K&R GT600-4T132G User Manual page 70

Ac drive high performance open and closed loop
Table of Contents

Advertisement

3. Electrical Installation
3
- 68 -
Wiring of DO
When digital output terminal must drive relay, it is necessary to install an absorption diode
across relay coil. This diode prevents inductive switching transients causing damage to
the DC 24V power supply. The absorption diode must have a forward current rating of 50
mA.
Figure 3-25 Wiring of digital output terminal
GT600
Be careful to install absorption diode with correct polarity, to prevent
CAUTION
damage to the 24 VDC power supply.
CME and COM are internally insulated, but are shorted externally by
a jumper. In this case, DO1 is driven by+24 V by default. Remove the
jumper if you need to drive DO1 by an external power supply.
Wiring of High-speed Output FM
When the FM terminal is used for continuous pulse output, maximum output frequency is
100 kHz.
Figure 3-26 Wiring of high-speed output terminal FM
+24V
DO
CME
COM
GT600
VCC
FM
COM
0V
External controller
Relay
Diode