Delta AH500 Hardware Operation Manual page 560

Hide thumbs Also See for AH500:

Advertisement

Error
Description
code
The checksum of the command
16#2021
received is incorrect.
(SM102/SM103)
The format of the command used
in MODRW does not conform to
16#2022
the ASCII format.
(SM102/SM103)
There is a communication
16#2023
timeout when MODRW is
executed. (SM120/SM103)
The setting value of the
16#2024
communication timeout is invalid.
(SM120/SM103)
There is a communication
16#2025
timeout when RS is executed.
(SM120/SM103)
The RS communication interrupt
16#2026
is abnormal. (SM102/104)
The execution of FWD is
16#2027
abnormal. (SM102/103)
The execution of REV is
16#2028
abnormal. (SM102/103)
The execution of STOP is
16#2029
abnormal. (SM102/103)
The execution of RSDT is
16#202A
abnormal. (SM102/103)
The execution of RSTEF is
16#202B
abnormal. (SM102/103)
16#202C
I/O interrupt service routine
|
0-31 does not exist.
16#204B
16#2054
I/O interrupt service routine
|
40-251 does not exist.
16#2127
An action in a sequential function
chart is incorrectly assigned
16#2128
qualifiers related to time.
(SM0/SM1)
The modifier R is assigned to an
16#2129
action in a sequential function
chart incorrectly. (SM0/SM1)
MC/MCR instruction cannot be
16#212A
used in interrupt or subroutine.
(SM5)
Ethernet speed cannot be
16#6000
detected (SM1106)
16#6001
Illegal IP address (SM1107)
C h a p t e r 1 2 Tr o u b l e s h o o t i n g
Remedy
1. Check whether there is noise, and retry the sending of
the command.
2. Check whether the slave operates normally.
Make sure that the format of the command conforms to
the ASCII format.
Check whether the slave operates normally, and whether
the connection is normal.
1. Check the program and the related special data
registers.
2. Set the communication port parameter for the CPU
module in HWCONFIG again.
Check whether the slave operates normally, and whether
the connection is normal.
Check whether the interrupt service routine used with RS
is downloaded.
Refer to AH500 Programming Manual, and check the
instruction FWD.
Refer to AH500 Programming Manual, and check the
instruction REV.
Refer to AH500 Programming Manual, and check the
instruction STOP.
Refer to AH500 Programming Manual, and check the
instruction RSDT.
Refer to AH500 Programming Manual, and check the
instruction RSTEF.
Download I/O interrupt service routine 0-31
(I/O interrupt 0-31).
Download I/O interrupt service routine 40-251
(I/O interrupt 40-251).
Check whether the action in the sequential function chart
is assigned qualifiers related to time.
Check whether the reset modifier assigned to the action
in the sequential function chart conflicts with another
modifier assigned to the action in the sequential function
chart.
Check the program, compile the program again, and
download the program again.
Check the Ethernet cable securely connected and is
functioning normally.
1. Check the program and the related special data
registers.
2. Set the Ethernet parameter for the CPU module in
HWCONFIG again.
1 2 - 11