K&R GT600-4T132G User Manual page 257

Ac drive high performance open and closed loop
Table of Contents

Advertisement

Jumper
Description
J3
AO2 output
selection: voltage
or current
J1
RS485 terminal
resistor matching
selection
J7
Run/Stop
selection
J8
OP1 connecting
mode selection
S1
AI3, PT100,
PT1000 selection
Setting of jumpers takes top view with main terminals at the bottom of the
Note
card as visual angle. Jumpers are silk-screened on the card.
Meaning
Setting
Voltage
Current
Matching the terminal
resistor
Not matching the
terminal resistor
Run
Stop
If DI connected in
SINK mode, OP1
connected to +24V
If DI connected in
SOURCE mode, OP1
connected to COM
AI3: 1, 2, 3 set to ON
ON
PT1000: 4, 5, 6 set to
ON
ON
PT100: 6, 7, 8 set to
ON
ON
8. Peripherals and Options