6. Description of Parameters
6.6.11 Output Overcurrent Protection
This is to provide overcurrent protection for the AC drive.
If the drive's output current is equal to or smaller than the value set in F8-36 and the duration
exceeds the value set in F8-37, digital output terminal set for function 36 becomes on.
Figure 6-47 Output current limit
Function Code
F8-36
6
F8-37
- 164 -
Output current
F8-36
Output
overcurrent
detection signal
Parameter Name
Output overcurrent threshold
Output overcurrent detection
delay
ON
F8-37
Setting Range
% (no detection)
0.0
% to 300.0% (rated motor
0.1
current)
0.00s to 600.00s
Time
Time
Default
200.0%
0.00s