12.2.6 Troubleshooting for EtherNet/IP

Error
Code
16#B100
I/O Connections Duplicated
16#B106
Ownership Conflict
16#B110
Target for Connection not Configured
16#B111
Adapter RPI Not Supported
16#B113
Out of Connections
16#B119
Non-Listen Only Not Opened
16#B127
Invalid Originator to Target Size
16#B128
Invalid Target to Originator Size
The configuration path parameters in the
16#B129
EDS file are mismatched.
16#B12D
Consumed Tag does not exist.
16#B12E
Produced Tag does not exist.
16#B203
I/O Connection Timeout
16#B204
Unconnected Request Timeout
Network Bandwidth NOT Available for
16#B302
Data
16#B315
Invalid Segment in Connection Path
Description
C h a p t e r 1 2 Tr o u b l e s h o o t i n g
How to fix them
1. Check if the system has created the I/O
connections.
2. Change the connection type to Listen Only.
1. Check the scanner owner.
2. Reconfigure the invalid scanner.
3. Change the connection to multicast.
1. Check the I/O connection status.
2. Activate the I/O connections again.
Check the RPI for the adapter.
1. Check if the connection exceeds the limit.
2. Reduce the number of the product
connection.
1. Check if the system has created the I/O
connections.
2. Check the scanner I/O connection status.
1. Check the module number and the product
setup file to see if they are matched.
2. Check the output size in the connection
parameters.
1. Check if the product information and the EDS
file are matched.
2. Reload the EDS file.
3. Ask the vendor of the device for the EDS file.
Check if the parameters in the consumed tag are
correctly set.
Check if the parameters in the produced tag are
correctly set.
1. Check the network connection status.
2. Check if the module is working fine.
3. Increase the RPI value.
No response from the adapter; check if the
power and the network connection of the
adapter are working properly.
1. Check the I/O connection limit between the
scanner and the adapter.
2. Increase the RPI value or reduce the number
of the connections.
Check the module number and the product
setup file to see if they are matched.
1 2 - 2 7