Example 2: On the condition that current input from AI2 is available, if 0 to 20 mA is input,
it corresponds to voltage input of 0 to 10 V. If 4 to 20 mA is input, it corresponds to voltage
input of 2 to 10 V.
To make current input at AI2 to control frequency reference and correspond 4 to 20 mA to
0 to 50 Hz, the settings are shown in the following figure.
Figure 6-17 Current input at AI2 to control frequency reference
4D/A
0 to 10 V
module
AI2
AO
4 to 20 mA
PLC
GND
GND
Example 3: To make voltage input at AI3 to control frequency reference and correspond 2
to 10 V to 10 to 50 Hz, the settings are shown in the following figure.
Figure 6-18 Voltage input at AI3 to control frequency reference
Select AI3 as main
frequency reference
+10V
setting channel.
Pot.
AI3
F0-03 = 4
(2 kΩ)
-10 to 10 V
F4-33 (hundreds
position) = 2
Select two-point
GND
curve 3 for AI3
Select AI2 as main
frequency reference
Para.
Setting
setting channel.
J9
F4-18
2.00
F0-03 = 2
F4-19
20.0%
F4-33 (units
F4-20
10.00
position) = 2
F4-21
80.0%
Select two-point
F4-22
0.10
curve 2 for AI2
Note:
4 to 20 mA corresponds to 0.0% to 100.0%.
100.0% corresponds to max. frequency (F0-10 = 50.00 Hz).
F4-26 100.0
Setting
Para.
F4-23
2.00
F4-24
20.0%
F4-25
10.00
F4-26
100.0%
F4-24
F4-27
0.10
Note:
2 to 10 V corresponds to 20.0% to 100.0%.
100.0% corresponds to max. frequency (F0-10 = 50.00 Hz).
6. Description of Parameters
Corresponding
percentage (%)
F4-21 100.0
80.0
60.0
40.0
20.0
0.0
F4-19
AI
0 4.0 8.0 12.016.020.0
(mA)
F4-18
F4-20
Correspondin
perc g entage
(%)
80.0
60.0
40.0
20.0
0.0
0.00 2.004.00 6.008.0010.00 AI (V)
F4-23
F4-25
Final
F0-07 (units
frequency
position) = 0
reference
Select main frequency
reference as final
frequency reference.
Final
F0-07 (units
frequency
position) = 0
reference
Select main
frequency reference
as final frequency
reference.
- 115 -
6