K&R GT600-4T132G User Manual page 198

Ac drive high performance open and closed loop
Table of Contents

Advertisement

Value Function
33
34
35
36
37
38
39
40
41
Function Code
F5-17
F5-18
6
F5-19
F5-20
F5-21
These parameters set output delay of terminals FMR, relay1, relay2, DO1 and DO2 from state
change.
Function Code
F5-22
This function parameter sets active mode of terminals FMR, relay1, relay2, DO1 and DO2.
- 196 -
- 196 -
Description
Reverse running
Terminal set for this function becomes on when the AC drive runs in
reverse direction.
Zero current
Refer to descriptions of
IGBT temperature
Terminal set for this function becomes on when heatsink
reached
temperature of AC Drive IGBT (F7-07) reaches IGBT temperature
threshold (F8-47).
Output current
Refer to descriptions of
exceeding limit
Frequency lower
The terminal set for this function becomes on when the running
limit reached
frequency reaches the frequency lower limit. When the drive stops,
(having output at
the terminal remains on.
stop)
Alarm output
If a fault occurs on the AC drive and the AC drive continues to run,
terminal set for this function outputs an alarm signal.
Motor overheat
Terminal set for this function becomes on when motor temperature
pending
reaches value set in F9-58 (Motor overheat pending threshold). You
can view motor temperature by using U0-34.
Current running
Terminal set for this function becomes on when current running time
time reached
of the AC drive exceeds value set in F8-53.
Fault output
When a fault occurs on the AC drive (except undervoltage), terminal
set for this function becomes on.
Parameter Name
FMR output delay
Relay 1 output delay
Relay 2 output delay
DO1 output delay
DO2 output delay
Parameter Name
DI active mode
selection 1
0: Positive logic active
Digital output terminal becomes active when being connected with COM, and inactive when
being disconnected from COM.
1: Negative logic active
Digital output terminal becomes active when being disconnected from COM, and inactive
when being connected with COM.
and
and
Setting Range
0.0s to 3600.0s
0.0s to 3600.0s
0.0s to 3600.0s
0.0s to 3600.0s
0.0s to 3600.0s
Setting Range
0: Positive logic active
1: Negative logic active
Units position: FMR active mode
Tens position: Relay1 active mode
Hundreds position: Relay2 active mode
Thousands position: DO1 active mode
Ten thousands position: DO2 active mode
6. Description of Parameters
.
.
Default
0.0s
0.0s
0.0s
0.0s
0.0s
Default
00000