6. Description of Parameters
6.11.8 Current Detection
The drive provides two groups of current detection level and width.
If output current of the AC drive reaches the width, digital output terminals set for functions 28
and 29 become on.
Figure 6-68 Current detection
6.11.9 Timing Function
6
These function parameters define the timing function of the drive. Once it is enabled, the AC
drive starts timing since start. When the set timing running time is reached, the AC drive stops
automatically and digital output terminal set for function 30 becomes on.
The AC drive starts timing from 0 again for each start. You can view remaining timing running
time in U0-20.
- 216 -
Output current
Current detection level
Current detection signal
DO or relay
Function Code
Parameter Name
F8-38
Detection level of current 1
F8-39
Detection width of current 1
F8-40
Detection level of current 2
F8-41
Detection width of current 2
Function Code
Parameter Name
F8-42
Timing function
F8-43
Running time setting channel
F8-44
Running time
ON
ON
OFF
OFF
Setting Range
0.0% to 300.0% (rated motor current)
0.0% to 300.0% (rated motor current)
0.0% to 300.0% (rated motor current)
0.0% to 300.0% (rated motor current)
Setting Range
0: Disabled
1: Enabled
0: Set by F8-44
1: AI1
2: AI2
3: AI3
(100% of analog input corresponds
to the value of F8-44)
0.0 to 6500.0 min
Current detection width
Current detection width
ON
OFF
Default
100.0%
0.0%
100.0%
0.0%
Default
0
0
0.0