Para. No.
Para. Name
F8-41
Detection width of current 2
F8-42
Timing function
F8-43
Running time setting channel
F8-44
Running time
F8-45
AI1 input voltage lower limit
F8-46
AI1 input voltage upper limit
F8-47
IGBT temperature threshold
F8-48
Cooling fan working mode
F8-49
Wakeup frequency
F8-50
Wakeup delay time
F8-51
Hibernating frequency
F8-52
Hibernating delay time
F8-53
Running time threshold this time
F8-54
Output power correction
coefficient
F8-55
Deceleration time for emergency
stop
Group F9: Fault and Protection
F9-00
Motor overload protection
F9-01
Motor overload protection gain
F9-02
Motor overload pre-warning
coefficient
F9-03
Overvoltage protection gain
F9-04
Overvoltage protection voltage
F9-07
Detection of short-circuit to ground
upon power-on
F9-08
Braking unit applied voltage
F9-09
Auto reset times
F9-10
Selection of DO action during auto
reset
F9-11
Delay of auto reset
F9-12
Input phase loss/pre-charge relay
protection
F9-13
Output phase loss protection
F9-14
1st fault type
F9-15
2nd fault type
F9-16
3rd (latest) fault type
F9-17
Frequency upon 3rd fault
F9-18
Current upon 3rd fault
F9-19
Bus voltage upon 3rd fault
Setting Range
0.0% to 300.0% (rated motor
current)
0, 1
0 to 3
0.0 to 6500.0 min
0.00 V to F8-46
F8-45 to 10.00 V
0° C to 100° C
0, 1
F8-51 to max. frequency
(F0-10)
0.0s to 6500.0s
0.00 Hz to wakeup frequency
(F8-49)
0.0s to 6500.0s
0.0 to 6500.0 min
0.0% to 200.0%
0s to 6553.5s
0, 1
0.20 to 10.00
50% to 100%
0 (no overvoltage stall) to
100
650 to 800 V
00 to 11
650 to 800 V
0 to 20
0, 1
0.1s to 100.0s
00 to 11
00 to 11
0 to 55
0 to 55
0 to 55
-
-
-
Appendix B Parameter Table
Default
Property Page
0.0%
0
0
0.0 min
3.10 V
6.80 V
75° C
0
0.00 Hz
0.0s
0.00 Hz
0.0s
0.0 min
100.0%
Model
dependent
1
1.00
80%
30
770 V
01
-
760 V
0
0
1.0s
11
01
-
-
-
-
-
-
-
-
-
-
-
-
12
- 339 -