6.9.5 Function of the AI Terminals
The drive provides two AI terminals (AI1, AI2). An extra AI terminal (AI3) is provided by I/O
extension card.
Here use AI terminals as DI. When AI input voltage is higher than 7 V, AI is in high level state.
When AI input voltage is lower than 3 V, AI is in low level state. AI is in hysteresis state between
3 V and 7 V.
Figure 6-58 Relationship between AI input voltage and DI state
AI voltage
7 VDC
3 VDC
DI state
Function Code
Parameter Name
A1-07
Function selection for AI1
used as DI
A1-08
Function selection for AI2
used as DI
A1-09
Function selection for AI3
used as DI
A1-10
Active state selection for AI
used as DI
ON
OFF
Setting Range
0 to 59
0 to 59
0 to 59
0: High level active
1: Low level active
Units position: AI1
Tens position: AI2
Hundreds position: AI3
6. Description of Parameters
Time
ON
Default
0
0
0
000
6
- 199 -