Download Print this page

Viewing Error Logs - Delta AH500 Hardware Operation Manual

Hide thumbs Also See for AH500:

Advertisement

A H 5 0 0 H a r d w a r e a n d O p e r a t i o n M a n u a l

12.1.4 Viewing Error Logs

When an error occurs, a corresponding error code generated by a system is recorded in a CPU module.
Twenty error logs at most can be stored in the CPU module. If there are more than twenty error logs generated,
the oldest error log will be overwritten by the latest error log. However, if a memory card is installed in the CPU
module, the twenty error logs are automatically backed up in the memory card before the oldest error log is
overwritten. One thousand error logs at most can be stored in the memory card. If there are more than 1000
error logs which will be stored in the memory card, the twenty oldest error logs will be overwritten by the twenty
latest error logs.
(1) After ISPSoft is started, click System Log on the PLC menu.
(2) The System Log window is as follows. Users can refresh the error logs by clicking Refresh, and clear the
error logs in the window and the CPU module by clicking Clear.
Rack number & Slot number: If errors are generated by extension modules, the racks and the slots on
Module ID: The IDs of CPU modules, or those of extension modules
Error Code: The error codes for error logs
Date & Time: The time when errors occur
The newer error log is exhibited in the upper row.
The description related to an error log is in the last field.
1 2 - 4
which the extension modules are installed are recorded in these
columns. If no rack number and no slot number are recorded, it means
that an error occurs in a CPU module.