8. Peripherals and Options
Mounting Dimensions of MDBUN Series Braking Unit
Always mount MDBUN series braking unit in an upright position.
8
For use and installation of MDBUN series braking unit, refer to the MDBUN Series Braking Unit
User guide.
- 244 -
Minimum resistance supports operating condition with ED of 10% and longest
Note
time for single braking of 10s.
Default initial braking voltage is 760 V.
The preceding table is for a reference only. You can select resistance and power
of braking resistor based on actual needs. Resistance must not be lower than
the reference value. Power may be higher than the reference value. Selection of
braking resistor model is determined by generation power of motor and is also
related to system inertia, deceleration time and potential energy load. For systems
with high inertia, and/or short deceleration time, and/or frequent braking, select a
braking resistor with higher power and lower resistance value.
60
165
Hot air
100
50
50
Upright
100
Cold air
Unit: mm
110