9.2.7

Downloading Routing Tables

After users make sure that the network architecture they create is correct, they can download the routing
tables produced to PLCs. The routing data stored in a PLC is data related to the PLC itself, and therefore the
routing tables downloaded to nodes are different. The users have to download the routing tables produced to
nodes in the working area.
The users can download the routing tables produced to nodes one by one, or download the routing tables
produced to nodes at the same time. If the users want to download the routing tables produced to nodes, the
Routing Mode checkbox in the Select a Driver window must be unselected. Please refer to section 9.1.3 for
more information.
Single node
The users have to select a node in the working area. Only AH500 series CPU modules support routing. If
the users select a device which is not an AH500 series CPU module, a routing table can not be
downloaded to the device.
After the users click Download to PLC on the PLC menu, or
Download window will appear. The users can also open the Optional Download window by right-clicking
the device they select, and clicking Download to PLC on the context menu. After the users select the
Routing Table checkbox in the Optional Download window, and click OK, a routing table will be
downloaded to the device.