6. Description of Parameters
6
- 104 -
F4-11 = 1: Two-wire Control Mode 2
In this mode, DI1 is RUN enabled terminal, and DI2 determines running direction. Allocate
DI1 for RUN enabled function and DI2 for running direction.
The parameters are set as below:
Function Code
Parameter Name
F0-02
Command source selection
F4-11
Terminal I/O control mode
F4-00
DI1 function selection
F4-01
DI2 function selection
In this mode,
When SW1 is closed, motor rotates in forward direction with SW2 open.
When SW1 is closed, motor rotates in reverse direction with SW2 closed.
When SW1 is open, motor stops no matter whether SW2 is open or closed.
Figure 6-5 Two-wire 2 sequence wiring diagram
Running Command
SW1
SW2
1
0
1
1
0
0
0
1
Sequence diagram of two-wire control mode 2 is shown in the following figure.
Figure 6-6 Two-wire 2 sequence
SW1 (run
enabled command)
SW2
(running direction)
Motor speed
Value
1
1
1
2
SW1
Forward
Reverse
Stop
Stop
SW2 off
SW2 on
Motor rotates in
Motor rotates in
reverse direction
forward direction
Function Description
Terminal I/O control
Two-wire control mode 2
Forward RUN (FWD)
Reverse RUN (REV)
Running command
DI1
SW2
Running direction
DI2
COM
SW1 run disabled
Stop