6. Description of Parameters
6
- 116 -
Pulse Reference (DI5)
Frequency reference is input by means of DI5 (high-speed pulse). Signal specification
of pulse reference is 9 to 30 V (voltage range) and 0 to 100 kHz (frequency range). The
corresponding value 100% of pulse reference corresponds to the value of F0-10 (max.
frequency).
Main frequency reference set via pulse reference and pulse output of the FM
Note
terminal (F5-00 = 1) cannot be used simultaneously.
F4-28 to F4-32 set relationship between pulse input (from DI5 only) and corresponding
percentage. It has the same function and usage as AI curve 1 does. Refer to
Function Code
Parameter Name
F4-28
Pulse min. input
F4-29
Corresponding percentage
of pulse min. input
F4-30
Pulse max. input
F4-31
Corresponding percentage
of pulse max. input
F4-32
Pulse filter time
Figure 6-19 Pulse input at DI5 to control frequency reference
Select pulse as main
frequency reference
setting channel.
DI5
COM
Use pulse signals to control
frequency reference
(valid for DI5 only)
Setting Range
0.00 kHz to F4-30
-100.00% to 100.0%
F4-28 to 50.00 kHz
-100.00% to 100.0%
0.00s to 10.00s
Set the relationship between
the pulse input (from DI5 only)
and the corresponding
percentage via F4-28 to F4-32.
F0-03 = 5
F4-33 (hundreds
position) = 2
Note:
100.0% corresponds to
max. frequency (F0-10).
Default
0.00 kHz
0.0%
50.00 kHz
100.0%
0.10s
F0-07 (units
Final
position) = 0
frequency
reference
Select main frequency
reference as final
frequency reference.