K&R GT600-4T132G User Manual page 123

Ac drive high performance open and closed loop
Table of Contents

Advertisement

6. Description of Parameters
- 122 -
FC-50 sets running time unit in simple PLC mode. FC-51 selects the setting channel of
reference 0.
Function Code
Parameter Name
FC-50
Time unit of simple
PLC running
FC-51
Reference 0 source
Simple PLC can be either frequency reference setting channel or voltage
Note
reference setting channel for V/F separation.
PID Reference
The PID (Proportional + Integral + Derivative) function uses system feedback for closed-
loop control of variables such as flow, pressure, temperature, and so on.
The purpose of PID control is to keep the drive output as close as possible to a desired
reference via PID adjustment.
Proportional gain (Kp1)
A large value tends to reduce present error, but too large setting will cause system
oscillation.
Integral time (Ti1)
The shorter the integral time is, the faster the error will be predicted. But too short
setting will cause overshoot or system oscillation.
Derivative time (Td1)
The longer the derivative time is, the faster the system will respond to the error. But
too longer setting will cause vibration.
Setting Range
0: s (second)
1: h (hour)
0: Set by FC-00
1: AI1
2: AI2
3: AI3
4: Pulse reference
5: PID
6: Set by preset frequency (F0-08),
modified via terminal UP/DOWN
Default
0
0
6