6.6.3 Fault Reset
Function Code
Parameter Name
F9-09
Auto reset times
This function parameter sets permissible times of auto fault reset. If reset times exceed the value
set in this parameter, the AC drive will keep fault status.
●
Undervoltage (Err09) is reset automatically when bus voltage recovers to
Note
normal. It is not included in auto reset times.
●
Short-circuit to ground (Err23) cannot be reset automatically or manually. It can
only be reset after power down.
Function Code
Parameter Name
F9-10
Selection of DO action
during auto reset
This function parameter decides whether digital output terminal set for fault output acts during
the fault reset.
Function Code
Parameter Name
F9-11
Delay of auto reset
This function parameter sets the delay of auto reset after the AC drive detects a fault.
6.6.4 Fault Protection Action Selection
Function Code
Parameter Name
F9-47
Fault protection
action selection 1
F9-48
Fault protection
action selection 2
Setting Range
0 to 20
Setting Range
0: Not act
1: Act
Setting Range
0.1s to 100.0s
Setting Range
0: Coast to stop
1: Stop according to the stop mode
2: Continue to run
Units position: Motor overload (Err11)
Tens position: Input phase loss (Err12)
Hundreds position: Output phase loss (Err13)
Thousands position: External fault (Err15)
Ten thousands position: Communication fault
(Err16)
Units position: Encoder fault (Err20)
0: Coast to stop
1: Switch over to V/F control, stop according to
stop mode
2: Switch over to V/F control, continue to run
Tens position: EEPROM read-write fault (Err21)
0: Coast to stop
1: Stop according to the stop mode
Hundreds position: Reserved
Thousands position: Motor overheat (Err25)
Same as F9-47
Ten thousands position: Accumulative running
time reached (Err26)
Same as F9-47
6. Description of Parameters
Default
0
Default
0
Default
1.0s
Default
00000
00000
6