6. Description of Parameters
Figure 6-50 Fixed length control
Length pulses input
Length rea
Settings of related function parameters in the preceding figure are as follows:
Function Code
F4-04
Any of F4-00 to F4-09
Any of F5-00 to F5-05
6
6.8.3 Counting
The drive has the counting function. The sampling DI terminal must be set for function 25
"Counter input ". For high pulse frequency, use terminal DI5.
Function Code
Fb-08
Fb-09
In the following figure, When the counting value reaches the level set in Fb-08, digital output
terminal set for function 8 "Set count value reached" becomes on. When the counting value
reaches the level set in Fb-09, digital output terminal set for function 9 "Designated count value
reached" becomes on.
- 174 -
Allocate DI5 with the length
F4-04 = 27
signal pulses counting function.
Number of sampled pulses / Fb-
DI5
07 (Number of pulses per meter)
DIx
Any of F4-04
Allocate DIx with the
to F4-09 = 28
length reset function.
1 2 3
Length
reset input
ched output
Parameter Name
DI5 function selection
DIx function selection
DOx function selection
●
Only length can be calculated according the number of pulses but rotation
Note
direction will not be obtained in fixed length control.
●
An automatic stop system can be implementing by connecting output length
reached signal of relay to the stop input terminal.
Parameter Name
Set count value
Designated count value
Fb-05
Set length
=
Fb-06
Actual length
Clear to 0
10 11 12
Fb-05 = 11
Fb-06 = 11
Setting Range
1 to 65535
1 to 65535
Any of F5-00
Allocate DO with the
to F5-05 = 10
length reached function.
≥
Compare
DO
Reset
1 2
U0-13 = 0
Fb-06 = 0
Setting
Description
27
Length pulses counting input
28
Length reset
10
Length reached
DO outputs the length
reached signal.
Default
1000
1000