K&R GT600-4T132G User Manual page 163

Ac drive high performance open and closed loop
Table of Contents

Advertisement

6.6.5 Motor Overheat Protection
Function Code
Parameter Name
F9-56
Type of motor temperature
sensor
F9-57
Motor overheat protection
threshold
F9-58
Motor overheat pre-warning
threshold
A motor temperature sensor can be connected to AI3 and PGND on extension I/O card. This
input is used by the drive for motor overheat protection.
When input signal reaches the value set in F9-57, the AC drive detects Err25 and acts as
selected in thousands position in F9-48. When input signal reaches the value set in F9-58, digital
output terminal set for function 39 becomes on.
The drive supports both PT100 and PT1000. Make sure to set sensor type correctly. You can
view motor temperature in U0-34.
6.6.6 Power Dip Ride-through
The power dip ride-through function ensures the system to run continuously at occurrence of
momentary power loss.
When an instantaneous power loss occurs, the AC drive compensates DC bus voltage reduction
with real-time energy feedback by reducing output frequency, preventing the AC drive from
stopping due to undervoltage.
F9-59 = 1: It is applicable to large-inertia applications such as fan, water pump and centrifuge
F9-59 = 2: It is applicable to the textile industry.
Figure 6-46 Power dip ride-through
Power dip ride-through
voltage
Output
frequency
Bus
6. Description of Parameters
Setting Range
0: No temperature sensor
1: PT100
2: PT1000
0° C to 200° C
0° C to 200° C
F9-60
Time (t)
Time (t)
F9-61
Default
0
110° C
90° C
F9-62
6