K&R GT600-4T132G User Manual page 214

Ac drive high performance open and closed loop
Table of Contents

Advertisement

6. Description of Parameters
RUN command
6
(operation panel)
Forward RUN command
(terminal, communication)
Reverse RUN command
(terminal, communication)
- 212 -
FWD/REV Switchover Dead-zone Time
Figure 6-61 Forward/Reverse run switchover dead-zone time
Output frequency (Hz)
Function Code
Parameter Name
F8-12
Forward/Reverse run
switchover dead-zone time
Reverse Run Prohibited
Figure 6-62 Control of reverse run
Frequency
> 0
reference
Frequency
reference ≤ 0
F8-13
Frequency
reference ≤ 0
Frequency
reference > 0
Function Code
Parameter Name
F8-13
Reverse RUN
selection
F0-09
Running direction
The original direction of motor will be resumed after parameter initialization.
Note
Do not use this function in applications where changing rotation direction of
motor is prohibited after system commissioning is completed.
Forward run
Dead-zone time
Setting Range
0.0s to 3000.0s
0
F0-09
1
0
1
Setting Range
0: Enabled
1: Disabled
0: Run in the default direction (FWD/REV
indicator off)
1: Run in the direction reverse to the
default direction (FWD/REV indicator on)
Reverse run
Default
0.0s
Motor
runs in FWD direction
0
1
runs in REV direction
runs in REV direction
0
1
runs in FWD direction
runs at 0.0 Hz
Default
0
0
- 209 -

Advertisement

Table of Contents
loading

Table of Contents