6. Description of Parameters
6.10.4 Write Frequency/Torque Reference
You can set frequency reference, torque limit, V/F separation voltage, PID reference and PID
feedback via communication address 1000H. The data range is -10000 to 10000, corresponding
to -100.00% to 100.00%.
For example, to set main frequency reference to 8000 by using Modbus protocol, first set F0-03
= 9 and send write command 01 06 10 00 1F 40 84 CA. In the command,
To set torque reference to -8000, send write command 01 06 10 00 E0 C0 C4 9A. In the
command, E0C0 is the lowest four bits of the hexadecimal number converted from -8000.
6
- 208 -
01H (settable): AC drive address
06H: write command
1000H: Communication address of giving the toque reference
1F40H: torque reference (converted into decimal 10000)
84CAH: CRC check
Range of frequency reference given via communication is -10000 to 10000,
Note
corresponding to -100.00% to 100.00%. -100.00% corresponds to negative
maximum frequency, 0.00% corresponds to minimum frequency, and 100.00%
corresponds the maximum frequency.
Suppose that F0-10 = 50 Hz, if frequency reference in write command is 1F40H,
converted to decimal 8000, frequency reference that is written is 50 x 80.00%
= 40 Hz.
Sending Message
ADDR
CMD
Parameter address high bits
Parameter address low bits
Data content high bits
Data content low bits
CRC high bits
CRC low bits
Response Message
01H
ADDR
06H
CMD
10H
Parameter address high bits
00H
Parameter address low bits
1FH
Data content high bits
40H
Data content low bits
84H
CRC high bits
CAH
CRC low bits
01H
06H
10H
00H
1FH
40H
84H
CAH