6. Description of Parameters
6
- 118 -
The four multi-reference terminals have 16 state combinations, corresponding to 16
references, as listed in the following table.
K4
K3
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
ON
ON
ON
Besides multi-speed function, the multi-reference can be also used as PID
Note
reference source or voltage source for V/F separation.
Simple PLC
When simple PLC is used to control frequency reference, the AC drive running frequency
can be selected from any of the 16 frequency reference set points.
Figure 6-21 Using simple PLC to control frequency reference
Running
direction
FC-19
FC-00
FC-18
DO or relay output
K2
K1
Reference Setting Corresponding Pr.
OFF
OFF
Reference 0
OFF
ON
Reference 1
ON
OFF
Reference 2
ON
ON
Reference 3
OFF
OFF
Reference 4
OFF
ON
Reference 5
ON
OFF
Reference 6
ON
ON
Reference 7
OFF
OFF
Reference 8
OFF
ON
Reference 9
ON
OFF
Reference 10
ON
ON
Reference 11
OFF
OFF
Reference 12
OFF
ON
Reference 13
ON
OFF
Reference 14
ON
ON
Reference 15
FC-02
FC-21
...............
FC-01
FC-20
FC-23
FC-00
FC-01
FC-02
FC-03
FC-04
FC-05
FC-06
FC-07
FC-08
FC-09
FC-10
FC-11
FC-12
FC-13
FC-14
FC-15
FC-14
FC-15
Time
250 ms
pulse signal