Wiring the Differential Input Terminals
4.13.5.1
The direct-current signals ranging in voltage from 5 V to 24 V can pass through the high-speed input terminals
X0.0+~X0.3+, X0.0-~X0.3-, X0.8+~X0.15+, and X0.8-~X0.15- on AH20MC-5A. The frequency of input signals
can be up to 200 kHz. These high-speed input terminals are connected to a differential (two-wire) line driver.
Wiring differential input terminals (The wiring below is used for high speed and high noise.)
E ncod er o utp ut
A
B
4.13.5.2 Transistor Output Circuit
AH20MC-5A
Direct-current power supply
The output terminals of a transistor module are open-collector output terminals. If Y0.8 is a pulse train
output terminal of a transistor module, the output current passing through its output pull-up resistor must
be greater than 0.1 A to ensure that the transistor module operates normally.
A relay or a solenoid valve is used as a DC load. A diode is connected in parallel to absorb the surge
voltage which occurs when the load is OFF.
A+
A-
B+
B-
LED
C h a p t e r 4 I n s t a l l i n g H a r d wa r e a n d W i r i n g
-
AH20 MC- 5A h ig h sp eed i np ut
X0 .0+
X0 .0-
X0.1 +
X0.1 -
Load
Y0.8
< 0.5A
C0
Transistor output
Emergency stop
Fuse
4 - 11 7