6.2.4 Command Source + Frequency Reference Setting Channel
It is possible to control final frequency reference through command source + frequency reference
setting channel.
Figure 6-29 Command source + main frequency reference setting channel
Operating
Units position
panel
0
Hundreds position
Tens position
Terminal I/O
1
Hundreds position
Serial
Hundreds
Tens position
comms.
position
2
Hundreds position
F0-02
When a command source + frequency reference setting channel is used to control final
frequency reference, both main and auxiliary frequency reference setting channels (F0-03 and
F0-04) become ineffective.
Function Code
F0-27
...
Units position
0
1
9
...
0
0
0
Tens position
...
0
0
0
...
009
Setting
000
001
...
Output
0
1
9
..
Units position
9
0
0
.
..
0
1
9
.
Tens position
..
0
0
0
.
..
010
090
.
Setting
000
..
1
9
.
Output
0
..
Units position
0
0
0
.
..
0
0
0
.
..
0
1
9
.
..
100
.
900
Setting
000
..
Output
0
1
9
.
F0-27
Parameter Name
Command source +
frequency source
No function 0
Digital setting 1
AI1 2
AI2 3
AI3 4
Pulse reference 5
Multi- reference 6
Simple PLC 7
PID reference 8
Serial comms. 9
Setting Range
0: No function
1: Digital setting
2: AI1
3: AI2
4: AI3
5: Pulse reference (DI5)
6: Multi-reference
7: Simple PLC
8: PID reference
9: Serial comms.
Units position: operating panel (keypad
& display) + frequency reference setting
channel
Tens position: terminal I/O control +
frequency reference setting channel
Hundreds position: serial comms. +
frequency reference setting channel
6. Description of Parameters
Final
frequency
reference
Default
000
6
- 133 -