6. Description of Parameters
Function Code
F9-59
F9-60
F9-61
F9-62
F9-71
F9-72
F9-73
6.6.7 Load Lost Protection
Function Code
6
F9-63
F9-64
F9-65
These function parameters define the load lost protection function.
When output current of the AC drive falls below detection level (F9-64) for longer than time set in
F9-65, the AC drive automatically reduces output frequency to 7% of rated frequency. Once load
recovers during protection, the AC drive accelerates to frequency reference.
- 162 -
Parameter Name
Power dip ride-through
function selection
Threshold of power dip ride-
through function disabled
Judging time of bus voltage
recovering from power dip
Threshold of power dip ride-
through function enabled
Power dip ride-through gain
Kp
Power dip ride-through
integral coefficient
Deceleration time of power
dip ride-through
In bus voltage constant control, when line voltage recovers, the AC drive
Note
accelerates to target frequency.
In deceleration to stop mode, when line voltage recovers, the AC drive continues
to decelerate to 0 Hz and stops. The AC drive will not be started until it receives
RUN command again.
Parameter Name
Load lost protection
Load lost detection level
Load lost detection time
Setting Range
0: Disabled
1: Bus voltage constant control
2: Decelerate to stop
85% to 120%
0.1s to 10.0s
60% to 85% (standard bus voltage)
0 to 100
0 to 100
0.0s to 300.0s
Setting Range
0: Disabled
1: Enabled
0.0% to 100.0% (rated motor current)
0.0s to 60.0s
Default
0
85%
0.5s
80.0%
40
30
20.0s
Default
0
10.0%
1.0s