6. Description of Parameters
Figure 6-53 User programmable function (2)
Set the
programmable card
to activate.
A7-00 = 1
Figure 6-54 The user programmable use schematic (3)
6
Set the
programmable card
to activate.
A7-00 = 1
- 178 -
FMR
(FM used as digital
output)
Relay1
(T/A-T/B-T/C)
Set the
drive
DO1
outputs.
FMP
(FM used as pulse
output)
AO1
The running command is
Command
given by the communication.
Set F0-02 = 2.
The frequency reference is set
Frequency
via communication.
reference
For details, see section 6.2.
The frequency reference is set
Torque
via communication.
reference
For details, see F2-09 and A0-01
PLC program modified
The value of A7-09 is
determined by the user
Fault
programmable card.
Control mode
(units position
AC drive control
of A7-01)
(See details in
group F5)
0
PLC program
control
1
Control mode
(tens position
AC drive control
of A7-01)
(See details in
group F5)
0
PLC program
1
control
Control mode
(hundreds
AC drive control
position
(See details in
of A7-01)
group F5)
0
PLC program
control
1
Control mode
(thousands
position
AC drive control
(See details in
of A7-01)
group F5)
0
PLC program
1
control
Control mode
(ten thousands
AC drive control
position
(See details in
of A7-01)
group F5)
0
PLC program
1
control
PLC program modified
The value of A7-08 is
determined by the user
programmable card.
PLC program modified
The value of A7-06 is
determined by the user
programmable card.
PLC program modified
The value of A7-07 is
determined by the user
.
programmable card.
0: No fault
80 to 89: User-defined
fault code
PLC program modified
PLC controls
0: output invalid
digital output
(units position
1: output valid
of A7-05)
PLC controls
0: output invalid
digital output
(tens position of A7-05)
1: output valid
PLC controls
0: output invalid
digital output.
(units position
1: output valid
of A7-05)
0.0% to 100.0%
PLC controls
Base value of percentage is
FMP output.
FMP output max. frequency
(A7-03)
(F5-09).
PLC controls
0.0% to 100.0%
AO1 output
Base value of percentage
(A7-04)
is 10 V or 20 mA.
0: No command
1: Forward run
2: Reverse run
3: Forward jog
4: Reverse jog
5: Coast to stop
6: Decelerate to stop
7: Fault reset
-100.0% to 100.0%
The base value of the percentage
is F0-10 (Max. frequency).
-200.0% to 200.0%
The base value of the percentage
is rated motor torque.