Error
Description
code
The device used in the Ether Link
16#6301
exceeds the device range.
The length of the data exchanged
16#6302
in the Ether Link exceeds the
limit.
The node used in the
16#6305
communication command is
different from the local node.
The module ID or the setting of
16#630A
the module is different from the
setting in the Ether Link.
The setting of the netmask
address for the CPU or the
16#630B
module is different from the
setting in the Ether Link.
An error occurs when a data
16#6500
exchange function is initialized.
(SM699)
An error occurs during the
16#860F
process of system restore
C h a p t e r 1 2 Tr o u b l e s h o o t i n g
Remedy
Check whether the device used in the Ether Link is within
the device range supported by the CPU module.
Check whether the length of the data exchanged in the
Ether Link is within the range supported by the CPU
module.
Check the setting of the Ether Link in NWCONFIG, and
download it again.
1. Check the setting of the parameter in HWCONFIG.
2. Check the setting of the Ether Link in NWCONFIG.
1. Check the setting of the parameter in HWCONFIG.
2. Check the setting of the Ether Link in NWCONFIG.
Check whether the sum of the number of Modbus TCP
data exchange blocks and the number of the Ether link
data exchange blocks exceeds the system specifications,
and download the setting again.
Some error in the backup file or the backup file does not
exist in the appointed file path. Recreate the backup file
and run the system restore again. If this error persists,
contact the local authorized distributors.