Item
Output terminals
Display and
LED display
operating
Key locking and function selection
panel
Protections
Phase loss protection
Instantaneous overcurrent protection
Overvoltage protection
Undervoltage protection
Overheat protection
Overload protection
Overcurrent protection
Braking protection
Short-circuit protection
Environment
Installation location
Altitude
Operation temperature
Storage temperature
Humidity
Vibration
Pollution degree
Overvoltage category
Description
Standard
Single high-speed pulse output terminal (open-collector)
for a square-wave signal output in the frequency range 0
to 100 kHz
Single digital output (DO) terminal
Single relay output terminal
Single analog output (AO) terminal that supports either
a current output in the range 0 to 20 mA or a voltage
output in the range 0 to 10 V.
Expanded capacity:
Single extra DO terminal
Single extra relay output terminal
Single extra AO terminal that supports either a current
output in the range 0 to 20 mA or a voltage output in the
range 0 to 10 V.
The 6-character LED display shows parameter values.
Keys on the control panel can be locked or partially
locked electronically to prevent accidental operation.
The range of some functions can be limited to a
permitted range to prevent incorrect settings.
Input phase loss protection
Output phase loss protection
Stop when 250% of rated output current is exceeded
Stop when the DC bus voltage is above 820 V
Stop when the DC bus voltage is below 350 V
Protection triggered when the AC Drive bridge gets
overheated.
Stop after running at 150% of rated current for 60
seconds (for GT600-4T450G, stop after running at
130% of rated current for 60 seconds)
Stop when 2.5 times of rated current of the AC drive is
exceeded.
Braking unit overload protection
Braking resistor short-circuit protection
Output phase-to-phase short-circuit protection
Output phase-to-ground short-circuit protection
Install the AC Drive where it is indoors and protected
from direct sunlight, dust, corrosive or combustible
gases, oil smoke, vapour, ingress from water or any
other liquid, and salt.
Below 1000 m
If the altitude exceeds 1000 m, de-rate the drive
1.5 De-rating.
according to section
Max. 3000 m for LVD directive requirement.
–10° C to +50° C
If the ambient temperature is not in this range, de-rate
the drive according to section
–20° C to +60° C
Less than 95% RH non-condensing.
Less than 5.9 m/s² (0.6 g).
PD2
OVC III
1. Product Information
1.5 De-rating.