AC Output Reactor Installation
Whether to install an AC output reactor on power output side is dependent on actual
situation. Cable connecting AC drive and motor should not be too long; capacitance
enlarges when an over-long cable is used and thus high-harmonics current may be easily
generated.
When an output reactor used, cable length can be increased to the value in below table.
AC Drive Power (kW)
4
5.5
7.5
11
15
18.5
22
≥ 30
AC Output Reactor Model
Recommended AC output reactor manufacturer and models are listed in the following
table.
AC Drive Model
GT600-4T18.5GB
GT600-4T22GB
GT600-4T30GB
GT600-4T37GB
GT600-4T45GB
GT600-4T55GB
GT600-4T75GB
GT600-4T90G
GT600-4T110G
GT600-4T132G
GT600-4T160G
Designation rules
MD-OCL
Inovance AC Output
Reactor
Mark
Rated Current
50
50 A
Rated Voltage (V)
200 to 500
200 to 500
200 to 500
200 to 500
200 to 500
200 to 500
200 to 500
280 to 690
AC Output Reactor Model (K&R)
MD-OCL-50-0.14-4T-1%
MD-OCL-60-0.12-4T-1%
MD-OCL-80-0.087-4T-1%
MD-OCL-90-0.078-4T-1%
MD-OCL-120-0.058-4T-1%
MD-OCL-150-0.047-4T-1%
MD-OCL-200-0.035-4T-1%
MD-OCL-250-0.028-4T-1%
MD-OCL-250-0.028-4T-1%
MD-OCL-330-0.021-4T-1%
MD-OCL-330-0.021-4T-1%
50
0.14
0.14
Mark
0.14 mH
Inductance
Appendix A Standards Compliance
Cable Length Limit (m)
50
70
100
110
125
135
150
150
4T
1%
Mark
Voltage Drop Percentage
1%
1%
Mark
Rated Voltage
4T
380 V
12
- 319 -