A H 5 0 0 H a r d w a r e a n d O p e r a t i o n M a n u a l
1.
Setting a PROFIBUS node address
The address knobs of AH10PFBS-5A are used for setting the node address of AH10PFBS-5A on a
PROFIBUS-DP network. There are two address knobs. They are a knob corresponding to x16
a knob corresponding to x16
The range for setting the node address is described below.
Address
H'1~H'7D
H'0 or H'7E~H'FF
Example: If users need to set the node address of AH10PFBS-5A to 26 (decimal value), they have to
turn the knob corresponding to x16
26 (decimal value)=1A (hexadecimal value)=1x16
Points for attention:
If users set the node address of AH10PFBS-5A when AH10PFBS-5A is not supplied with power,
they have to power AH10PFBS-5A after the node address of AH10PFBS-5A is set.
If users change the node address of AH10PFBS-5A when AH10PFBS-5A is powered, the
change will not take effect immediately after the node address of AH10PFBS-5A is changed, and
it will take effect after the users cut off the power supplied to AH10PFBS-5A and then power
AH10PFBS-5A again.
To prevent the address knobs on AH10PFBS-5A from being scratched, please carefully use a
slotted screwdriver to rotate the address knobs on AH10PFBS-5A.
2.
Definitions of the pins in the PROFIBUS-DP port
Pin
1
2
3
4
5
6
7
8
9
2 - 7 6
1
. The range for one address knob is 0~F.
Definition
Valid PROFIBUS address
Invalid PROFIBUS address
1
to "1", and the knob corresponding to x16
PIN name
--
--
RxD/TxD-P
Sending/receiving data (P (B))
--
DGND
Data reference potential (C)
VP
Supplying positive voltage
--
RxD/TxD-N
Sending/receiving data (N (A))
--
1
0
+Ax16
.
Description
N/C
N/C
N/C
N/C
N/C
0
, and
1
x16
0
x16
0
to "A".
9
5
6
1