K&R GT600-4T132G User Manual page 309

Ac drive high performance open and closed loop
Table of Contents

Advertisement

Installing Fuse on the Input Side
To prevent accidents caused by short circuit, install fuse on the input side and the fuse
must comply with the UL standard.
Select the fuse according to the following figure.
GT600 Model
GT600-4T18.5GB
GT600-4T22GB
GT600-4T30GB
GT600-4T37GB
GT600-4T45GB
GT600-4T55GB
GT600-4T75GB
GT600-4T90G
GT600-4T110G
GT600-4T132G
GT600-4T160G
GT600-4T200G
GT600-4T220G
GT600-4T250G
GT600-4T280G
GT600-4T315G
GT600-4T355G
GT600-4T400G
GT600-4T450G
Preventing Entry of Foreign Objects
The drive units must be installed in a fireproof cabinet with doors that provide effective
electrical and mechanical protection. The installation must conform to local and regional
laws and regulations, and to relevant IEC requirements.
Grounding
If using an AC drive of the 400 V class, connect the neutral point of the drive power supply
to ground.
FWH Series Fuse
Manufacturer: Bussmann
Rated Current (A)
80
100
100
125
150
200
250
275
325
400
500
600
700
800
800
1000
1000
1400
1400
Appendix A Standards Compliance
Model
FWH-80B
FWH-100B
FWH-100B
FWH-125B
FWH-150B
FWH-200B
FWH-250B
FWH-275B
FWH-325B
FWH-400B
FWH-500B
FWH-600B
FWH-700B
FWH-800B
FWH-800B
170M5016
170M5016
170M6017
170M6017
12
- 307 -

Advertisement

Table of Contents
loading

Table of Contents