6. Description of Parameters
6.9.6 Function of the AO and Pulse Output Terminals
The drive provides an AO terminal (AO1). An extra AO terminal (AO2) is provided by the I/O
extension card (GT60IO1).
Function Code
F5-00
F5-06
F5-07
F5-08
These parameters select the function of the pulse output terminal and the two analog output
terminals.
The pulse output frequency range of the FMP terminal is 0.01 kHz to F5-09 (Max. FMP output
frequency). F5-09 must be set in the range of 0.01 to 100.00 kHz.
The output range of AO1 and AO2 is 0 to 10 V or 0 to 20 mA.
The functions of the three terminals are listed in the following table.
Value
0
1
2
6
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
- 200 -
- 200 -
Parameter Name
FM terminal output mode
FMP function selection
AO1 function selection
AO2 function selection
Output Function
Running frequency
Frequency reference
Output current
Output torque (absolute value)
Output power
Output voltage
Pulse input
AI1
AI2
AI3
Length
Counting value
Communication reference
Motor speed
Output current
Output voltage
Output torque of the motor (actual
value, a percentage of the rated
motor torque)
Output torque of the AC drive
(actual value, a percentage of the
rated AC drive torque )
Max. value in the range indicates Xmax in the following formulas to calculate AO
Note
gain and AO zero offset coefficient.
Setting Range
0: Pulse output (FMP)
1: Digital output (FMR)
0 to 16
0 to 16
0 to 16
Range
(Corresponding to 0.0% to 100.0% of Pulse or
Analog Output Range)
0 to max. frequency
0 to max. frequency
0 to 2 times of rated motor current
0 to 2 times of rated motor torque
0 to 2 times of rated power
0 to 1.2 times of rated AC drive voltage
0.01 to 100.00 kHz
0 to 10 V
0 to 10 V (or 0 to 20 mA)
0 to 10 V
0 to max. set length
0 to max. count value
0.0% to 100.0%
0 to motor speed corresponding to max. output
frequency
0.0 to 1000.0 A
0.0 to 1000.0 V
-2 times of rated motor torque to 2 times of rated
motor torque
-
Default
0
0
0
1