6. Description of Parameters
6.9.2 Function of DO Terminals
The drive provides a digital output (DO) terminal, an analog output (AO) terminal, a relay terminal
and an FM terminal (either high-speed pulse output or open-collector output).
Extra AO terminal (AO2), relay terminal (relay2) and DO terminal (DO2) are provided by the I/O
extension card.
Function Code
F5-00
This function parameter is a programmable multiplexing terminal and determines whether FM
terminal is high-speed pulse output (FMP) or open-collector output (FMR). When used for high-
speed pulse output, max. output frequency is 100 kHz. For details, see the description of
Function Code
F5-01
F5-02
F5-03
F5-04
F5-05
These five function parameters select the function of the five digital output terminals. T/A-T/B-T/
C is the relay of the drive and P/A-P/B-P/C is the relay on the I/O extension card.
6
The functions of the digital output terminals are described in the following figure.
Value Function
0
1
2
3
4
5
6
7
8
9
- 194 -
Parameter Name
FM terminal output mode
Parameter Name
FMR function selection
Relay (T/A-T/B-T/C) function selection
Extension card relay (P/A-P/B-P/C)
function selection
DO1 function selection
Extension card DO2 function
selection
Description
No output
Terminal has no function.
AC drive running
When the AC drive is running and has output frequency (can be
zero), terminal set for this function becomes on.
Fault output
When a fault occurs and the AC drive stops due to the fault, terminal
set for this function becomes on.
Frequency level
Refer to descriptions of
detection 1 output
Frequency reached
Refer to descriptions of
Zero-speed
When output frequency is 0 during drive running, terminal set for this
running (no output
function becomes on. When the drive stops, terminal becomes off.
at stop)
Motor overload
The AC drive judges motor overload pre-warning according to pre-
pending
warning threshold before performing overload protection. If this
threshold is exceeded, terminal set for this function becomes on. For
motor overload parameters, see descriptions of
AC drive overload
Terminal set for this function becomes on 10s before the AC drive
pending
performs overload protection.
Set count value
Terminal set for this function becomes on when count value reaches
reached
the value set in Fb-08.
Designated count
Terminal set for this function becomes on when count value reaches
value reached
value set in Fb-09.
Setting Range
0: Pulse output (FMP)
1: Digital output (FMR)
Setting Range
0 to 41
0 to 41
0 to 41
0 to 41
0 to 41
and
.
Default
0
.
Default
0
2
0
1
4
to
.