6.6.3 Fault Reset
Function Code
Parameter Name
F9-09
Auto reset times
This function parameter sets permissible times of auto fault reset. If reset times exceed the value
set in this parameter, the AC drive will keep fault status.
Undervoltage (Err09) is reset automatically when bus voltage recovers to
Note
normal. It is not included in auto reset times.
Short-circuit to ground (Err23) cannot be reset automatically or manually. It can
only be reset after power down.
Function Code
Parameter Name
F9-10
Selection of DO action
during auto reset
This function parameter decides whether digital output terminal set for fault output acts during
the fault reset.
Function Code
Parameter Name
F9-11
Delay of auto reset
This function parameter sets the delay of auto reset after the AC drive detects a fault.
6.6.4 Fault Protection Action Selection
Function Code
Parameter Name
F9-47
Fault protection
action selection 1
F9-48
Fault protection
action selection 2
Setting Range
0 to 20
Setting Range
0: Not act
1: Act
Setting Range
0.1s to 100.0s
Setting Range
0: Coast to stop
1: Stop according to the stop mode
2: Continue to run
Units position: Motor overload (Err11)
Tens position: Input phase loss (Err12)
Hundreds position: Output phase loss (Err13)
Thousands position: External fault (Err15)
Ten thousands position: Communication fault
(Err16)
Units position: Encoder fault (Err20)
0: Coast to stop
1: Switch over to V/F control, stop according to
stop mode
2: Switch over to V/F control, continue to run
Tens position: EEPROM read-write fault (Err21)
0: Coast to stop
1: Stop according to the stop mode
Hundreds position: Reserved
Thousands position: Motor overheat (Err25)
Same as F9-47
Ten thousands position: Accumulative running
time reached (Err26)
Same as F9-47
6. Description of Parameters
Default
0
Default
0
Default
1.0s
Default
00000
00000
6
- 159 -