8. Peripherals and Options
8
- 254 -
Type
Terminal
Analog input
AI3-PGND Analog input 3
Digital inputs
DI6-OP1
DI7-OP1
DI8-OP1
DI9-OP1
DI10-OP1
Analog output
AO2-GND
PA1- PC1
Relay outputs
(RELAY x 2)
PA2- PC2
RS485
485+/485-
communication
CGND
RS422
CN1
Table 8-6 Jumper descriptions of GT60PC1
Jumper
Description
J2
AI3 input
selection: voltage
or current
Terminal Name
Function Description
Optically-coupled isolation input, supporting
differential voltage input, current input and
temperature detection resistance input
Input voltage range: -10 to 10 VDC
Input current range: -20 to 20 mA
Connect the PT100 or PT1000 temperature
sensor
Input mode determined by DIP switch
S1, multiple functions not supported
simultaneously
Digital input 6
Optically-coupled isolation compatible with
dual-polarity inputs
Digital input 7
Input resistance: 2.4 kΩ
Digital input 8
Voltage range for inputs: 9 to 30 V
Digital input 9
Digital input 10
Analog output 2 Output voltage range: 0 to 10 V
Output current range: 0 to 20 mA
Contact driving capacity:
Relay 1 NO
terminal
250 VAC, 3 A, Cos f = 0.4
Relay 2 NO
30 VDC, 1 A
terminal
RS485
Modbus-RTU communication input and
Communication
output terminal, isolated input
interface
RS485
communication
isolation power
ground
User program
User program downloading port
downloading
Meaning
Voltage
Current
Setting