K&R GT600-4T132G User Manual page 48

Ac drive high performance open and closed loop
Table of Contents

Advertisement

3. Electrical Installation
3
- 46 -
Cable Dimensions and Tightening Torque
Data and models recommended in this section are for reference only.
Note
The user selected cable diameter must not be larger than the terminal
width in the following figures.
Selection of IEC cables is based on:
– Standards EN 60204-1 and IEC 60364-5-52
– PVC insulation
– 40° C ambient temperature and 70° C surface temperature
– Symmetrical cable with copper mesh shield
– A maximum of 9 cables are allowed in a
For North America, the recommended cables in the preceding table must
be copper wires rated 600 V, 75° C.
Figure 3-1 Terminal dimensions of GT600-4T18.5GB/22GB
16
Table 3-2 Recommended cable dimensions and tightening torque of GT600-4T18.5GB/22GB
AC Drive Model
Rated
Input
Current (A)
GT600-
49.5
4T18.5GB
GT600-4T22GB
59
cable tray.
136
15
Power
Crimp
Ground
Input/Output
Terminal
Cable
Cable
Model
2
3 x 10 mm
8-6
10 mm
3 x 6 AWG
8 AWG
2
3 x 16 mm
14-6
16 mm
3 x 4 AWG
8 AWG
17
16
Crimp
Tightening
Screw
Terminal
Torque
Spec.
Model
(N· m)
2
8-6
4.0
M6
2
8-6
4.0
M6

Advertisement

Table of Contents
loading