system exceeds the staging bandwidth (SBW). Staging is delayed by the length of the time programmed. If the pressure increases within the SBW before the timer has elapsed, the timer is reset.
  • Page 558 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions (27-24) SBW destage delay (27-20) Setpoint (27-20) Figure 105: SBW Destaging Delay 25-25 OBW Time Default value: 10 s Parameter type: Range, 0 - 300 s Setup: Conversion index: All setups Data type: Uint16 Change during operation:...
  • Page 559 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 25-26 Destage at No-Flow Default value: [0] Disabled Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True This parameter ensures that when a no-flow situation occurs, the fixed-speed pumps are destaged 1 by 1 until the no-flow signal disappears.
  • Page 560: Staging Settings

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions The destage function ensures that the lowest numbers of pumps are running to save energy and to avoid dead-head water circulation in the variable-speed pump. If the destage function is set to [0] Disabled, parameter 25-30 Destage Function Time is not activated. Option Name Description...
  • Page 561 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint16 Change during operation: True NOTICE Use this option only if [1] Soft starter or [2] Star-Delta is selected in parameter 25-02 Motor Start. When adding a fixed-speed pump controlled by a soft starter or a star-delta starter, it is possible to delay the ramp down of the lead pump until a preset time after the start of the fixed-speed pump.
  • Page 562 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Speed Destaging Lead pump (controlled by drive) Fixed-speed pump (controlled by soft starter) Time P PC-41 Lead pump starts to ramp up Cascade Controller prepares for removing pump Figure 109: Destaging with Ramp-up Delay 25-42 Staging Threshold Default value: Size related...
  • Page 563 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions is the ratio of parameter 4-11 Motor Speed Low Limit [RPM] or parameter 4-12 Motor Speed Low Limit [Hz], to parameter 4-13 Motor Speed High Limit [RPM] or parameter 4-14 Motor Speed High Limit [Hz], expressed in percent. Destaging threshold must range from to 100%, where n is motor speed low limit and n is motor speed high limit.
  • Page 564: Alternation Settings

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Readout of the calculated value for destaging speed. When removing a fixed-speed pump to prevent an overshoot of pressure, the variable-speed pump ramps up to a higher speed. When the variable-speed pump reaches the destaging speed, the fixed-speed pump is destaged.
  • Page 565 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description At command Alternation of the lead-pump function takes place at an external command signal or a preprogrammed event. See parameter 25-51 Alternation Event for available options. At staging or command Alternation of the lead pump takes place at staging or according to [2] At command.
  • Page 566 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: VisStr[7] Change during operation: True Readout parameter for the alternation time interval value set in parameter 25-52 Alternation Time Interval. 25-54 Alternation Predefined Time Default value: Parameter type: Size related Range, 0 - 0 Setup:...
  • Page 567 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions The following illustration is an example of the slow transfer-staging. The variable-speed pump (top graph) and 1 fixed-speed pump (bottom graph) run before the staging command. When the [0] Slow transfer command is activated, an alternation is carried out by ramping the variable-speed pump to parameter 4-13 Motor Speed High Limit [RPM] or parameter 4-14 Motor Speed High Limit [Hz], and then decelerated to zero speed.
  • Page 568 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 25-59 Run on Mains Delay Default value: 0.5 s Parameter type: Range, Par. 25-58 - 5 s Setup: All setups Conversion index: Data type: Uint16 Change during operation: True NOTICE This parameter is only active if the option selected in parameter 25-50 Lead Pump Alternation is different from [0] Off.
  • Page 569 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: VisStr[4] Change during operation: True Readout of the status for each of the relays assigned to control the pumps. Every element in the array shows a relay. If a relay is activated, the corresponding element is set to On.
  • Page 570 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions View the interlock status of the connected compressors. 25-9* Service 6.25.7 The parameters in this parameter group are used if there is a service on 1 or more of the controlled pumps. 25-90 Pump Interlock Default value: [0] Off...
  • Page 571 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Power card Control card Analog I/O card 10 11 12 12 13 18 19 27 29 32 33 20 37 39 42 50 53 54 55 01 02 03 04 05 06 Humidifier steps or cooling steps Figure 113: Overview of Terminals, VLT®...
  • Page 572 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 54: Relevant Parameters (continued) Terminal Parameters Terminal Parameters Terminal Parameters X42/5 – – – – Parameter 26-02 Terminal X42/5 Mode. parameter group 26-3* Analog Input X42/5 Analog outputs Analog outputs X42/7 Parameter group Parameter group...
  • Page 573 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setting of on-board real-time clock The analog I/O option incorporates a real-time clock with battery backup. This can be used as backup of the clock function included in the drive as standard. See parameter group 0-7* Clock Settings. The analog I/O option can be used for the control of devices such as actuators or valves, using the extended closed-loop facility, thus removing control from the building management system.
  • Page 574 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Terminal X42/3 can be programmed as an analog input accepting a voltage or input from either Pt 1000 (1000 Ω at 0 °C (32 °F)) or Ni 1000 (1000 Ω at 0 °C (32 °F)) temperature sensors. Select the mode. [2] Pt 1000 [°C] and [4] Ni 1000 [°C] if operating in Celsius, or [3] Pt 1000 [°F] and [5] Ni 1000 [°F] if operating in Fahrenheit.
  • Page 575 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Ni 1000 [°C] Ni 1000 [°F] 6.26.3 26-1* Analog Input X42/1 This parameter group contains parameters for configuring the scaling and limits for analog input terminal X42/1. 26-10 Terminal X42/1 Low Voltage Default value: Parameter type:...
  • Page 576 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint16 Change during operation: True NOTICE This parameter cannot be adjusted while the motor is running. This is a first-order digital low-pass filter time constant for suppressing noise in terminal X42/1. A high value of time constant improves dampening, but also increases the time delay through the filter.
  • Page 577 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Int32 Change during operation: True Enter the analog input scaling value that corresponds to the low-voltage value set in parameter 26-20 Terminal X42/3 Low Voltage. 26-25 Term.
  • Page 578 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Int16 Change during operation: True Enter the low-voltage value. This analog input scaling value should correspond to the low reference/feedback value set in parameter 26-34 Term.
  • Page 579 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True This parameter makes it possible to enable the live zero monitoring, for example, where the analog input is the drive control, rather than being used as a decentral I/O system, such as a building management system.
  • Page 580 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [113] Ext. closed loop 1 0–100%, (0–10 V). [114] Ext. closed loop 2 0–100%, (0–10 V). [115] Ext. closed loop 3 0–100%, (0–10 V). [117] Shaft power [121] Air pres.
  • Page 581 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: 1 setup Conversion index: Data type: Uint16 Change during operation: True Holds the preset level of terminal X42/7. If a fieldbus and a timeout function are selected in parameter 26-50 Terminal X42/9 Output, the output presets to this level.
  • Page 582 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [141] Bus ctrl t.o. 0–100%, (0–10 V). [186] Pressure sensor 4 26-51 Terminal X42/9 Min. Scale Default value: Parameter type: Range, 0 - 200% Setup: All setups Conversion index: Data type: Change during operation:...
  • Page 583 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 26-60 Terminal X42/11 Output Default value: [0] No operation Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Set the function of terminal X42/11 as an analog current output. Option Name Description...
  • Page 584 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Int16 Change during operation: True Scale the minimum output of the selected analog signal at terminal X42/11 as a percentage of the maximum signal level. For example, if 0 V (or 0 Hz) is required at 25% of the maximum output value, program 25%. Scaling values up to 100% can never be higher than the corresponding setting in parameter 26-62 Terminal X42/11 Max.
  • Page 585 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 30-21 High Starting Torque Current [%] Default value: Size related Parameter type: Range, 0 - 200.0% Setup: All setups Conversion index: Data type: Uint32 Change during operation: True Set the high starting current that should be applied for the time specified in parameter 30-20 High Starting Torque Time. The increased current will improve the starting torque and starting performance in demanding applications.
  • Page 586: Unit Configuration

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 30-5* Unit Configuration 6.27.2 This parameter group contains parameters for configuring the operation of internal units that communicate with the drive. The settings affect the behavior of hardware components inside the drive. 30-50 Heat Sink Fan Mode Default value: –...
  • Page 587 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 30-91 Channel Default value: Parameter type: Range, 1 - 11 Setup: 1 setup Conversion index: Data type: Uint8 Change during operation: True Enter the wireless channel number. The default channel number is 5. Change the channel number, if there is an interference from other wireless networks.
  • Page 588 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: 1 setup Conversion index: Data type: Uint16 Change during operation: True Enter the TCP port to connect to. 30-97 Wifi Timeout Action Default value: [0] Do nothing Parameter type: Option Setup: Conversion index:...
  • Page 589 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions The drive also includes the SFP performance calculation information to fulfill the EN 16798 requirement. The pressure sensors can be connected to the analog input or to a fieldbus, for example, Modbus RTU master concept. The filter monitoring can cover up to 4 individual filters that could cover different parts of the AHU.
  • Page 590 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 31-21 Below Level Threshold Default value: Size related Parameter type: Range, -8000 - 5000 Pa, Array Setup: Conversion index: All setups Data type: Int16 Change during operation: True This is an array parameter with 4 elements, 1 for each sensor. Enter the lowest threshold level to trigger pressure sensor status notifications.
  • Page 591 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint16 Change during operation: True This is an array parameter with 4 elements, 1 for each sensor. A pressure filter time constant adjusts the dynamic of the reaction to the actual pressure input to ensure reliable and stable status generation.
  • Page 592 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Actual value and value range for sensor 3 is updated at power-up. Shows the readout of pressure sensor 3. 31-29 Pressure Sensor 4 Default value: -8000 Pa Parameter type: Range, -8000 - 8000 Pa Setup: All setups Conversion index:...
  • Page 593 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 31-33 Toggled Readout Text Default value: Size related Parameter type: Range, 0 -12, Array [4] Setup: All setups Conversion index: Data type: VisStr[12] Change during operation: True This is an array parameter with 4 elements, 1 for each sensor. Each of the sensors allows a customized text of up to 11 characters. Customizing of text enables better understanding of the sensor pressure signal.
  • Page 594 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [23] PTU 025 [24] Bus Fdb. Pres. [3136] [25] Bus Fdb. Pres. [3137] [26] Bus Fdb. Pres. [3138] [27] Bus Fdb. Pres. [3139] 31-36 Bus Feedback Pressure 1 Default value: 0 Pa Parameter type:...
  • Page 595: Pressure Warnings

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 31-5* Pressure Warnings 6.28.5 31-50 Above Level Threshold W2 Default value: Size related Parameter type: Range, -8000 - 8000 Pa, Array Setup: All setups Conversion index: Data type: Change during operation: Int16 True This is an array parameter with 4 elements, 1 for each sensor.
  • Page 596 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Int32 Change during operation: True Set the nominal air volume flow at nominal maximum Hz defined in parameter 4-14 Motor Speed High Limit [Hz] to define the actual airflow for the filer air volume monitoring.
  • Page 597 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 31-61 Captured Air Flow Default value: 0 AirPresToFlowUnit Parameter type: Range, 0 - 99999 AirPresToFlowUnit Setup: Conversion index: All setups Data type: Int32 Change during operation: True To set the value of this parameter, either enter it manually or collect it via the drive capture function. 31-62 Nominal Specific Fan Power Default value: 0 Wh...
  • Page 598 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 31-67 Nominal SFP History Default value: Size related Parameter type: Range, 0 - 0 Setup: All setups Conversion index: Data type: TimeOfDay Change during operation: True Shows the date and time of the last nominal capture. It is required to enter the date and time when the nominal SFP trigger is off. 31-68 SFP Threshold W1 Default value: Parameter type:...
  • Page 599 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint32 Change during operation: True Readout showing the accumulated energy cost above the nominal SFP baseline. Reset the counter in parameter 31-74 Reset Function. 31-73 Differential KWh Counter Default value: 0 kWh...
  • Page 600 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 31-76 Replacement Days Default value: Parameter type: Range, -99999 - 99999 Setup: All setups Conversion index: Data type: Int32 Change during operation: True View the calculated number of days before the filter replacement is expected. The calculation is based on the higher average energy cost on a 24-hour basis versus the filter replacement cost.
  • Page 601 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint16 Change during operation: True Shows the value received in PCD1 of the fieldbus telegram. 34-02 PCD 2 Write to MCO Default value: Parameter type: Range, 0 - 65535 Setup: All setups Conversion index:...
  • Page 602 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Shows the value received in PCD7 of the fieldbus telegram. 34-08 PCD 8 Write to MCO Default value: Parameter type: Range, 0 - 65535 Setup: All setups Conversion index: Data type: Uint16 Change during operation: True...
  • Page 603 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint8 Change during operation: True Shows the value sent in PCD2 of the fieldbus telegram. 34-24 PCD 4 Read from MCO Default value: Parameter type: Range, 0 - 65535 Setup: All setups Conversion index:...
  • Page 604 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Shows the value sent in PCD9 of the fieldbus telegram. 34-30 PCD 10 Read from MCO Default value: Parameter type: Range, 0 - 65535 Setup: All setups Conversion index: Data type: Uint16 Change during operation: True...
  • Page 605 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint8 Change during operation: True Select the unit to be used with temperature input X48/7 settings and readouts. Option Name Description [60]* °C [160] °F 35-03 Term. X48/7 Input Type Default value: Parameter type: [0] Not connected...
  • Page 606 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions View the temperature sensor type detected at input X48/10. Option Name Description [0]* Not connected PT100 2-wire PT1000 2-wire PT100 3-wire PT1000 3-wire 35-06 Temperature Sensor Alarm Function Default value: Parameter type: [5] Stop and trip Option...
  • Page 607 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* Disabled Enabled 35-16 Term. X48/4 Low Temp. Limit Default value: Parameter type: Size related Range, -50 - par. 35-17 Setup: All setups Conversion index: Data type: Int16 Change during operation: True...
  • Page 608 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 35-26 Term. X48/7 Low Temp. Limit Default value: Size related Parameter type: Range, -50 - par. 35-27 Setup: All setups Conversion index: Data type: Int16 Change during operation: True Enter the minimum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/7. 35-27 Term.
  • Page 609 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 35-37 Term. X48/10 High Temp. Limit Default value: Size related Parameter type: Range, par. 35-36 - 204 Setup: All setups Conversion index: Data type: Int16 Change during operation: True Enter the maximum temperature reading that is expected for normal operation of the temperature sensor at terminal X48/10. 35-4* Analog Input X48/2 6.30.5 35-42 Term.
  • Page 610 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 35-46 Term. X48/2 Filter Time Constant Default value: 0.005 s Parameter type: Range, 0.005 - 10 s Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Enter the filter time constant. This is a first-order digital low-pass filter time constant for suppressing electrical noise in terminal X48/2. A high time constant value improves dampening but also increases the time delay through the filter.
  • Page 611 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 36-01 Term. X49/3 Mode Default value: [1] Voltage Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Select the output mode of analog terminal X49/3. Option Name Description...
  • Page 612 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [0]* Voltage 0–10V Voltage 2–10V Current 0–20mA Current 4–20mA Digital 36-04 Term. X49/9 Mode Default value: [0] Voltage 0–10V Parameter type: Option Setup: All setups Conversion index: –...
  • Page 613 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 36-1* Analog Input X49/1 6.31.2 36-10 Terminal X49/1 Low Voltage Default value: 0.07 V Parameter type: Range, 0 - 10 V Setup: All setups Conversion index: Data type: Int32 Change during operation: True Enter the voltage corresponding to the low reference value set in parameter 36-14 Term.
  • Page 614 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Int32 Change during operation: True Enter the reference or feedback value (in RPM, Hz, bar, and so on) corresponding to the voltage or current set in parameter 36-12 Terminal X49/1 High Voltage or parameter X49/1 High Current.
  • Page 615 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 36-22 Terminal X49/3 High Voltage Default value: 10 V Parameter type: Range, 0 - 10 V Setup: All setups Conversion index: Data type: Int16 Change during operation: True Enter the voltage corresponding to the high reference value set in parameter 36-25 Term. X49/3 High Ref./Feedb. Value. 36-23 Terminal X49/3 High Current Default value: 20 mA...
  • Page 616 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 36-27 Term. X49/3 Live Zero Default value: [1] Enabled Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Use this parameter for either disabling or enabling the live zero monitoring function. Option Name Description...
  • Page 617 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 36-34 Terminal X49/5 Low Ref./Feedb. Value Default value: 0 ReferenceFeedbackUnit Parameter type: Range, -999999.999 - 999999.999 ReferenceFeedbackUnit Setup: All setups Conversion index: Data type: Int32 Change during operation: True Enter the reference or feedback value (in RPM, Hz, bar, and so on) corresponding to the voltage or current set in parameter 36-30 Terminal X49/5 Low Voltage or parameter 36-31 Terminal X49/4 Low Current.
  • Page 618 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 36-40 Terminal X49/7 Analogue Output Default value: [0] No operation Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Select the functionality of terminal X49/7. Option Name Description...
  • Page 619 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [121] Air pres- to flow [139] Bus ctrl An output value set from fieldbus process data. The output works independently of internal functions in the drive. [141] Bus ctrl t.o.
  • Page 620 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [15] Out of speed range Output speed/frequency is outside the frequency range set in parameter 4-52 Warning Speed Low and parameter 4-53 Warning Speed High. [16] Below speed, low Output speed is lower than the setting in parameter 4-52 Warning Speed Low.
  • Page 621 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [45] Bus ctrl. Controls digital output/relay via bus. The state of the output is set in parameter 5-90 Digital & Relay Bus Control. The output state is retained in the event of a bus timeout. [46] Bus ctrl, 1 if timeout Controls output via bus.
  • Page 622 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [74] Logic rule 4 See parameter group 13-4* Logic Rules. If logic rule 4 in SLC is true, the output goes high. Otherwise, it is low. [75] Logic rule 5 See parameter group 13-4* Logic Rules.
  • Page 623 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [154] ATEX ETR freq. warning Selectable if parameter 1-90 Motor Thermal Protection is set to [20] ATEX ETR or [21] Advanced ETR. If warning 165, ATEX ETR freq.lim.warning is active, the output is 1.
  • Page 624 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [196] Fire mode The drive operates in fire mode. See parameter group 24-0* Fire Mode. [197] Fire mode was act. The drive has been operating in fire mode. In software version 7.2X, this output is only active 1 min after fire mode is stopped.
  • Page 625 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 36-42 Terminal X49/7 Min Scale Default value: Parameter type: Range, 0 - 200% Setup: All setups Conversion index: Data type: Int16 Change during operation: True Match the minimum output of terminal X49/7 with a required value. The required value is defined as a percentage of the value selected in parameter 36-40 Terminal X49/7 Analogue Output.
  • Page 626 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: 1 setup Conversion index: Data type: Uint16 Change during operation: True The drive sends the value of this parameter to the output terminal when the terminal is controlled by a fieldbus and a timeout is detected.
  • Page 627 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [107] Speed 0-HighLim Taken from parameter 3-03 Maximum Reference. 20 mA equals the value in parameter 3-03 Maximum Reference. [113] Ext. closed loop 1 0–100%, (0–10 V) [114] Ext. closed loop 2 0–100%, (0–10 V) [115] Ext.
  • Page 628 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [12] Out of current range The motor current is outside the range set in parameter 4-18 Current Limit. [13] Below current, low The motor current is lower than set in parameter 4-50 Warning Current Low.
  • Page 629 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [35] External interlock The external interlock function has been activated via 1 of the digital inputs. [40] Out of ref range Active when the actual speed is outside the settings in parameter 4-52 Warning Speed Low to parameter 4-55 Warning Reference High.
  • Page 630 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [71] Logic rule 1 See parameter group 13-4* Logic Rules. If logic rule 1 in SLC is true, the output goes high. Otherwise, it is low. [72] Logic rule 2 See parameter group 13-4* Logic Rules.
  • Page 631 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [152] ATEX ETR freq. alarm Selectable if parameter 1-90 Motor Thermal Protection is set to [20] ATEX ETR or [21] Advanced ETR. If alarm 166, ATEX ETR freq.lim.alarm is active, the output is 1.
  • Page 632 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [193] Sleep mode The drive/system has entered sleep mode. See parameter group 22-4* Sleep Mode. [194] Broken belt A broken-belt condition has been detected. Enable this function in parameter 22-60 Broken Belt Function.
  • Page 633 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [250] Fire mode limits During fire mode operation, 1 of the critical alarms has been activated and suppressed by fire mode. This may lead to reduced drive performance and expected operation lifetime before service is required.
  • Page 634 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 36-54 Terminal X49/9 Bus Ctrl Default value: Parameter type: Range, 0 - 100% Setup: All setups Conversion index: Data type: Change during operation: True This parameter contains the output level of terminal X49/9 if the terminal is controlled by bus. 36-55 Terminal X49/9 Timeout Preset Default value: Parameter type:...
  • Page 635 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [103] Motor cur. 0-Imax The value is taken from parameter 16-37 Inv. Max. Current. The inverter maximum current (160% current) is equal to 20 mA. Example: Inverter normal current (11 kW) is 24 A. 160 %=38.4 A. Motor normal current is 22 A, the readout is 11.46 mA.
  • Page 636 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Standby/no warning The drive is ready for operation. No start or stop command is given (start/disable). There are no warnings. Running The motor is running, and shaft torque is present. Running/no warning Output speed is higher than the speed set in parameter 1-81 Min Speed for Function at Stop [RPM].
  • Page 637 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [27] Torque limit & stop Use for performing a coasted stop in a torque limit condition. If the drive has received a stop signal and is in torque limit, the signal is logic 0.
  • Page 638 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [64] Comparator 4 See parameter group 13-1* Comparators. If comparator 4 in SLC is true, the output goes high. Otherwise, it is low. [65] Comparator 5 See parameter group 13-1* Comparators. If comparator 5 in SLC is true, the output goes high.
  • Page 639 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [83] SL digital output D See parameter 13-52 SL Controller Action. Output D is low on smart logic action [35] Set digital out D low. Output D is high on smart logic action [41] Set digital out D high.
  • Page 640 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [173] 10Wh counter pulse [180] Clock fault The clock function has been reset to default (2000-01-01) because of a power failure. [181] Prev. maintenance One or more of the preventive maintenance events programmed in parameter 23-10 Maintenance Item has passed the time for the specified action in parameter 23-22 Maintenance Action.
  • Page 641 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description [237] Ext. CL 2 on ref [238] Ext. CL 3 on ref [240] RS flipflop 0 See parameter group 13-1* Comparators. [241] RS flipflop 1 See parameter group 13-1* Comparators. [242] RS flipflop 2 See parameter group 13-1* Comparators.
  • Page 642 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Scale the maximum output of terminal X49/11. For example, the scaling is done for the following reasons: To provide an output value lower than the maximum possible value. To provide the full signal range using output values lower than a certain limit. To know more about how this parameter works, see parameter 6-52 Terminal 42 Output Max Scale.
  • Page 643 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint16 Change during operation: True The kinetic back-up controller integral time value enables optimizing the DC-link voltage response. If there is external capacitance on the DC link, increase the value.
  • Page 644 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 40-2* PM Motor Specific 6.32.2 40-26 Individual Currents Default value: [0] Off Parameter type: Option Setup: All setups Conversion index: – Data type: Uint8 Change during operation: True Select whether or not to use individual axis currents for induction calculations. Option Name Description...
  • Page 645 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint16 Change during operation: False View the motor voltage when the logged event occurred. 40-44 Alarm Log: DC Link Voltage Default value: Parameter type: Range, 0 - 10000 V, Array [10] Setup: Conversion index:...
  • Page 646 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Int32 Change during operation: False View the CBM threshold for this alarm. 40-5* Advanced Control Settings 6.32.4 40-50 Flux Sensorless Model Shift Default value: Parameter type: –...
  • Page 647 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions [2] PM, salient IPM ¢ 40-53 Current PID Anti Windup Gain Default value: Size related Paramter type: Range, 0 - 500% Setup: All setups Conversion index: Data type: Int16 Change during operation: True This Flux parameter is active in the drive when the following parameters are set to 1 of the values listed here: Parameter 1-00 Configuration Mode...
  • Page 648: Ipv6 Settings

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 40-6* IPv6 Settings 6.32.5 40-60 IPv6 Address Assignment Default value: [3] Disable Parameter type: Option Setup: 1 setup Conversion index: – Data type: Uint8 Change during operation: True Select the method for assigning the IP address. If selecting [0] Manual, the IP address can be set in parameter 40-61 IPv6 Address. To stop communication via IPv6, select [3] Disable.
  • Page 649 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 40-64 DHCPv6 Server Default value: Size related Parameter type: Range, 3 - 39 Setup: 1 setup Conversion index: Data type: VisStr[39] Change during operation: True This parameter shows the IP address of the detected DHCPv6 server. 40-65 Lease Expires IPv6 Default value: Size related...
  • Page 650: Component Status

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Shows status and configuration information of the current IoT protocol. 40-9* Security 6.32.7 40-90 UUID Default value: Size related Parameter type: Range, 36 - 36 Setup: 1setup Conversion index: Data type: Change during operation: VisStr[36] True...
  • Page 651 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions [9]: Fan power card 1 (optional). [10]: Fan power card 2 (optional). 43-00 Component Temp. Default value: Parameter type: 0 °C Range, -128 - 127 °C, Array [18] Setup: All setups Conversion index: Data type: Int8...
  • Page 652 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Shows the heat sink temperature at the location of the phase U IGBT power module. This measurement is not available in all enclosure sizes. Parameter 16-34 Heatsink Temp. uses the value in this parameter. 43-11 HS Temp.
  • Page 653 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Shows the measured speed of fan C on the power card. Each power card has up to 3 fan connections. Place the fan in the drive according to the Operating Guide. A typical placement for fan C is inside the enclosure (the mixing fan). The value of this parameter is: The actual fan speed when there is a DC fan in the drive.
  • Page 654: Warning Log

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Shows the speed of the power card fan F. 43-3* Warning Log 6.33.4 43-30 Warning Log: Warning Number Default value: Parameter type: Range, 0 - 65535, Array [30]...
  • Page 655 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 43-39 Warning Log: Duration Default value: Parameter type: Range, -1 - 2147483647 s, Array [30] Setup: Conversion index: All setups Data type: Int32 Change during operation: False View for how long the warning was active. 43-40 Warning Log: Ext.
  • Page 656 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 43-45 Warning Log: Control Word Default value: Parameter type: Range, 0 - 65535, Array [30] Setup: All setups Conversion index: Data type: Change during operation: False View the control word sent from the drive when the logged event occurred. 43-46 Warning Log: Status Word Default value: Parameter type:...
  • Page 657 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 45-00 Function Default value: – Parameter type: Option Setup: 2 setups Conversion index: – Data type: Uint8 Change during operation: False Set type of notification level and to enable monitoring of the drive. Option Name Description...
  • Page 658 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 45-03 Stop Time Default value: Size related Parameter type: Range, 0 - 0, Array [6] Setup: All setups Conversion index: Data type: TimeOfDay Change during operation: True This parameter shows at which date and time the monitoring function was stopped. 45-09 Readout Setting Default value: [0] Actual...
  • Page 659 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Set the maximum threshold limit. The drive triggers a notification when threshold limit is exceeded. Table 58: Options Parameter ID Description 45-10.0 Stator Winding 45-10.1 Stator Winding Active 45-10.2 Stator Winding Load 45-10.3 Load Envelope 45-10.4...
  • Page 660 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 60: Parameter Index Parameter ID Description 45-12.0 Stator Winding 45-12.1 Stator Winding Active 45-12.2 Stator Winding Load 45-12.3 Load Envelope 45-12.4 Sensor 1 Vibration 45-12.5 Sensor 2 Vibration 45-13 Actual Monitor Value Default value: Parameter type: Range, 0 - 655.35%, Array [8]...
  • Page 661 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 62: Parameter Index (continued) 45-14.2 Stator Winding Load 45-14.3 Load Envelope 45-14.4 Sensor 1 Vibration 45-14.5 Sensor 2 Vibration 45-15 Warning S2 Low Threshold Default value: Parameter type: Range, 0 - 655.35%, Array [8] Setup: Conversion index: All setups...
  • Page 662 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 64: Parameter Index (continued) 45-16.4 Sensor 1 Vibration 45-16.5 Sensor 2 Vibration 45-2* Baseline Settings 6.34.3 Use the parameters in this group to configure how to capture baseline data. 45-20 Type Default value: [0] Off...
  • Page 663 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description Baseline failed Online inadequate data 45-22 Progress Default value: Parameter type: Range, 0 - 100% Setup: All setups Conversion index: Data type: Change during operation: Uint8 True Shows the progress of baseline computation.
  • Page 664 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Option Name Description 1 min 2 mins 4 mins 10 mins 30 mins [13] 1 hour [16] 2 hours [19] 4 hours [23] 8 hours [27] 1 day [30] 2 days [33] 5 days [36]...
  • Page 665 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 45-27 Max. Speed Default value: Size related Parameter type: Range, 100 - 35700 [RPM] Setup: 2 setups Conversion index: Data type: Uint16 Change during operation: True Use this parameter to set the maximum speed of the drive for condition-based monitoring functions. Setting the minimum and maximum speed defines the speed range for condition-based monitoring functions to perform effectively.
  • Page 666 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 45-31 Warning Mode Default value: [1] Offset Parameter type: Option Setup: 2 setups Conversion index: – Data type: Uint8 Change during operation: True Select a mode to define threshold limit for warnings. Option Name Description...
  • Page 667 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 67: Parameter Index Parameter ID Description 45-32.0 Stator Winding 45-32.1 Load Envelope 45-32.2 Sensor 1 Vibration 45-32.3 Sensor 2 Vibration 45-33 Alarm High Default value: Parameter type: Size related Range, 0 - 100%, Array [6] Setup: 2 setup...
  • Page 668 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 45-35 Warning S1 High Default value: Size related Parameter type: Range, 0 - 100% Setup: 2 setups Conversion index: Data type: Uint16 Change during operation: True Type the threshold value for computing a warning S1 high notification. Based on the type of warning mode selected by the user, a warning S1 high threshold is calculated.
  • Page 669 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 72: Options Parameter ID Description 45-37.0 Stator Winding 45-37.1 Load Envelope 45-37.2 Sensor 1 Vibration 45-37.3 Sensor 2 Vibration 45-38 Alarm Low Default value: Parameter type: Size related Range, 0 - 100% Setup: 2 setups Conversion index:...
  • Page 670 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 45-40 Extend Factor Default value: 1.00f Parameter type: Range, 0.05 - 5.00f, Array [6] Setup: 2 setups Conversion index: Data type: Uint16 Change during operation: True In this parameter, consider the extended factor required for setting the extended threshold generation via parameter 45-45 Threshold Generation 6.34.5 45-4* Threshold Generation...
  • Page 671: Sensor Config

    Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint8 Change during operation: True Clear the threshold limit warning when the threshold is at an acceptable level. Option Name Description [0]* Limits OK Limits Exceeded 45-5* Sensor Config. 6.34.6 Select the analog input for sensor and unit configuration.
  • Page 672 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 45-51 Sensor 1 Unit Default value: [0] None Parameter type: Option, Array [4] Setup: 2 setups Conversion index: – Data type: Uint8 Change during operation: True Use the parameter to set unit of monitoring signals from the sensor. The unit is specified on the vibration sensor. Option Name Description...
  • Page 673 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Use this parameter to activate the resonance region supply imbalance control. Enter the threshold offset value from the baseline data. 45-61 Load Mode Default value: [0] Absolute Parameter type: Option Setup: 2 setups Conversion index:...
  • Page 674 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 45-66 DC-link Ripple Value Default value: Parameter type: Range, 0 - 100% Setup: All setups Conversion index: Data type: Uint16 Change during operation: True View the actual value of the DC-link voltage ripple. 45-9* Actual Readouts 6.35 The parameters in this group are readout parameters showing the actual monitoring values.
  • Page 675 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint16 Change during operation: True This parameter shows the actual sensor 2 monitor value in % at motor output speed. 45-95 Sensor 2 [Unit] Default value: Parameter type: Range, -999999.999 - 999999.999 Setup:...
  • Page 676 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Parameter Group 46-** CBM Adv. Thresholds 6.36 46-0* History 6.36.1 The parameters in this group hold threshold history, such as timestamps of the last modification. 46-00 Last Change Time Default value: Parameter type: Size related Range, 0 - 0, Array [6]...
  • Page 677 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Set the time in seconds to define duration during which the alarm is not triggered. When the value which is monitored exceeds or falls below the alarm threshold for more than the time specified in the parameter, an alarm is triggered. Alarm time is the amount of time in seconds a monitoring state should be over alarm threshold before triggering an alarm.
  • Page 678 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Table 78: Parameter Index (continued) 46-12.2 Sensor 1 Vibration 46-12.3 Sensor 2 Vibration 46-13 Interpolation Type Default value: [0] Linear Parameter type: Option, Array [6] Setup: 2 setups Conversion index: –...
  • Page 679 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Set the threshold value which defines a warning S2 alarm for stator monitoring. When the value of the monitored value exceeds the threshold specified in the parameter for the duration of time specified in warning S2 time, a high warning S2 is triggered. The parameter contains 20 index values to manually configure Stator Winding Monitoring Warning S2 High Threshold for each individual speed point.
  • Page 680 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Set the threshold value which defines a high warning S2 for load envelope monitoring. When the value of the monitored value exceeds the threshold specified in the parameter for the duration of time specified in warning S2 time, a warning S2 high is triggered. The parameter contains 20 index values which can be used to manually configure Load Warning S2 High Threshold for each individual speed point.
  • Page 681 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 46-4* Sensor 1 6.36.6 Use the parameters in this group to enter, adjust, and display threshold values for Sensor 1 monitoring function. 46-40 Alarm High Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index:...
  • Page 682 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 46-5* Sensor 2 6.36.7 Use the parameters in this group to enter, adjust, and display threshold values for Sensor 2 monitoring function. 46-50 Alarm High Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index:...
  • Page 683 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 46-6* Sensor 3 6.36.8 Use the parameters in this group to enter, adjust, and display threshold values for Sensor 3 monitoring function. 46-60 Alarm High Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index:...
  • Page 684 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 46-7* Sensor 4 6.36.9 Use the parameters in this group to enter, adjust and display threshold values for Sensor 4 monitoring function. 46-70 Alarm High Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: Conversion index: All setups...
  • Page 685 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Data type: Uint16 Change during operation: True Parameter Group 47-** CBM Baseline Data 6.37 47-0* History 6.37.1 The parameters in this group holds the baseline history of start and stop timestamps of the active and previous baseline. 47-00 Actual Start Time Default value: Parameter type:...
  • Page 686 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Setup: All setups Conversion index: Change during True operation: This parameter shows the baseline speed points of the actual baseline data captured. 47-05 Previous Speed Default value: 0 RPM Parameter type: Range, 0 - 65535 [RPM], Array [20] Setup:...
  • Page 687 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 47-10 Actual Counter Default value: Parameter type: Range, 0 - 65535, Array [20] Setup: All setups Conversion index: Data type: Uint16 Change during operation: False The parameter shows the active minutes to capture monitoring values for speed points. 47-11 Previous Max Default value: Parameter type:...
  • Page 688 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 47-1* Stator Res. Active 6.37.4 47-16 Actual Max Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index: Data type: Uint16 Change during operation: False This parameter shows the active stator resistance.
  • Page 689 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 47-22 Previous Mean Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index: Data type: Uint16 Change during operation: False This parameter shows the average of stator resistance readings for the previous baseline. 47-23 Previous Min Default value: Parameter type:...
  • Page 690 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions This parameter shows the minimum value of stator resonance load recordings for the active baseline. 47-28 Previous Max Default value: Parameter Type: Range, 0 - 655.35%, Array [20] Setup: All setups Conversion index: Data type: Uint16...
  • Page 691 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions Data type: Uint16 Change during operation: False This parameter shows the active mean and 3 standard deviation of load envelope recordings for active baseline. 47-34 Actual Mean Default value: Parameter type: Range, 0 - 655.35%, Array [20] Setup: All setups...
  • Page 692 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions This parameter shows the mean and 3 standard deviations of load envelope readings for the previous baseline. 47-40 Previous Mean Default value: Parameter type: Range, 0 - 655.35%, Array [20] Setup: All setups Conversion index:...
  • Page 693 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions This parameter shows the average and 3 standard deviations for upper threshold of recordings from vibration sensors for active baseline. 47-46 Actual Mean Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index:...
  • Page 694 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 47-52 Previous Min Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index: Data type: Uint16 Change during operation: False The parameter shows the minimum value of Sensor 1 for the previous baseline. 47-53 Previous Counter Default value: Parameter type:...
  • Page 695 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 47-58 Actual Counter Default value: Parameter type: Range, 0 - 65535, Array [20] Setup: All setups Conversion index: Data type: Uint16 Change during operation: False The parameter shows the active minutes to capture monitoring values for Sensor 2. 47-59 Previous Max Default value: Parameter type:...
  • Page 696 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 47-6* Sensor 3 6.37.9 47-64 Actual Max Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index: Data type: Uint16 Change during operation: False This parameter shows the maximum recordings from vibration sensors for the active baseline. 47-65 Actual Mean + 3 Std.
  • Page 697 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 47-70 Previous Mean + 3 Std. Dev. Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index: Data type: Uint16 Change during operation: False This parameter shows the mean and 3 standard deviations of Sensor 3 readings for the previous baseline. 47-71 Previous Mean Default value: Parameter type:...
  • Page 698 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 47-76 Actual Mean Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index: Data type: Uint16 Change during operation: False Shows the average value of recordings from vibration sensors for active baseline. 47-77 Actual Min Default value: Parameter type:...
  • Page 699 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 47-82 Previous Min Default value: Parameter type: Range, 0 - 100%, Array [20] Setup: All setups Conversion index: Data type: Uint16 Change during operation: False The parameter shows the minimum value of Sensor 4 for the previous baseline. 47-83 Previous Counter Default value: Parameter type:...
  • Page 700 Programming Guide | VLT® HVAC Drive FC 102 Parameter Descriptions 47-9* Version 6.37.12 47-99 Version Default value: Parameter type: Range, 0 - 255 Setup: All setups Conversion index: Data type: Uint8 Change during operation: True View the CBM version number. The readout is only shown in VLT® Motion Control Tool MCT 10. Parameter Group 50-** License 6.38 50-00 License Installed...
  • Page 701: Troubleshooting

    Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Troubleshooting Status Messages Warnings and Alarms 7.1.1 A warning or an alarm is signaled by the relevant indicator light on the front of the drive and indicated by a code on the display. A warning remains active until its cause is no longer present.
  • Page 702 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 80: Alarm/Warning Code List Number Description Warning Alarm/ Alarm/ Parameter Fire mode alarm handling selected Warranty- reference in parameter 24-09 Fire Mode Alarm affecting trip trip lock Handling. Critical alarms cause a trip alarms in fire mode [0] Trip +...
  • Page 703 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 80: Alarm/Warning Code List (continued) Number Description Warning Alarm/ Alarm/ Parameter Fire mode alarm handling selected Warranty- reference in parameter 24-09 Fire Mode Alarm affecting trip trip lock Handling. Critical alarms cause a trip alarms in fire mode [0] Trip +...
  • Page 704 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 80: Alarm/Warning Code List (continued) Number Description Warning Alarm/ Alarm/ Parameter Fire mode alarm handling selected Warranty- reference in parameter 24-09 Fire Mode Alarm affecting trip trip lock Handling. Critical alarms cause a trip alarms in fire mode [0] Trip +...
  • Page 705 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 80: Alarm/Warning Code List (continued) Number Description Warning Alarm/ Alarm/ Parameter Fire mode alarm handling selected Warranty- reference in parameter 24-09 Fire Mode Alarm affecting trip trip lock Handling. Critical alarms cause a trip alarms in fire mode [0] Trip +...
  • Page 706 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 80: Alarm/Warning Code List (continued) Number Description Warning Alarm/ Alarm/ Parameter Fire mode alarm handling selected Warranty- reference in parameter 24-09 Fire Mode Alarm affecting trip trip lock Handling. Critical alarms cause a trip alarms in fire mode [0] Trip +...
  • Page 707 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 80: Alarm/Warning Code List (continued) Number Description Warning Alarm/ Alarm/ Parameter Fire mode alarm handling selected Warranty- reference in parameter 24-09 Fire Mode Alarm affecting trip trip lock Handling. Critical alarms cause a trip alarms in fire mode [0] Trip +...
  • Page 708 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 80: Alarm/Warning Code List (continued) Number Description Warning Alarm/ Alarm/ Parameter Fire mode alarm handling selected Warranty- reference in parameter 24-09 Fire Mode Alarm affecting trip trip lock Handling. Critical alarms cause a trip alarms in fire mode [0] Trip +...
  • Page 709 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 80: Alarm/Warning Code List (continued) Number Description Warning Alarm/ Alarm/ Parameter Fire mode alarm handling selected Warranty- reference in parameter 24-09 Fire Mode Alarm affecting trip trip lock Handling. Critical alarms cause a trip alarms in fire mode [0] Trip +...
  • Page 710 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 80: Alarm/Warning Code List (continued) Number Description Warning Alarm/ Alarm/ Parameter Fire mode alarm handling selected Warranty- reference in parameter 24-09 Fire Mode Alarm affecting trip trip lock Handling. Critical alarms cause a trip alarms in fire mode [0] Trip +...
  • Page 711 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 80: Alarm/Warning Code List (continued) Number Description Warning Alarm/ Alarm/ Parameter Fire mode alarm handling selected Warranty- reference in parameter 24-09 Fire Mode Alarm affecting trip trip lock Handling. Critical alarms cause a trip alarms in fire mode [0] Trip +...
  • Page 712 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 80: Alarm/Warning Code List (continued) Number Description Warning Alarm/ Alarm/ Parameter Fire mode alarm handling selected Warranty- reference in parameter 24-09 Fire Mode Alarm affecting trip trip lock Handling. Critical alarms cause a trip alarms in fire mode [0] Trip +...
  • Page 713 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 80: Alarm/Warning Code List (continued) Number Description Warning Alarm/ Alarm/ Parameter Fire mode alarm handling selected Warranty- reference in parameter 24-09 Fire Mode Alarm affecting trip trip lock Handling. Critical alarms cause a trip alarms in fire mode [0] Trip +...
  • Page 714 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 80: Alarm/Warning Code List (continued) Number Description Warning Alarm/ Alarm/ Parameter Fire mode alarm handling selected Warranty- reference in parameter 24-09 Fire Mode Alarm affecting trip trip lock Handling. Critical alarms cause a trip alarms in fire mode [0] Trip +...
  • Page 715 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 80: Alarm/Warning Code List (continued) Number Description Warning Alarm/ Alarm/ Parameter Fire mode alarm handling selected Warranty- reference in parameter 24-09 Fire Mode Alarm affecting trip trip lock Handling. Critical alarms cause a trip alarms in fire mode [0] Trip +...
  • Page 716 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 80: Alarm/Warning Code List (continued) Number Description Warning Alarm/ Alarm/ Parameter Fire mode alarm handling selected Warranty- reference in parameter 24-09 Fire Mode Alarm affecting trip trip lock Handling. Critical alarms cause a trip alarms in fire mode [0] Trip +...
  • Page 717 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 80: Alarm/Warning Code List (continued) Number Description Warning Alarm/ Alarm/ Parameter Fire mode alarm handling selected Warranty- reference in parameter 24-09 Fire Mode Alarm affecting trip trip lock Handling. Critical alarms cause a trip alarms in fire mode [0] Trip +...
  • Page 718 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 80: Alarm/Warning Code List (continued) Number Description Warning Alarm/ Alarm/ Parameter Fire mode alarm handling selected Warranty- reference in parameter 24-09 Fire Mode Alarm affecting trip trip lock Handling. Critical alarms cause a trip alarms in fire mode [0] Trip +...
  • Page 719: Indicator Light

    Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting A trip is the action following an alarm. The trip coasts the motor and is reset by pressing [Reset] or by a digital input (parameter group 5-1* Digital Inputs). The original event that caused an alarm cannot damage the drive or cause dangerous conditions. A trip lock is an action when an alarm occurs, which could damage the drive or connected parts.
  • Page 720 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 82: Description of Alarm Word (continued) Alarm word Alarm word 2 Alarm word 3 Parameter 16-90 Parameter 16-91 Parameter 16-97 Alarm Word Alarm Word 2 Alarm Word 3 00002000 8192 Inrush fault (A33) Illegal option –...
  • Page 721 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 83: Description of Warning Word Warning word Warning word 2 Warning word 3 Parameter 16-92 Parameter 16-93 Parameter 16-98 Warning Word Warning Word 2 Warning Word 3 00000001 Brake check (W28) Start delayed Temp.
  • Page 722 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 83: Description of Warning Word (continued) Warning word Warning word 2 Warning word 3 Parameter 16-92 Parameter 16-93 Parameter 16-98 Warning Word Warning Word 2 Warning Word 3 00100000 1048576 Brake IGBT (W27) Hoist mechanical Sensor 4 S2...
  • Page 723 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 84: Description of Extended Status Word (continued) Ext. status word Ext. status word 2 Ext. status word 3 Parameter 16-94 Parameter 16-95 Parameter 16-99 Ext. Status Word Ext. Status Word 2 Ext.
  • Page 724 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 84: Description of Extended Status Word (continued) Ext. status word Ext. status word 2 Ext. status word 3 Parameter 16-94 Parameter 16-95 Parameter 16-99 Ext. Status Word Ext. Status Word 2 Ext.
  • Page 725: Warning 1, 10 Volts Low

    Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Table 84: Description of Extended Status Word (continued) Ext. status word Ext. status word 2 Ext. status word 3 Parameter 16-94 Parameter 16-95 Parameter 16-99 Ext. Status Word Ext. Status Word 2 Ext.
  • Page 726 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Check that the drive programming and switch settings match the analog signal type. Perform the input terminal signal test. WARNING/ALARM 3, No Motor Cause No motor is connected to the output of the drive. Troubleshooting Check the cable connection between the drive and the motor.
  • Page 727: Warning/Alarm 9, Inverter Overload

    Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting WARNING/ALARM 9, Inverter Overload Cause The drive is about to cut out because of an overload (too high current for too long). The counter for electronic, thermal inverter protection issues a warning at 90% and trips at 100%, while giving an alarm. The drive cannot be reset until the counter is below 90%. The fault occurs when the drive has run with more than 100% overload for too long.
  • Page 728: Warning/Alarm 13, Overcurrent

    Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Troubleshooting If the motor torque limit is exceeded during ramp-up, extend the ramp-up time. If the generator torque limit is exceeded during ramp-down, extend the ramp-down time. If torque limit occurs while running, increase the torque limit. Make sure that the system can operate safely at a higher torque. Check the application for excessive current draw on the motor.
  • Page 729: Warning/Alarm 17, Control Word Timeout

    Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Parameter 15-61 Option SW Version (for each option slot). ALARM 16, Short Circuit Cause There is short-circuiting in the motor or motor wiring. Troubleshooting NOTICE HAZARDOUS VOLTAGE AC drives contain hazardous voltage when connected to the AC mains or connected on the DC terminals. Failure to perform installation, start-up, and maintenance by qualified personnel can result in death or serious injury.
  • Page 730: Warning/Alarm 21, Parameter Error

    Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Parameter 18-39 Temp. Input X48/10 Warning/Alarm 21, Parameter Error Cause The parameter is out of range. The parameter number is shown in the display. Troubleshooting Set the affected parameter to a valid value. Warning/Alarm 22, Hoist Mechanical Brake Cause The value of this warning/alarm shows the type of warning/alarm.
  • Page 731 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Troubleshooting Remove the power to the drive and replace the brake resistor (refer to parameter 2-15 Brake Check. WARNING/ALARM 26, Brake Resistor Power Limit Cause The power transmitted to the brake resistor is calculated as an average value over the last 120 s of run time. The calculation is based on the DC-link voltage and the brake resistor value set in parameter 2-16 Brake Max.
  • Page 732 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting ALARM 30, Motor Phase U Missing Cause NOTICE HAZARDOUS VOLTAGE AC drives contain hazardous voltage when connected to the AC mains or connected on the DC terminals. Failure to perform installation, start-up, and maintenance by qualified personnel can result in death or serious injury.
  • Page 733 Table 85: Internal Fault List Fault number Cause Solution The serial port cannot be initialized. Contact the Danfoss supplier or Danfoss service department. 256–258 The power EEPROM data is defective or too old. Replace the power card. 512–519 Internal fault.
  • Page 734 The software version of the option or the fieldbus variant is not ported/allowed. compatible with the drive software. 1379–2819 Internal fault. Contact the Danfoss supplier or Danfoss service department. 1792 Hardware reset of digital signal processor. 1793 Motor-derived parameters not transferred cor- rectly to the digital signal processor.
  • Page 735 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting ALARM 39, Heat Sink Sensor Cause There is no feedback from the heat sink temperature sensor. The signal from the IGBT thermal sensor is not available on the power card. Troubleshooting Check the ribbon cable between the power card and the gate drive card.
  • Page 736 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting ALARM 46, Power Card Supply Cause The supply on the power card is out of range. Another reason can be a defective heat sink fan. There are 3 supplies generated by the switch mode supply (SMPS) on the power card: 24 V.
  • Page 737 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Troubleshooting Contact a supplier or the service department. ALARM 51, AMA check U and I Cause The settings for motor voltage, motor current, and motor power are wrong. Troubleshooting Check the settings in parameter 1-20 to parameter 1-25. ALARM 52, AMA Low I Cause The motor current is too low.
  • Page 738: Alarm 60, External Interlock

    Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting ALARM 57, AMA Timeout Cause AMA timeout. Troubleshooting Try to restart the AMA. Repeated restarts can overheat the motor. ALARM 58, AMA Internal Fault Cause An AMA internal fault occurs. Troubleshooting Contact a local supplier.
  • Page 739: Alarm 67, Option Module Configuration Has Changed

    Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Troubleshooting for Flux Mode Check the application for possible causes. The load torque could be too significant to drag the motor run to a high speed. Increase the output frequency limit. Ensure that the system can operate safely at a higher output frequency. Cause for VVC TCL Mode The output speed limit is reached, and the torque reference is derated.
  • Page 740: Alarm 70, Illegal Fc Configuration

    Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Troubleshooting Check that the configuration change is intentional and reset the unit. ALARM 68, Safe Stop Activated Cause The Safe Torque Off (STO) has been activated. Troubleshooting To resume normal operation, apply 24 V DC to terminal 37, then send a reset signal via bus, digital I/O, or by pressing [Reset]. ALARM 69, Power Card Temperature Cause The internal temperature has exceeded the allowed operating limits.
  • Page 741: Alarm 79, Illegal Power Section Configuration

    Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting WARNING 73, Safe Stop Auto Restart Cause STO is activated. Troubleshooting With automatic restart enabled, the motor can start when the fault is cleared. WARNING 76, Power Unit Setup Cause The required number of power units does not match the detected number of active power units. Troubleshooting When replacing a drive module, this warning can occur if the power-specific data in the module power card does not match the rest of the drive.
  • Page 742 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting WARNING/ALARM 90, Feedback Monitor Cause A feedback fault is detected by option B. ALARM 91, Analog Input 54 Wrong Settings Troubleshooting Set switch S202 in position OFF (voltage input) when a KTY sensor is connected to analog input terminal 54. WARNING/ALARM 92, No Flow Cause A no-flow condition has been detected in the system.
  • Page 743 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Reset the drive when the fault is cleared. WARNING 97, Stop Delayed Cause Stopping the motor has been delayed due to short-cycle protection. Parameter 22-76 Interval between Starts is enabled. Troubleshooting Troubleshoot the system.
  • Page 744 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Bit 4: Vdd high Bit 5: Vdd low ALARM 145, External SCR Disable Cause The alarm indicates a series DC-link capacitor voltage imbalance. WARNING/ALARM 146, Mains Voltage Cause Mains voltage is outside valid operating range. Troubleshooting See the following report values for details.
  • Page 745 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting WARNING 165, ATEX ETR Freq.Lim.Warning Cause The drive has run for more than 50 s below the allowed minimum frequency as set in parameter 1-98 ATEX ETR Interpol. Points.Freq.). ALARM 166, ATEX ETR Freq.Lim.Alarm Cause The drive has run for more than 60 s in a period of 600 s below the allowed minimum frequency as set in parameter 1-98 ATEX ETR Interpol.
  • Page 746 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Troubleshooting Inspect that the motor operates properly. WARNING 220, Configuration File Version not Supported Cause The drive does not support the current configuration file version. Customization is aborted. ALARM 243, Brake IGBT Cause This alarm is only for multi-drive systems.
  • Page 747 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting 3 = Third drive module from the left (in 4-module systems). 4 = Fourth drive module from the left (in 4-module systems). Troubleshooting Check the power card. Check the gate drive card. Check the ribbon cable between the power card and the gate drive card.
  • Page 748 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting WARNING 250, New Spare Part Cause A component in the drive system has been replaced. Troubleshooting Enter the serial number and type code for canceling the trip lock status after a power cycle. WARNING 251, New Typecode Cause The power card or other components have been replaced, and the type code has changed.
  • Page 749 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting ALARM 426, FPC Config Cause The number of found fan power cards does not match the number of configured fan power cards. See parameter group 15-6* Option Ident for the number of configured fan power cards. Troubleshooting Check fan power card wiring.
  • Page 750 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Warning 506, Load Envelope Low Warning 2 The application load has reached condition orange low limit. Troubleshooting Investigate the root cause for the decrease in motor load and then check the load specified for the application ALARM 510, Motor Stator Winding Alarm Cause Stator winding has reached condition red.
  • Page 751 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Warning 512, Sensor 1 Monitoring Warning 1 Cause An increase in the Sensor 1 value is detected. The value levels in Sensor 1 have reached condition yellow. Troubleshooting Investigate the root cause for the increased values. Alarm 513, Sensor 2 Monitoring Warning 1 Cause There is an excessive amount of motor vibration on sensor 2.
  • Page 752 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Warning 515, Sensor 4 Monitoring Warning 1 Cause An increase in the Sensor 4 value is detected. The value levels in Sensor 4 have reached condition yellow. Troubleshooting Investigate the root cause for the increased values. Alarm 516, Load Envelope Low Alarm The application load has reached low-level condition red.
  • Page 753 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Warning 523, Sensor 2 Thld At Max/Min Cause The sensor 2 threshold in the condition-based monitoring is at its minimum or maximum value of the Sensor 2 function. Troubleshooting Check the threshold values at maximum or minimum in parameter group 46-** CBM Adv Thresholds to parameter group 46-5* Sensor 2 and adjust the values if needed.
  • Page 754 Programming Guide | VLT® HVAC Drive FC 102 Troubleshooting Warning 551, Sensor 2 Low Monitoring Warning 1 The value measured on Sensor 2 is very low and has reached condition yellow low. Troubleshooting Investigate the root cause for the value reaching the red low level. For example, lost connection to analog inputs or no proper data communication on fieldbus sensors.
  • Page 755  ...
  • Page 756 Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product. All trademarks in this material are property of Danfoss A/S or Danfoss group companies.

Table of Contents