K&R GT600-4T132G User Manual page 64

Ac drive high performance open and closed loop
Table of Contents

Advertisement

3. Electrical Installation
3
- 62 -
Terminal Function
Type
Terminal
Power
+10V
GND
supply
+24V
COM
OP
AI1
GND
Analog
inputs
AI2
GND
Digital
DI1
OP
inputs
DI2
OP
DI3
OP
DI4
OP
DI5
OP
Analog
AO1
GND
output
Name
Description
+10 V power
Provides +10 V power supply to an
supply
external unit.
Generally used to supply an external
potentiometer of 1 to 5 kΩ
Max. output current: 10 mA
+24 V power
Provides +24 V power supply to an
supply
external unit.
Generally used to supply the DI/DO
terminals and external sensors
Max. output current: 170 mA
Input terminal for
Connected to +24 V by default.
external power
When DI1 to DI5 need to be driven by
supply
external signals, OP must be disconnected
from + 24 V and connected to an external
power supply.
Analog input 1
Voltage range of inputs: 0 to 10 VDC
Input impedance: 22 kΩ
Analog input 2
Either a voltage or a current input,
determined by jumper J9
Input voltage range: 0 to 10 VDC
Input current range: 0 to 20 mA
Input impedance: 22 kΩ (voltage input),
500 Ω or 250 Ω (current input) decided by
<1>
J10
Digital input 1
Optically-coupled isolation compatible with
dual-polarity inputs
Digital input 2
Input impedance: 1.39 kΩ
Digital input 3
Voltage range for inputs: 9 to 30 V
Digital input 4
High-speed pulse
In addition to having the same features as
input
DI1 to DI4, DI5 can also be used for high-
speed pulse inputs.
Max. input frequency: 100 kHz
Input impedance: 1.03 kΩ
Analog output 1
Either a voltage or a current output,
determined by jumper J7.
Output voltage range: 0 to 10 V
Output current range: 0 to 20 mA.

Advertisement

Table of Contents
loading

Table of Contents