Troubleshooting For Ah10Pfbs-5A - Delta AH500 Hardware Operation Manual

Hide thumbs Also See for AH500:

Advertisement

12.3.9 Troubleshooting for AH10PFBS-5A

Error
Description
code
The node address of
16#A4F0
AH10PFBS-5A exceeds the
valid range.
16#A4F1
Internal hardware error
16#A4F2
Parameter error
16#A4F3
Configuration error
16#A4F4
GPIO detection error
AH10PFBS-5A enters the mode
16#A4F5
of factory test.
1.
AH10PFBS-5A has not
been connected to the
PROFIBUS-DP network.
2.
PROFIBUS-DP master has
not configured
16#A4F6
AH10PFBS-5A slave or the
configured node address of
AH10PFBS-5A is
inconsistent with that of the
actually connected one.
C h a p t e r 1 2 Tr o u b l e s h o o t i n g
Remedy
The node address of AH10PFBS-5A must be in the range
of 1 to 125.
If the error still exists after repowering AH10PFBS-5A,
replace it with a new one.
Check whether the GSD file AH10PFBS-5A is using is
correct.
Check whether the GSD file AH10PFBS-5A is using is
correct.
If the error still exists after repowering AH10PFBS-5A,
replace it with a new one.
Repower AH10PFBS-5A after setting its node address
between 1~125.
1.
Check whether the communication cable between
AH10PFBS-5A and PROFIBUS-DP master is in
normal status.
2.
Ensure that AH10PFBS-5A slave has been configured
to PROFIBUS-DP master and the configured node
address of AH10PFBS-5A is consistent with that of the
actually connected one.
3.
Check whether the PROFIBUS-DP master works
normally.
1 2 - 5 9