6. Description of Parameters
6
- 124 -
Function Code
Parameter Name
FA-08
PID output limit in
reverse direction
FA-08: In some applications a high PID output in reverse direction may introduce adverse
reactions and so a limit need to be applied".
When frequency reference setting channel is purely PID reference, FA-08 limits the
output in reverse direction.
When frequency reference setting channel is main frequency reference + PID
reference, FA-08 limits the calculation result in reverse direction.
Function Code
Parameter Name
FA-09
PID error limit
FA-09: This function helps to make the AC drive output accurate and stable.
Function Code
Parameter Name
FA-10
PID differential limit
FA-10 applies a limit to PID differential output as a large output can cause excessive
system oscillation.
Function Code
Parameter Name
FA-11
PID reference change time
FA-11 sets time it takes PID reference to change from 0.0% to 100.0%. PID reference
changes linearly based on the time set in this parameter, reducing negative impact of
sudden PID reference change.
Function Code
Parameter Name
FA-12
PID feedback filter time
FA-13
PID output filter time
FA-12 filters the PID feedback, which helps to lower interference on PID feedback but
slows system response performance.
FA-13 filters the PID output frequency, which helps to drop off mutation of the AC drive
output frequency but slows system response performance.
Setting Range
0.00 Hz to max. frequency
Setting Range
0.0% to 100.0%
Setting Range
0.00% to 100.00%
Setting Range
0.00s to 650.00s
Setting Range
0.00s to 60.00s
0.00s to 60.00s
Default
2.00 Hz
Default
0.0%
Default
0.10%
Default
0.00s
Default
0.00s
0.00s